Intelligent Touch Controller
•<br />
19<br />
1 Main features<br />
Survey..........................................................................................................................................................................2<br />
New functions .......................................................................................................................................................2<br />
2 System Overview..................................................................................................................3<br />
3 System Image<br />
Double intelligent touch Controllers ......................................................................................................4<br />
Options.......................................................................................................................................................................4<br />
4 Part Names and Functions<br />
Part Names and Functions.............................................................................................................................5<br />
Terminals on the Back of intelligent touch Controller................................................................6<br />
5 Part Names on the Monitoring Screen and the Functions.......................7<br />
6 Specifications...........................................................................................................................8<br />
7 Accessories................................................................................................................................8<br />
8 Dimensions ...............................................................................................................................9<br />
9 System Wiring......................................................................................................................10<br />
10 Power Proportional Distribution Card<br />
Function and Outline......................................................................................................................................11<br />
Preparation...........................................................................................................................................................12<br />
File Format.............................................................................................................................................................13<br />
• Systems • Control Systems 1
•<br />
1 Main features<br />
Intelligent Touch Controller is an advanced centralised control air conditioning management system that provides complete control for air conditioning<br />
equipment. This "all in one" graphic controller mounts neatly on any wall and takes up far less room space than BMS type systems.<br />
Intelligent Touch Controller incorporates a touch screen and colour LCD display - easy for any operator to use - whilst its unique Daikin DIII -NET wiring<br />
and all-in-one system, enables the Intelligent Touch Controller to be installed in no time.<br />
1-1 Survey<br />
1<br />
1 Languages<br />
• English<br />
• French<br />
• German<br />
• Italian<br />
• Spanish<br />
2 Powerful Functions<br />
• Automatic cooling/heating changeover<br />
• Heating optimization<br />
• Temperature limit<br />
• Yearly schedule<br />
• Power proportional distribution (optional)<br />
• Fire emergency stop control<br />
• Flexible timer functionality (several schedules up to a full year)<br />
• Flexible grouping in zones<br />
• History <strong>data</strong><br />
• Password security (system set-up)<br />
3 Cost Performance<br />
• Labour saving<br />
• Easy installation<br />
• Compact design: limited installation space<br />
• Overall energy saving<br />
4 Simple Operation<br />
• User friendly full colour LCD<br />
• Touch panel<br />
• Icon display<br />
5 Connectable to<br />
• VRV<br />
• HRV<br />
• Sky Air (via interface adapter)<br />
• Split (via interface adapter)<br />
1-2 New functions<br />
1 AUTOMATIC COOLING / HEATING CHANGEOVER<br />
Maintains optimum room temperature by automatically selecting cooling or heating mode according to room temperature for locations<br />
subject to large temperature differences between night and day.<br />
2 TEMPERATURE LIMIT<br />
Automatically starts and stops the air conditioner to prevent temperatures in unoccupied rooms from rising or falling too far, e.g.<br />
- prevents overheating of equipment and formation of condensation in temperature controlled equipment in unoccupied rooms<br />
- also assists in preserving heat in entire buildings by preventing unoccupied rooms from reaching extreme night time temperatures.<br />
3 HEATING OPTIMIZATION<br />
Starts/stops the air conditioner during heating mode, depending on room and set temperatures to prevent the temperature from rising.<br />
2<br />
• Systems • Control Systems
•<br />
2 System Overview<br />
This intelligent Touch Controller is capable of controlling/monitoring up to 64 groups of indoor units<br />
(max. 128 indoor units) (hereafter "groups").<br />
The main functions of the intelligent Touch Controller include:<br />
1 Collective starting/stopping of operation of the indoor units connected to the intelligent Touch Controller.<br />
2 Starting/stopping of operation, temperature setting, switching between temperature control modes and enabling/<br />
disabling of operation with the hand-held remote control by zone or group.<br />
3 Scheduling by zone or group.<br />
4 Monitoring of the operation status by zone or group.<br />
2<br />
5 Display of the air conditioner operation history.<br />
6 Compulsory contact stop input from the central monitoring panel (non-voltage, normally-open contact).<br />
7 Power distribution of the air conditioners. (With the optional DCS002A1)<br />
A group of indoor units includes:<br />
1 One indoor unit without a remote control.<br />
Indoor unit<br />
No remote control<br />
2 One indoor unit controlled with one or two remote controls.<br />
Remote control<br />
or<br />
Remote control<br />
3 Up to 16 indoor units controlled with one or two remote controls.<br />
Remote control<br />
Up to 16 units<br />
Two remote controls<br />
Up to 16 units<br />
A zone includes 1 or more groups of indoor units<br />
* Zone control with the intelligent Touch Controller<br />
* Zone control, which allows collective settings for more than one group, is available with the intelligent Touch<br />
Controller, which facilitates the setting operations<br />
Zone 1<br />
Zone 2 Zone 3 Zone 4<br />
intelligent Touch Controller<br />
Zone 5<br />
• One setting makes the same setting for all of the units in one zone.<br />
• Groups can be zoned at will with the intelligent Touch Controller.<br />
• One group can be attributed to more than one zone.<br />
• Systems • Control Systems 3
•<br />
3 System Image<br />
3-1 Double intelligent touch Controllers<br />
Using two intelligent Touch Controllers allows central control of indoor units from different places.<br />
Outdoor unit<br />
Outdoor unit<br />
In-Out Out-Out<br />
In-Out Out-Out<br />
F1, F2 F1, F2<br />
F1, F2 F1, F2<br />
3<br />
F1, F2<br />
F1, F2<br />
F1, F2 F1, F2 F1, F2<br />
F1, F2<br />
Remote control<br />
Up to 16<br />
Up to 64 groups<br />
When the optional power distribution function<br />
is used, up to 64 indoor units can be connected.<br />
3-2 Options<br />
Connecting the collective remote adapter allows using the contact for normal and abnormal operation signal and collective start/stop with a contact.<br />
Central monitoring panel<br />
Collective start, stop and<br />
error monitoring with contact<br />
Unification adapter (DCS302A52)<br />
for computerized control<br />
Outdoor unit<br />
In-Out Out-Out<br />
Outdoor unit<br />
In-Out Out-Out<br />
F1, F2 F1, F2<br />
F1, F2 F1, F2<br />
Hand switch<br />
Power<br />
1~100 - 240 VAC Grounding<br />
50/60 Hz<br />
Forced stop command<br />
CN2<br />
L1, L2<br />
F1, F2<br />
F1, F2<br />
Meter x 3<br />
(When the optional power distribution function is used)<br />
F1, F2 F1, F2 F1, F2<br />
Remote control<br />
Up to 16<br />
Up to 64 groups<br />
When the optional power distribution function<br />
is used, up to 64 indoor units can be connected.<br />
4<br />
• Systems • Control Systems
•<br />
4 Part Names and Functions<br />
4-1 Part Names and Functions<br />
4<br />
DCS601B51<br />
PCMCIA Card Slot<br />
Used when using the optional power distribution (DCS002A1)<br />
or updating the intelligent Touch Controller software to a newer<br />
version.<br />
Color LCD with Touch Panel<br />
Provides a display for monitoring and operation.<br />
Be sure to use the touch pen provided for operation.<br />
( The display shows the Monitoring and System Setup screens.)<br />
Touch Pen<br />
Be sure to use the touch pen for operation.<br />
Use caution not to lose the touch pen.<br />
Maintenance Door<br />
Generally not used. Close the door for general use.<br />
Use the door when adjusting the contrast of the LCD or<br />
luminance of the backlight.<br />
NOTES<br />
1 Be sure to use the touch pen for operation on the touch panel of the intelligent Touch Controller.<br />
2 Operating with an object other than the touch pen provided may cause damage and failure.<br />
• Systems • Control Systems 5
•<br />
4 Part Names and Functions<br />
4-2 Terminals on the Back of intelligent touch Controller<br />
Use these ports for modem communication when using the<br />
AIRNET Service.<br />
4<br />
232C-1 232C-2 CN2<br />
Ethernet COM Dil Pi3 COM Pi2 Pi1 F2 F1 LON L2 L1<br />
Connect the collective remote control adapter to this connector<br />
for "collective start of operation," "collective stop of operation"<br />
or "error monitoring" remotely with a contact signal.<br />
This port is not used with this model.<br />
This port is not used with this model.<br />
Connect a non-voltage contact for collective stopping of<br />
operation with a contact signal.<br />
Terminals for communication with air conditioning system.<br />
Terminal for the grounding wire.<br />
Connect a watt-hour meter when using the optional power<br />
distribution function software (DCS002A1).<br />
Terminals for the power supply. Connect single-phase power of<br />
100 to 240 VAC, 50/60 Hz.<br />
6<br />
• Systems • Control Systems
•<br />
5 Part Names on the Monitoring Screen and the Functions<br />
Contents of the List Currently Displayed<br />
• When Group List is displayed<br />
"Zone: Zone Name"<br />
• When Zone List is displayed<br />
"Zone List"<br />
Zone/Group Name<br />
Set the names in the Group Registration or Zone<br />
Registration in the System Setup Mode.<br />
Display Mode Selection<br />
Select between Zone and Group.<br />
Display Type Selection<br />
Select the type between Icon and List.<br />
The example below shows the Icon Display.<br />
For List Display, see pages 8 .<br />
Display for Collective Monitoring of Air<br />
Conditioners Connected to intelligent Touch Controller<br />
When operation is normal and any air conditioner is in operation:<br />
Red/Normal<br />
When operation is normal and all air conditioners are in stoppage:<br />
Green/Normal<br />
When there is any air conditioner generating an error:<br />
Yellow/Abnormal<br />
When there is any air conditioner with communication error:<br />
Blue/Abnormal<br />
Target of Automatic Control<br />
Displayed when there is any air conditioner with the<br />
registration of scheduled or demand operation in the<br />
zone or in the group.<br />
Monitoring Screen Legend<br />
Pressing the "?" button shows more detailed legend.<br />
Description of Zone/Group<br />
Set the names in the Group Registration or Zone<br />
Registration in the System Setup Mode.<br />
Start All Button<br />
Button to collectively start all the air conditioners<br />
connected to intelligent Touch Controller.<br />
Stop All Button<br />
Button to collectively stop all the air conditioners<br />
connected to intelligent Touch Controller.<br />
Group/Zone Start Button<br />
Button to start operation of the group/zone selected.<br />
5<br />
Button to Switch to the System Setup Mode<br />
Use this button for settings including the time, group,<br />
zone and schedule. B<br />
System Status Display Area<br />
Area for displaying the system status<br />
(compulsory stop, etc.).<br />
Filter/Element Sign<br />
Displayed when there is any air conditioner showing a<br />
filter or element sign in the zone or the group.<br />
Information on Zone/Group Currently Displayed<br />
Generally, the temperature setting and the operation mode are<br />
displayed. If any error occurs in the air conditioner, the error<br />
code is displayed.<br />
Zone/Group Currently Displayed<br />
The name of the zone/group currently selected is<br />
highlighted.<br />
Scroll Bars<br />
Use the bars to monitor any area of the group/zone list<br />
not currently shown.<br />
Sliding the bars up/down and left/right changes the<br />
range monitored.<br />
Group/Zone Stop Button<br />
Button to stop operation of the group/zone selected.<br />
Group/Zone Set/Prop Button<br />
Makes detailed settings (temperature setting,<br />
temperature control mode, etc.) and display of the<br />
group/zone selected.<br />
Current Time Display<br />
Shows the current date and time.<br />
NOTE<br />
1 Groups can be visualised as icon or can be shown as a list<br />
• Systems • Control Systems 7
•<br />
6 Specifications<br />
6<br />
Intelligent Touch Controller (1*)<br />
DCS601B51<br />
POWER SUPPLY<br />
externally supplied AC100V-240V, 50/60Hz<br />
CONDITION OF INSTALLATION METHOD FOR USE<br />
JIS4 switchbox embedded in indoor wall<br />
OPERATING CONDITION Surrounding temperature 0°C - 40°C<br />
Humidity<br />
less than 85 % RH (if no condensation)<br />
DIMENSIONS PANEL HxWxD mm 147x230x40<br />
LCD PANEL Size 5.7 inches<br />
Nr. of dots<br />
QVGA 320x240<br />
Nr. of colors<br />
4,096 colors<br />
MAXIMUM NUMBER OF INDOOR UNITS 64 (128)<br />
MAXIMUM NUMBER OF OUTDOOR UNITS 10<br />
PC & DISPLAY<br />
built-in<br />
INPUT Touch panel 10 bit encoded analog input<br />
COMMUNICATION FUNCTIONS DIII-NET 1 line of air conditioner equipment for communication use<br />
Ethernet for servicing x 1<br />
modem x 1<br />
INPUT TERMINALS Digital input compulsory shutdown input x 1<br />
Pulse input power measuring pulse input x 3<br />
OVERSEAS CERTIFICATION Safety of information Technology Equipment IEC60730<br />
Interference (EMC)<br />
CISPR22, class-B, EN50082-1<br />
PROJECT DATA & ENGINEERING<br />
Configuration and engineering for each project are necessary.<br />
For further details, please consult with Daikin distributor and dealers<br />
NOTE<br />
1 Service and commissioning is offered by your <strong>technical</strong> service department<br />
7 Accessories<br />
Item<br />
Comments<br />
SOFTWARE DCS002B51 Power Proportional Distribution (PPD)<br />
INSTALLATION BOX KJB411A For wall mounted installation<br />
TOUCH-PEN 1264009 Spare part n° of Touch-Pen for Intelligent Touch Controller<br />
INTERFACE ADAPTERS KRP928A2S For connection to Split units<br />
DTA102A52<br />
For connection to R-22/R-407C Sky Air units<br />
DTA112B51<br />
For connection to R-410A Sky Air units<br />
8<br />
• Systems • Control Systems
•<br />
8 Dimensions<br />
Front view<br />
Door for PCMCIA card<br />
When using the optional Power Proportional<br />
Distribution Card (DCS002A51), open the door<br />
and insert the PCMCIA memory card.<br />
Back view<br />
DCS601B51<br />
Port shown by oblique lines is<br />
to be embedded in the wall<br />
or the control panel<br />
Access door<br />
Touch pen for operating the touch panel<br />
( attached to the intelligent Touch Controller )<br />
8<br />
This connector cannot be<br />
used with this unit.<br />
Ethernet<br />
Lon<br />
Item Nr Color<br />
1 KA Ivory white<br />
Ki Gray<br />
KU N-2. 0 (Black)<br />
KE SP-536 (Orange metallic)<br />
KO N-6. 0 (Gray)<br />
NOTES<br />
1 Rated electrical conditions<br />
• Rated voltage and frequency: Single phase AC100-240,50/60Hz<br />
• Rated power Maximum 10W<br />
2 Conditions for use<br />
• Power supply fluctuation: ±10% of the rated value<br />
• Ambient temperature: 0~+40°C<br />
• Ambient humidity: 10~ 90% (Sweating is not acceptable)<br />
3 Mass: 1.2 Kg<br />
3D031659<br />
• Systems • Control Systems 9
•<br />
9 System Wiring<br />
(Do not fail to use a round crimp terminal with reinforcing sleeve for safety wiring connection to the intelligent Touch Controller.)<br />
Wiring outline<br />
Outdoor unit<br />
Switch<br />
Fuse (10A)<br />
9<br />
Power supply<br />
1-100V~240V<br />
50/60Hz<br />
Grounding work<br />
Force stop command<br />
Up to 16 units maximum<br />
Measuring meter * 3<br />
Up to 64 groups maximum<br />
(Where Power Proportional Distribution Card as option is used)<br />
( The number of connectable indoor units is up to 64 units maximum,<br />
where the Power Proportional Distribution Card as option is used.)<br />
System wiring<br />
Outdoor unit<br />
Outdoor unit<br />
intelligent Touch Controller back<br />
In-Out Out-Out<br />
F1, F2 F1, F2<br />
In-Out Out-Out<br />
F1, F2 F1, F2<br />
Indoor unit<br />
to other outdoor unit<br />
Indoor unit<br />
Force-stop input<br />
*1<br />
Measuring meter x 3 *2 (Where<br />
Power proportional distribution<br />
Card as option is used)<br />
Grounding<br />
work<br />
Power supply<br />
1-100V~240V<br />
50/60Hz<br />
Indoor unit Indoor unit Indoor unit<br />
Unification adapter for computerized control<br />
(DCS302A52)<br />
Connector for connection<br />
(For the detail, see installation manual of the<br />
Unification adapter for computerized control)<br />
*1: When FORCE-STOP INPUT is kept ON, the indoor units connected are unable to be operated because they are force-stopped.<br />
- Use a contact which can guarantee minimum application load DC16V and 10mA.<br />
- Use an instantaneous contact of 200msec or more in current feed time, where required.<br />
*2: The measuring meters to be connected must meet the requirements specified below.<br />
- To be a measuring meter with pulse oscillator. (pulse/kWh)<br />
- Pulse band of 100msec or more<br />
- Measuring meter which uses mercury relay or semiconductor relay for pulse output and outputs pulses from non-voltage contact.<br />
Caution 1: Terminals COM are inter-connected. Connecting to either one is allowed, but the number of cables connectable to one terminal<br />
is limited to 2 pieces.<br />
Caution 2: Don't connect the power cable to this terminal block and F1, F2 terminal blocks. Wrong connection to these terminal blocks<br />
could result in damage and burning of the centralized control devices and of the electric parts of the indoor and outdoor units.<br />
This is very hazardous. Check each wired cable once more before turning ON the power switch.<br />
Wiring specification<br />
Power cable wiring<br />
Fuse<br />
Communication wiring for indoor unit<br />
and outdoor unit<br />
(*1)<br />
Wiring for force stop input<br />
(*2)<br />
Meter wiring for power distribution (option)<br />
(*3)<br />
1.25mm 2<br />
10A<br />
0.75 - 1.25 mm 2 vinyl cord or cable with sheath (2 wire)<br />
---Up to 1,000 m maximum<br />
(Wiring length -- up to 2,000 m maximum)<br />
(When shield cable is used, the wiring length is available up to 1,500m.)<br />
0.75 - 1.25 mm 2 vinyl cord or cable with sheath (2 wire) -- up to 150m maximum<br />
0.75 - 1.25 mm 2 vinyl cord or cable with sheath (2 wire) -- up to 150m maximum<br />
NOTE<br />
1 The above wiring *1 - *3 are for the communication wiring for control use. Don't clamp these cables together with high voltage cables. Failure to<br />
observe this instruction would cause control error.<br />
3D031660<br />
10<br />
• Systems • Control Systems
•<br />
10 Power Proportional Distribution Card<br />
10-1 Function and Outline<br />
Power Proportional Distribution Card, in combination with an existing intelligent Touch Controller, enables to proportionally calculate and display<br />
electricity amount used by air conditioner per indoor unit.<br />
10-1-1 Main Functions<br />
NEW<br />
NEW<br />
• 13 months <strong>data</strong> storage possible<br />
• Data available per hour per indoor unit<br />
• Power proportional distribution may be calculated for 64 indoor units at maximum.<br />
• Power proportion distribution results <strong>data</strong> may be saved into a PCMCIA card.<br />
Data is saved CSV format generally applied to personal computers, so bills may be issued by use of a general purpose table calculation<br />
software package in easy manners.<br />
(A personal computer and a general purpose table calculation software package may be available separately.)<br />
• There are 2 kinds of power proportional distribution:<br />
10<br />
10-1-2 Precautions<br />
Normal type: Power proportional distribution is carried out by VRV style calculation.<br />
Power proportional distribution is carried out per indoor unit.<br />
This system calculates electricity consumptions by size of indoor units, run time, expansion vales open gap, suction rate and the number of pulses from<br />
the power meters installed at the Outdoor Units.<br />
This method is not calculated by direct measurement alone.<br />
Electric power meter<br />
(with pulse output)<br />
123 123 123<br />
Power proportional distribution pulse.<br />
Maximum number of inputs -3.<br />
DIII-NETx1<br />
Outdoor unit<br />
DCS601B51<br />
PCMCIA card slot<br />
Indoor unit<br />
ÇcÇbÇr ÇOÇOÇQÇ`ÇTÇP<br />
DAIKIN INDUSTRIES. LTD.<br />
Power Proportional<br />
Distribution Card<br />
Bills may be issued by use of a general purpose table<br />
calculation software package in easy manners.<br />
64 units at maximum<br />
General purpose<br />
software<br />
Bills<br />
A personal computer and a general purpose table calculation software package may be available separately.<br />
• Systems • Control Systems 11
•<br />
10 Power Proportional Distribution Card<br />
10-2 Preparation<br />
10-2-1 Checking Attachments<br />
Power Proportional Distribution Card (DCS002B51) includes the following attachments.<br />
CBR000'TP<br />
10<br />
DAIKIN INDUSTRIES. LTD.<br />
Instruction Manual<br />
10-2-2 How to Connect<br />
To activate the power proportional distribution function, it is necessary to set the<br />
program by use of the attached PCMCIA card and carry out a trial operation.<br />
Before use, consult your supplier.<br />
12<br />
• Systems • Control Systems
•<br />
10 Power Proportional Distribution Card<br />
10-3 File Format<br />
When Power Proportional Distribution Report is saved, a zone information file and an electric power information file are created.<br />
10-3-1 Zone information file<br />
This contains zone name and information of air conditioners in the zone.<br />
(1) File name : ZONE.CSV<br />
(2) File format:<br />
10<br />
(Example)<br />
zone ID, Name<br />
0,all<br />
1, 'Z-000<br />
2, 'Z-001<br />
3, 'Z-002<br />
Index<br />
Zone ID, zone name<br />
zone ID, AC No.<br />
0, 0<br />
0, 1<br />
1, 2<br />
1, 3<br />
One line space<br />
Zone ID, air conditioner number<br />
10-3-2 Electric power information file<br />
This file contains Power Proportional Distribution Report and information of air conditioners.<br />
(1) File name : 332 - MMDD - N.CSV<br />
Serial number<br />
Month and date of calculation completion<br />
Year, month and date of calculation start<br />
Year, month and date of calculation start<br />
(2) File format :<br />
(Example)<br />
Index<br />
Start day, number of days, air conditioner type (0 : normal type), electric power amount not proportionally distributed, period designation type<br />
(0 : period designation, 1 : month designation)<br />
20010511, 30, 0, 0, 0<br />
One line space<br />
Air conditioner number, indoor unit number, horse power code, electricity use amount, electric power amount at stop.<br />
1, '1-01, fb, 0, 8<br />
2, '1-03, 38, 0, 0, 13, 0<br />
• Systems • Control Systems 13
2<br />
Systems<br />
ISO14001 assures an effective environmental<br />
management system in order to help protect<br />
human health and the environment from the potential<br />
impact of our activities, products and services and to<br />
assist in maintaining and improving the quality of<br />
the environment.<br />
Daikin units comply with the European<br />
regulations that guarantee the safety of<br />
the product.<br />
Daikin Europe N.V. is approved by LRQA for its Quality<br />
Management System in accordance with the ISO9001<br />
standard. ISO9001 pertains to quality assurance regarding<br />
design, development, manufacturing as well as to services<br />
related to the product.<br />
VRV products are not within the scope<br />
of the Eurovent certification programme.<br />
Specifications are subject to change without prior notice<br />