19.06.2015 Views

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

WIND ENERGY SYSTEMS - Cd3wd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 5—Electrical Network 5–22<br />

magnitude and phase. Generator action is obtained by increasing the magnitude of E with<br />

the field control. The pitch controller sets the blade pitch at the optimum point if the blades<br />

are not already at this point. The blade torque will attempt to accelerate the generator, but<br />

this is impossible because the generator and the power grid are in synchronism. The torque<br />

will advance the relative position of the generator rotor with respect to the power grid voltage,<br />

however, so E will lead V by the power angle δ. The input mechanical power to the generator<br />

is fixed for a given wind speed and blade pitch, which also fixes the output power. If |E|<br />

is changed by the generator field control, then the power angle will change automatically to<br />

maintain this fixed output power.<br />

This synchronization process may sound very difficult, but is accomplished routinely by<br />

automatic equipment. If the wind speed and blade pitch are such that the turbine and<br />

generator are slowly accelerating through synchronous speed, the relay can usually be closed<br />

just as synchronous speed is reached. The microprocessor control would then adjust the field<br />

current and the blade pitch for proper operating conditions. An observer would see a smooth<br />

operation lasting only a minute or so.<br />

The control systems necessary for synchronization and the generator field supply are not<br />

cheap. On the other hand, their costs are not strongly dependent on system size over the<br />

normal range of wind turbine sizes. This means that the control systems would form a small<br />

fraction of the total turbine cost for a 1000-kW turbine, but a substantial fraction for a 5-kW<br />

turbine. For this reason, the synchronous generator will be more common in sizes of 100 kW<br />

and up, and not so common in the smaller sizes.<br />

4 PER UNIT CALCULATIONS<br />

Problems such as those in the previous section can always be worked using the actual circuit<br />

values. There is an alternative, however, to the use of actual circuit values which has several<br />

advantages and which is widely used in the electric power industry. This is the per unit system,<br />

in which voltages, currents, powers, and impedances are all expressed as a percent or per unit<br />

of a base or reference value. For example, if a base voltage of 120 V is chosen, voltages of 108,<br />

120, and 126 V become 0.90, 1.00, and 1.05 per unit, or 90, 100, and 105 percent, respectively.<br />

The per unit value of any quantity is defined as the ratio of the quantity to its base value,<br />

expressed as a decimal.<br />

One advantage of the per unit system is that the product of two quantities expressed in per<br />

unit is also in per unit. Another advantage is that the per unit impedance of an ac generator<br />

is essentially a constant for a wide range of actual sizes. This means that a problem like the<br />

preceding example needs to be worked only once in per unit, with the results converted to<br />

actual values for each particular size of machine for which results are needed.<br />

We shall choose the base or reference as the per phase quantities of a three-phase system.<br />

Thebaseradianfrequencyω base = ω o is the rated radian frequency of the system, normally<br />

Wind Energy Systems by Dr. Gary L. Johnson November 21, 2001

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!