WIND ENERGY SYSTEMS - Cd3wd
WIND ENERGY SYSTEMS - Cd3wd WIND ENERGY SYSTEMS - Cd3wd
Chapter 5—Electrical Network 5–26 E pu = V pu + I pu (jX s,pu )=1+0.693/33.69 o (1.38)/90 o = 1+0.956/123.69 o =1− 0.530 + j0.796 = 0.470 + j0.796 = 0.924/59.46 o The per unit generator inductance per phase is The actual generator inductance per phase is L pu = X s,pu = 1.38 =1.38 ω pu 1 The per unit load capacitance per phase is L = L pu L base =1.38(14.7) = 20.3 mH C pu = The actual load capacitance per phase is 1 = 1 X C,pu ω pu 0.8(1) =1.25 C = C pu C base =1.25(480) = 600 µF The base of any device such as an electrical generator, motor, or transformer is always understood to be the nameplate rating of the device. The per unit impedance is usually available from the manufacturer. Sometimes the base values need to be changed to a common base when several devices are connected together. Solving an electrical circuit requires either the actual impedances or the per unit impedances referred to a common base. The per unit impedance on the old base can be converted to the per unit impedance for the new base by Example Z pu,new = Z pu,old ( Vbase,old V base,new ) 2 Sbase,new S base,old (46) A single-phase distribution transformer secondary is rated at 60 Hz, 10 kVA, and 240 V. The open circuit voltage V oc is 240 V. The per unit series impedance of the transformer is Z = 0.005 + j0.03. Two electric heaters, one rated 1500 W and 230 V, and the other rated at 1000 W and 220 V, are connected to the transformer. Find the per unit transformer current I pu and the magnitude of the actual load voltage V 1 , as shown in Fig. 15. Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001
Chapter 5—Electrical Network 5–27 Figure 15: Single-phase transformer connected to two resistive loads. The first step is to get all impedance values computed on the same base. Any choice of base will work, but minimum effort will be exerted if we choose the transformer base as the reference base. This yields V base = 240 V and S base = 10 kVA. The per unit values of the electric heater resistances would be unity on their nameplate ratings. The per unit values referred to the transformer rating would be R 1,pu =(1) ( ) 2 230 10 240 1.5 =6.12 R 2,pu =(1) ( ) 2 220 10 240 1 =8.40 The equivalent impedance of these heaters in parallel would be The per unit current is then I pu = The load voltage magnitude is V oc,pu Z pu + R pu = R pu = 6.12(8.40) 6.12 + 8.40 =3.54 1 =0.282/ − 0.48o 0.005 + j0.03 + 3.54 |V 1 | = I pu R pu V base =0.282(3.54)(240) = 239.6 V The voltage V 1 has decreased only 0.4 V from the open circuit value for a current of 28.2 percent of rated. This indicates the voltage varies very little with load changes, which is quite desirable for transformer outputs. 5 THE INDUCTION MACHINE A large fraction of all electrical power is consumed by induction motors. For power inputs of less than 5 kW, these may be either single-phase or three-phase, while the larger machines are Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001
- Page 165 and 166: Chapter 4—Wind Turbine Power 4-29
- Page 167 and 168: Chapter 4—Wind Turbine Power 4-31
- Page 169 and 170: Chapter 4—Wind Turbine Power 4-33
- Page 171 and 172: Chapter 4—Wind Turbine Power 4-35
- Page 173 and 174: Chapter 4—Wind Turbine Power 4-37
- Page 175 and 176: Chapter 4—Wind Turbine Power 4-39
- Page 177 and 178: Chapter 4—Wind Turbine Power 4-41
- Page 179 and 180: Chapter 4—Wind Turbine Power 4-43
- Page 181 and 182: Chapter 4—Wind Turbine Power 4-45
- Page 183 and 184: Chapter 4—Wind Turbine Power 4-47
- Page 185 and 186: Chapter 4—Wind Turbine Power 4-49
- Page 187 and 188: Chapter 4—Wind Turbine Power 4-51
- Page 189 and 190: Chapter 4—Wind Turbine Power 4-53
- Page 191 and 192: Chapter 5—Electrical Network 5-1
- Page 193 and 194: Chapter 5—Electrical Network 5-3
- Page 195 and 196: Chapter 5—Electrical Network 5-5
- Page 197 and 198: Chapter 5—Electrical Network 5-7
- Page 199 and 200: Chapter 5—Electrical Network 5-9
- Page 201 and 202: Chapter 5—Electrical Network 5-11
- Page 203 and 204: Chapter 5—Electrical Network 5-13
- Page 205 and 206: Chapter 5—Electrical Network 5-15
- Page 207 and 208: Chapter 5—Electrical Network 5-17
- Page 209 and 210: Chapter 5—Electrical Network 5-19
- Page 211 and 212: Chapter 5—Electrical Network 5-21
- Page 213 and 214: Chapter 5—Electrical Network 5-23
- Page 215: Chapter 5—Electrical Network 5-25
- Page 219 and 220: Chapter 5—Electrical Network 5-29
- Page 221 and 222: Chapter 5—Electrical Network 5-31
- Page 223 and 224: Chapter 5—Electrical Network 5-33
- Page 225 and 226: Chapter 5—Electrical Network 5-35
- Page 227 and 228: Chapter 5—Electrical Network 5-37
- Page 229 and 230: Chapter 5—Electrical Network 5-39
- Page 231 and 232: Chapter 5—Electrical Network 5-41
- Page 233 and 234: Chapter 5—Electrical Network 5-43
- Page 235 and 236: Chapter 5—Electrical Network 5-45
- Page 237 and 238: Chapter 5—Electrical Network 5-47
- Page 239 and 240: Chapter 5—Electrical Network 5-49
- Page 241 and 242: Chapter 5—Electrical Network 5-51
- Page 243 and 244: Chapter 5—Electrical Network 5-53
- Page 245 and 246: Chapter 5—Electrical Network 5-55
- Page 247 and 248: Chapter 5—Electrical Network 5-57
- Page 249 and 250: Chapter 5—Electrical Network 5-59
- Page 251 and 252: Chapter 5—Electrical Network 5-61
- Page 253 and 254: Chapter 6—Asynchronous Generators
- Page 255 and 256: Chapter 6—Asynchronous Generators
- Page 257 and 258: Chapter 6—Asynchronous Generators
- Page 259 and 260: Chapter 6—Asynchronous Generators
- Page 261 and 262: Chapter 6—Asynchronous Generators
- Page 263 and 264: Chapter 6—Asynchronous Generators
- Page 265 and 266: Chapter 6—Asynchronous Generators
Chapter 5—Electrical Network 5–26<br />
E pu = V pu + I pu (jX s,pu )=1+0.693/33.69 o (1.38)/90 o<br />
= 1+0.956/123.69 o =1− 0.530 + j0.796<br />
= 0.470 + j0.796 = 0.924/59.46 o<br />
The per unit generator inductance per phase is<br />
The actual generator inductance per phase is<br />
L pu = X s,pu<br />
= 1.38 =1.38<br />
ω pu 1<br />
The per unit load capacitance per phase is<br />
L = L pu L base =1.38(14.7) = 20.3 mH<br />
C pu =<br />
The actual load capacitance per phase is<br />
1<br />
= 1<br />
X C,pu ω pu 0.8(1) =1.25<br />
C = C pu C base =1.25(480) = 600 µF<br />
The base of any device such as an electrical generator, motor, or transformer is always<br />
understood to be the nameplate rating of the device. The per unit impedance is usually<br />
available from the manufacturer.<br />
Sometimes the base values need to be changed to a common base when several devices are<br />
connected together. Solving an electrical circuit requires either the actual impedances or the<br />
per unit impedances referred to a common base. The per unit impedance on the old base can<br />
be converted to the per unit impedance for the new base by<br />
Example<br />
Z pu,new = Z pu,old<br />
(<br />
Vbase,old<br />
V base,new<br />
) 2<br />
Sbase,new<br />
S base,old<br />
(46)<br />
A single-phase distribution transformer secondary is rated at 60 Hz, 10 kVA, and 240 V. The open<br />
circuit voltage V oc is 240 V. The per unit series impedance of the transformer is Z = 0.005 + j0.03.<br />
Two electric heaters, one rated 1500 W and 230 V, and the other rated at 1000 W and 220 V, are<br />
connected to the transformer. Find the per unit transformer current I pu and the magnitude of the<br />
actual load voltage V 1 , as shown in Fig. 15.<br />
Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001