08.06.2015 Views

PCM-2 Manual.pdf - Voss Associates

PCM-2 Manual.pdf - Voss Associates

PCM-2 Manual.pdf - Voss Associates

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Gas use is expressed as the percentage of time the inlet valve has been opened in<br />

order to maintain pressure. The long-term value represents total consumption<br />

since the counter was last reset (or since the unit was powered on). Short term<br />

use covers the latest five minutes. If a gas leak occurs, the short term number<br />

will increase more rapidly than the long term value.<br />

If the control knob is pressed, the display will prompt for entry of a password.<br />

This value is permanently set at "1287". Rotate the knob until the first number<br />

"1" shows, then press the knob. Repeat this procedure for the other three digits.<br />

If the knob is pressed and held for 3-4 seconds during normal operation, both gas<br />

use counters will be reset to zero. This should be done after purging the system<br />

to obtain steady-state gas consumption values. No password is required to reset<br />

the counters.<br />

Once a correct password has been entered, the first screen displayed is pressure<br />

setpoint. Rotate the knob to increase or decrease this setting. To accept the<br />

displayed value, press the knob.<br />

The second control screen offers to initiate an automatic purge. If the knob is<br />

rotated one click, the word "NO" will be replaced by "Yes." Press the knob to<br />

accept the displayed choice. If "Yes" is accepted, another window will be<br />

displayed in which the desired purge time may be set. Rotate the knob until the<br />

correct value is displayed, then press to begin the purge cycle.<br />

Finally, another "Yes/No" screen will offer to reset the long-term gas use counter.<br />

Again, rotate the knob to make a selection, then press it to accept.<br />

Calibration<br />

When initially setting up an instrument, initiate a detector purge and adjust the<br />

flow valve to approximately 800 cc/minute. Allow a minimum of 4 hours at this<br />

purge flow rate to completely purge all of the <strong>PCM</strong>-2's detectors. Reset the flow<br />

rate thereafter to approximately 150 cc/minute for normal operation.<br />

Zero Pressure<br />

Reference Reset NOTE: This step should only be performed ifthe gas manager's pressure<br />

transducer is replaced or if IlOIl-zero pressures are displayed when<br />

the instrument is actually at zero pressure. Resetting the zero<br />

reference when there is actually pressure in the detectors will result<br />

in higher than desired operating pressures and may damage both the<br />

detectors and the pressure transducer.<br />

Before resetting the zero reference, disconnect the system exhaust hose from the<br />

gas manager. This will insure that the pressure transducer is actually at zero (i.e.<br />

atmospheric pressure).<br />

1776 rCM2.M/\N/ Il:;v /\I/\p/i) 19%

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!