1 Specifications • Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE 1-2 ELECTRICAL SPECIFICATIONS FXDQ20PVE FXDQ25PVE FXDQ32PVE FXDQ40NAVE FXDQ50NAVE FXDQ63NAVE Power Supply Name VE Phase 1 1 1 1 1 1 Frequency Hz 50 50 50 50 50 50 Voltage V 220-240 Current Minimum circuit amps A 0.80 0.80 0.80 1.00 1.00 1.10 (MCA) Maximum fuse amps (MFA) A 15 15 15 15.00 15.00 15.00 Full load amps (FLA) A 0.60 0.60 0.60 0.80 0.80 0.90 Voltage range Minimum V -10% Maximum V +10% Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA

• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PVE - FXDQ-NAVE 2 Safety device settings PC board (A1P) fuse Fan motor thermal protector FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA 250V 5A OFF: 130 5C OFF ON: 83 15C ON 2 4D043861F 4 • VRV Systems • Indoor Units

• Indoor Units • SLIM CONCEALED CEILING UNIT • <strong>FXDQ</strong>-<strong>PVE</strong> - <strong>FXDQ</strong>-<strong>NAVE</strong><br />

2 Safety device settings<br />

PC board (A1P) fuse<br />

Fan motor thermal protector<br />

<strong>FXDQ</strong>20P <strong>FXDQ</strong>25P <strong>FXDQ</strong>32P <strong>FXDQ</strong>40NA <strong>FXDQ</strong>50NA <strong>FXDQ</strong>63NA<br />

250V 5A<br />

OFF: 130 5C OFF<br />

ON: 83 15C ON<br />