<strong>Series</strong> <strong>20</strong><br />
<strong>Air</strong> <strong>Cooled</strong> <strong>Condensing</strong> <strong>Units</strong><br />
Standard Features<br />
Unit Configuration<br />
• Low Profile<br />
• Base Rail Configuration<br />
• Multiple Rigging Points<br />
• Removable Access Panels<br />
• Hinged Control Panel Access<br />
• ETL Certified Unit<br />
Refrigerant Circuit<br />
• Liquid Line Shut Off Valve with Charging Port<br />
• Oil Failure Switch on each Compressor<br />
(CS, CD, & CM units)<br />
• High Pressure Safety Control<br />
• Low Pressure Operating Control<br />
• Shipped With Dry Nitrogen Holding Charge<br />
Condenser<br />
• Direct Drive Condenser Fans<br />
• Epoxy Powder Coated Fan Guards<br />
• Three-Phase Motors with Permanently<br />
Lubricated Ball Bearings<br />
• Fan Staging Heads Pressure Control to +<strong>20</strong>°F<br />
• Sub-Circuit Fan Motor fusing with Internal<br />
Overload Motor Protector<br />
• Fan Motor Contactor<br />
• Plate Fin / Full Tube Collar Condenser Coils<br />
• Baffled Condenser Plenum<br />
• "True" Subcooling<br />
Electrical Components<br />
• Fused Control Circuit<br />
• Prewired Controls<br />
• Auto / Demand Pumpdown Switch<br />
• UL 508 Certified & Labeled<br />
Compressors<br />
• Energy Efficient Copeland ® Compressors<br />
• Compressor Service Valves<br />
• Internal Compressor Overload Protection<br />
• Compressor Fusing (LD, CD & CM units)<br />
• Compressor Contactors<br />
• Compressor Time Delay (LD, CD, & CM units)<br />
• Compressor Isolator Pads<br />
• Oil Equalization System each Circuit (CM units)<br />
We reserve the right to change or revise specifications and product design in connection with<br />
any feature of our products. Such changes do not entitle the buyer to corresponding changes,<br />
improvements, additions or replacement for equipment previously sold or shipped.
Technical Systems’ <strong>Series</strong> <strong>20</strong> condensing units have<br />
been designed to satisfy the requirements of the most<br />
discerning customer. Whatever the concern; versatility,<br />
efficiency, serviceability… Technical Systems <strong>Series</strong> <strong>20</strong><br />
condensing units apply sound engineering principles to<br />
satisfy even the most demanding applications.<br />
All <strong>Series</strong> <strong>20</strong> condensing units are designed and<br />
rated in accordance with ARI standard 5<strong>20</strong>. All refrigerant<br />
containing vessels are constructed in accordance with<br />
ANSI B9.1. Electrical components are UL approved<br />
and applied in accordance with their approved usage.<br />
All wiring and electrical construction are in accordance<br />
with the National Electric Code. <strong>Units</strong> are ETL listed and<br />
labeled. The control panels are UL 508 listed and labeled.<br />
The <strong>Series</strong> <strong>20</strong> product line offers a total of 50 units<br />
making it one of the most comprehensive offering of air<br />
cooled condensing units available today.<br />
“LS” and “LD” condensing units are designed with<br />
full hermetic scroll compressors for single circuit and<br />
dual circuit applications. Capacities ranging from 3 to<br />
32 tons make the “LS” and “LD” series condensing units<br />
perfect for commercial applications. Unit configuration<br />
is a base rail design for structural integrity. All “LS” and<br />
“LD” condensing units incorporate independent refrigerant<br />
circuits. Each circuit has independent safeties for proper<br />
system protection.<br />
“CS” condensing units offer a tonnage range of 6 to<br />
57 tons with unmatched versatility in design. Technical<br />
Systems’ <strong>Series</strong> <strong>20</strong> condensing units make it possible<br />
to design a system with smaller tonnage requirements<br />
and know that a condensing unit with such features as<br />
semi-hermetic compressors, single circuit simplicity, and<br />
base rail design is available. These units are available<br />
with a full compliment of accessories ranging from gauge<br />
<strong>Series</strong> Designation<br />
for <strong>Condensing</strong> <strong>Units</strong><br />
Standard Construction<br />
<strong>Air</strong> <strong>Cooled</strong><br />
Unit Design Vintage<br />
panels to service indication lights; phase failure monitors<br />
to unit disconnects; and copper fin condenser coils to<br />
special surface coatings. If versatility and quality are job<br />
requirements, Technical Systems’ “CS” condensing units<br />
can meet the specification.<br />
“CD” condensing units combine many of the features<br />
and benefits of the “CS” condensing units with capacities<br />
from 13 to 115 tons, offering one of the finest midrange<br />
dual circuit air cooled condensing units available.<br />
Independent circuits offer redundancy in operation and<br />
allow for a more dependable condensing unit. Each<br />
circuit is protected by an independent set of safeties<br />
which assures proper circuit protection. Each compressor<br />
is protected by an inherent thermistor embedded in<br />
each of the three windings providing proper thermal<br />
protection. Oil failure safety switches are provided for<br />
each compressor, thus monitoring the oil pressure for that<br />
specific compressor. CD10 through CD80 condensing<br />
units are fabricated on a formed steel base, and CD90<br />
and up are fabricated on a structural steel base. <strong>Series</strong><br />
<strong>20</strong> “CD” condensing units are designed to offer mid-range<br />
capacities with the advantages previously reserved only<br />
for large tonnage condensing units.<br />
“CM” condensing units offer a capacity range of 92<br />
to 168 tons with a unit EER as high as 13.72. These<br />
excellent efficiencies are accomplished with dependable<br />
components such as high efficiency Discus compressors<br />
and condensers with 1/2” copper tubes and a maximum<br />
fin spacing of 14 fins per inch. Add to the excellent<br />
efficiencies and dependable components the structural<br />
integrity of a welded steel base and the accessibility of<br />
removable side screens and you have a condensing unit<br />
designed to operate with reliability not only for the first<br />
year, but for years to come.<br />
Nomenclature<br />
<strong>20</strong> A O C M 1<strong>20</strong><br />
Nominal Horsepower<br />
Number of Compressors<br />
S - Single<br />
D - Dual<br />
M - Multiple<br />
Compressor Type<br />
L - Scroll<br />
C - Reciprocating<br />
S - Screw<br />
When Ordering Please Specify:<br />
• Complete Model Number • Room Temperature<br />
• Saturated Suction Temperature • Accessories<br />
• Electrical Characteristics Unit Voltage & Control Voltage
TOTALLY ENCLOSED FAN MOTOR - Totally<br />
enclosed non-ventilated motors are available for<br />
corrosive or hazardous environments.<br />
GAUGES* - Oil, high, and low pressure liquid<br />
filled gauges are optional on all Technical Systems’<br />
condensing units. We recommend the gauges be<br />
supplied with manual shut off valves.<br />
CYLINDER UNLOADING** - Additional steps of<br />
cylinder unloading are available to meet today’s part<br />
load design requirement.<br />
HOT GAS BYPASS - Standard hot gas bypass,<br />
includes hand isolation valve, regulator and solenoid<br />
mounted, wired, and piped.<br />
CONTROL CIRCUIT TRANSFORMER - A factory<br />
mounted transformer provides 115-volt or 24-volt control<br />
where a separate power source is not available. 115-<br />
volt convenience outlet is also available upon request.<br />
ALARM CIRCUIT WITH HORN - Allows for audible<br />
alarm on oil, high, or low pressure failure. Dry contacts<br />
for remote indication are available.<br />
GUARANTEED OFF TIMER - 3 to 30 minute timers<br />
are available to prevent compressor short cycling.<br />
PART WINDING START*** - Factory wired part<br />
winding start is available to reduce electrical inrush.<br />
Available Options<br />
3 VALVE BYPASS - May be factory installed to allow<br />
for drier bypass and change-out during unit operation.<br />
DISCONNECT SWITCH - Fused and non-fused<br />
disconnects may be factory installed for single point<br />
connections.<br />
REFRIGERATION SPECIALTIES - A full line of<br />
refrigeration specialties such as suction accumulators,<br />
suction/discharge vibrasorbers, hot gas mufflers, etc.<br />
are optional for factory mounting and piping.<br />
DOOR INTERLOCK - May be installed on control<br />
panel if desired. A positive latching solenoid will insure<br />
that control panel doors may not be opened until power<br />
is disconnected from the unit. Additionally, a throughthe-door<br />
panel mounted disconnect with door interlock<br />
is available up to <strong>20</strong>0 amps.<br />
LOW AMBIENT LOCKOUT - Available as an option<br />
to prevent unit operation below an adjustable set point.<br />
This protects a system from being inadvertently started<br />
in ambients for which it was not designed.<br />
AUTOMATIC LEAD/LAG - Automatic lead/lag switch<br />
available to sequence starting of compressors on every<br />
system cycle.<br />
CIRCUIT BREAKER - Optional on all condensing<br />
units. Circuit breakers may be installed in lieu of system<br />
fusing.<br />
INDICATING LIGHTS - When required, indicating<br />
lights can be factory installed for visual confirmation of<br />
system operation.<br />
PHASE FAILURE / UNDER VOLTAGE<br />
PROTECTION - Optional factory mounted in control<br />
panel to protect against “brown out” and phase failure<br />
conditions.<br />
LOW AMBIENT HEAD PRESSURE CONTROL -<br />
Low ambient head pressure control by fan cycling is<br />
standard to <strong>20</strong>°F. on all condensing units. However,<br />
additional control by condenser flooding to -<strong>20</strong>°F. is<br />
available.<br />
PRESSURE RELIEF - Pressure relief valves and<br />
bull’s eye sight glasses are available for factory<br />
mounting when receives are specified.<br />
PAINT - Standard paint systems are available. Gray<br />
color is standard; however, color selection to match<br />
surrounding decor is available.<br />
COPPER FIN CONDENSER COILS - Available as<br />
an option for corrosion environments. Features dieformed<br />
configured fins.<br />
KILOWATT AND AMP METERS - Available as a<br />
factory option for continuous monitoring of the unit<br />
kilowatt and/or amperage consumption. Meters are<br />
available with analog or digital readout.<br />
ELAPSED TIME METERS - Meters give a visual<br />
display of the accumulative hours that a compressor<br />
has operated. Allows for easier scheduling of preventive<br />
maintenance.<br />
LIQUID LINE TRIM - Replaceable core driers, liquid<br />
line solenoids and moisture indicating sight glasses are<br />
all available factory mounted or shipped loose for field<br />
installation.<br />
* High and Low Pressure Gauges are available on all<br />
units. Oil Pressure Gauge not available on “L” <strong>Series</strong><br />
compressors.<br />
** This option is available only on units with type “C”<br />
compressors (CS5 and CS8 are not available with<br />
unloading).<br />
*** The part winding start option is available only on units<br />
with type “C” compressors (CS<strong>20</strong> and larger).
General Specifications<br />
<strong>Series</strong> <strong>20</strong> air cooled condensing units are<br />
designed for easy handling and reduced installation<br />
costs. All <strong>Series</strong> <strong>20</strong> condensing units are pressure<br />
tested prior to shipment. Internal power and control<br />
wiring are ready for field connection to utilities.<br />
CABINET<br />
All <strong>Series</strong> <strong>20</strong> condensing units are constructed of<br />
heavy duty mill galvanized steel panels. <strong>Units</strong> are<br />
base rail configured for distributed roof loadings,<br />
convenient handling and easier installation. Lifting<br />
points and mounting holes are provided on each<br />
unit.<br />
COMPRESSORS<br />
<strong>Series</strong> <strong>20</strong> condensing units with type “C”<br />
compressors are equipped with Copeland Discus®<br />
semi-hermetic compressors. These high efficiency,<br />
industrial grade semi-hermetic compressors are<br />
designed to provide field serviceability for easier<br />
maintenance and optimum system performance.<br />
Copeland compressors utilize blocked suction<br />
unloading which allows for reduced power<br />
consumption during unloaded conditions and<br />
reduces total yearly power usage. Suction and<br />
discharge service valves, suction strainer, charging<br />
port and oil pumps are all standard with type “C”<br />
compressor.<br />
CONDENSER<br />
The casing is heavy duty, corrosion resistant<br />
steel. Each fan section is separated by baffles to<br />
prevent air bypass.<br />
The condenser coils are constructed with<br />
seamless copper tubes arranged in a staggered<br />
row pattern and mechanically expanded into plated<br />
type configured aluminum fins with full fin collars.<br />
A separate subcooling coil, integral with the<br />
condenser, is provided on each circuit to eliminate<br />
the possibility of liquid flashing and to increase unit<br />
efficiency.<br />
Quiet and efficient direct driven, multiple<br />
propeller fans with steel hubs and aluminum<br />
blades discharge vertically from formed venturis<br />
to provide maximum static efficiency and minimize<br />
noise generation. Condenser fans are driven by<br />
three-phase motors that are specifically designed<br />
for vertical shaft direct drive applications. Motors<br />
feature permanently lubricated ball bearings and<br />
have inherent thermal protection. Fan guards are of<br />
heavy gauge, close meshed steel wire construction<br />
with an epoxy powder coating.<br />
ELECTRICAL CONTROL CENTER<br />
The Technical Systems air cooled condensing<br />
units are shipped with operating and safety controls<br />
including:<br />
• Circuit Pump Down Switch<br />
• Oil Pressure Control-Manual Reset<br />
(“C” type compressor only)<br />
• High Pressure Control - Manual Reset<br />
• Pumpdown Pressure Control - Auto Reset<br />
• Fan Staging Controls - Pressure Actuated<br />
Type “L” compressors are the reliable Copeland<br />
Scroll compressors. The Copeland Compliant<br />
Scroll® is a welded hermetic compressor. This<br />
design provides a rotary compressor action for<br />
smooth and quiet operation.<br />
POWER CONTROLS INCLUDE:<br />
• Compressor Motor Contactors<br />
• Fan Motor Contactors<br />
• Compressor Motor Fuses*<br />
• Fan Motor Fuses<br />
• Control Circuit Fuses<br />
• Power Terminal Blocks<br />
• Separate 115-Volt Control Circuit<br />
Terminal Blocks<br />
• Control Relays<br />
• Compressors Crankcase Heater Relays<br />
• Field Auxiliary Control Terminals<br />
• Fuses are not provided on “LS” and “CS” units.
Model<br />
<strong>20</strong>AO<br />
LS 3<br />
LS 5<br />
LS 8<br />
LS 9<br />
LS 10<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 2.76 2.89 11.44 2.60 3.19 9.81 2.44 3.49 8.39<br />
40° 3.04 2.95 12.34 2.86 3.25 10.56 2.68 3.57 9.03<br />
45° 3.33 3.02 13.23 3.14 3.33 11.32 2.94 3.65 9.68<br />
50° 3.64 3.09 14.13 3.43 3.41 12.06 3.21 3.74 10.29<br />
35° 4.94 4.83 12.26 4.64 5.38 10.36 4.32 5.96 8.71<br />
40° 5.42 4.96 13.10 5.09 5.52 11.07 4.73 6.11 9.29<br />
45° 4.92 5.12 13.87 5.55 5.69 11.72 5.16 6.29 9.85<br />
50° 6.44 5.38 14.59 6.04 5.88 12.33 2 2 2<br />
35° 7.25 7.51 11.58 6.88 8.25 10.00 6.48 9.03 8.61<br />
40° 7.96 7.68 12.45 7.56 8.43 10.75 7.12 9.23 9.26<br />
45° 8.72 7.87 13.31 8.27 8.64 11.49 7.79 9.45 9.90<br />
50° 9.53 8.08 14.15 9.03 8.87 12.22 8.51 9.69 10.53<br />
35° 8.59 9.24 11.16 8.13 10.14 9.61 7.63 11.10 8.25<br />
40° 9.43 9.48 11.93 8.91 10.41 10.28 2 2 2<br />
45° 10.32 9.76 12.68 9.75 10.70 10.93 2 2 2<br />
50° 11.25 10.07 13.41 10.63 11.04 11.56 2 2 2<br />
35° 9.89 10.62 11.63 9.40 11.72 9.62 2 2 2<br />
40° 10.83 10.92 11.90 10.26 12.02 10.25 2 2 2<br />
45° 11.83 11.25 12.61 11.19 12.37 10.85 2 2 2<br />
50° 12.88 11.64 13.28 12.16 12.76 11.43 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
LS 3 LS 5 LS 8 LS 9 LS 10<br />
Nominal Tons* 3.1 5.4 8.1 9.4 10.8<br />
L" x W" x H" 76" x 34" x 46" 76" x 34" x 46" 87" x 34" x 46" 87" x 34" x 46" 87" x 34" x 46"<br />
Shipping Weight 711 lb. 759 lb. 977 lb. 1,005 lb. 1,029 lb.<br />
Refrigerant Circuits 1 1 1 1 1<br />
Refrigerant Charge (R-22) 3.5 lbs. 6 lbs. 10 lbs. 11 lbs. 13 lbs.<br />
Coil Pumpdown Capacity** 7.3 lbs. 14.3 lbs. 23.8 lbs. 23.8 lbs. 24.7 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 3 5 7.5 9 10<br />
Oil Charge 55 oz. 65 oz. 128 oz. 128 oz. 128 oz.<br />
Crankcase Heater Watts 40 40 70 70 70<br />
Suction Connection - ODS 7/8" 1 1/8" 1 3/8" 1 3/8" 1 3/8"<br />
Liquid Line Connection - ODS 1/2" 1/2" 5/8" 5/8" 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 5 6.5 10.8 10.8 10.8<br />
Rows / Fins Per Inch (FPI) 2 / 14 3 / 14 3 / 14 3 / 14 4 / 14<br />
Total CFM 4,410 5,100 7,500 7,500 7,<strong>20</strong>0<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 1 / 24" 1 / 24" 1 / 28" 1 / 28" 1 / 28"<br />
Horsepower - Each 1/2 1/2 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 6,900 6,900 8,060 8,060 8,060<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
LS 13<br />
LS 15<br />
LD 10<br />
LD 15<br />
LD 18<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 12.31 14.08 10.49 11.64 15.42 9.06 2 2 2<br />
40° 13.51 14.47 11.<strong>20</strong> 12.77 15.83 9.68 2 2 2<br />
45° 14.78 14.93 11.88 13.97 16.30 10.28 2 2 2<br />
50° 16.12 15.44 12.52 15.23 16.85 10.84 2 2 2<br />
35° 14.80 15.79 11.25 13.96 17.33 9.67 13.06 18.95 8.27<br />
40° 16.27 16.19 12.05 15.34 17.75 10.37 2 2 2<br />
45° 17.80 16.67 12.82 16.79 18.25 11.04 2 2 2<br />
50° 19.43 17.18 13.57 18.32 18.80 11.70 2 2 2<br />
35° 9.89 9.62 12.35 9.30 10.71 10.42 8.66 11.87 8.76<br />
40° 10.85 9.88 13.18 10.19 10.99 11.13 9.49 12.16 9.36<br />
45° 11.85 10.18 13.96 11.13 11.31 11.80 10.35 12.51 9.93<br />
50° 12.91 10.53 14.71 12.11 11.69 12.43 2 2 2<br />
35° 14.50 15.01 11.59 13.75 16.50 10.01 12.96 18.06 8.61<br />
40° 15.93 15.35 12.46 15.11 16.86 10.75 14.24 18.45 9.27<br />
45° 17.45 15.72 13.32 16.55 17.27 11.49 15.59 18.88 9.9<br />
50° 19.06 16.15 14.16 18.07 17.74 12.22 17.02 19.39 10.53<br />
35° 17.18 18.48 11.16 16.25 <strong>20</strong>.29 9.61 15.26 22.19 8.26<br />
40° 18.86 18.96 11.94 17.83 <strong>20</strong>.81 10.29 2 2 2<br />
45° <strong>20</strong>.64 19.52 12.69 19.50 21.39 10.94 2 2 2<br />
50° 22.51 <strong>20</strong>.13 13.42 21.26 22.06 11.56 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
LS 13 LS 15 LD 10 LD 15 LD 18<br />
Nominal Tons* 13.6 16.4 10.9 16.2 18.8<br />
L" x W" x H" 1<strong>20</strong>" x 34" x 46" 1<strong>20</strong>" x 34" x 46" 76" x 68" x 63" 87" x 68" x 63" 87" x 68" x 63"<br />
Shipping Weight 1,199 lbs. 1,288 lbs. 1,604 lbs. 2,056 lbs. 2,080 lbs.<br />
Refrigerant Circuits 1 1 2 2 2<br />
Refrigerant Charge (R-22) 16 lbs. 18 lbs. 12 lbs. 19 lbs. 24 lbs.<br />
Coil Pumpdown Capacity** 27.9 lbs. 41.8 lbs. 28.6 lbs. 47.6 lbs. 47.6 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 13 15 5 5 7.5 7.5 9 9<br />
Oil Charge 140 oz. 140 oz. 65 oz. 65 oz. 128 oz. 128 oz. 128 oz. 128 oz.<br />
Crankcase Heater Watts 70 70 40 40 70 70 70 70<br />
Suction Connection - ODS 1 3/8" 1 3/8" 1 1/8" 1 1/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"<br />
Liquid Line Connection - ODS 7/8" 7/8" 1/2" 1/2" 5/8" 5/8" 5/8" 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 18.9 18.9 13 21.7 21.7<br />
Rows / Fins Per Inch (FPI) 2 / 14 3 / 14 3 / 14 3 / 14 4 / 14<br />
Total CFM 13,100 12,400 10,<strong>20</strong>0 15,000 15,000<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 2 / 28" 2 / 28" 2 / 24" 2 / 28" 2 / 28"<br />
Horsepower - Each 1 1 1/2 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 6,900 8,060 8,060<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
LD <strong>20</strong><br />
LD 26<br />
LD 30<br />
CS 5<br />
CS 8<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 19.84 <strong>20</strong>.97 11.35 18.85 23.16 9.77 17.85 25.47 8.41<br />
40° 21.73 21.54 12.11 <strong>20</strong>.61 23.74 10.41 2 2 2<br />
45° 23.75 22.<strong>20</strong> 12.84 22.47 24.41 11.05 2 2 2<br />
50° 25.87 22.95 13.53 24.44 25.18 11.65 2 2 2<br />
35° 24.68 27.92 10.61 23.35 30.57 9.16 21.97 33.37 7.91<br />
40° 27.09 28.66 11.34 25.62 31.37 9.80 2 2 2<br />
45° 29.64 29.55 12.04 28.03 32.29 10.42 2 2 2<br />
50° 32.35 30.54 12.71 30.57 33.36 10.99 2 2 2<br />
35° 29.68 31.32 11.37 28.00 34.39 9.77 26.22 37.60 8.37<br />
40° 32.61 32.11 12.19 30.78 35.21 10.49 28.83 38.48 8.99<br />
45° 35.70 33.02 12.97 33.70 36.17 11.18 2 2 2<br />
50° 38.96 34.04 13.73 36.77 37.26 11.85 2 2 2<br />
35° 5.76 5.68 12.18 5.37 6.05 10.65 4.98 6.38 9.36<br />
40° 6.39 5.90 13.00 5.96 6.31 11.35 5.54 6.68 9.95<br />
45° 7.06 6.13 13.83 6.60 6.57 12.05 2 2 2<br />
50° 7.77 6.37 14.63 7.27 6.85 12.73 2 2 2<br />
35° 8.15 8.38 11.67 7.61 8.92 10.24 7.07 9.41 9.02<br />
40° 9.02 8.69 12.45 8.43 9.28 10.91 7.84 9.82 9.59<br />
45° 9.95 9.01 13.25 9.31 9.65 11.57 2 2 2<br />
50° 10.94 9.36 14.02 10.25 10.04 12.24 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
LD <strong>20</strong> LD 26 LD 30 CS 5 CS 8<br />
Nominal Tons* 21.6 27.1 32.8 6.4 8.9<br />
L" x W" x H" 87" x 68" x 63" 123" x 68" x 63" 123" x 68" x 63" 76" x 34" x 46" 87" x 34" x 46"<br />
Shipping Weight 2,132 lbs. 2,431 lbs. 2,614 lbs. 1,019 lbs. 1,118 lbs.<br />
Refrigerant Circuits 2 2 2 1 1<br />
Refrigerant Charge (R-22) 26 lbs. 32 lbs. 36 lbs. 5 lbs. 9 lbs.<br />
Coil Pumpdown Capacity** 39.5 lbs. 34.4 lbs. 51.6 lbs. 14.3 lbs. 23.8 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 10 10 13 13 15 15 5 7.5<br />
Oil Charge 128 oz. 128 oz. 140 oz. 140 oz. 140 oz. 140 oz. 112 oz. 144 oz.<br />
Crankcase Heater Watts 70 70 70 70 70 70 70 70<br />
Suction Connection - ODS 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 1/8" 1 1/8"<br />
Liquid Line Connection - ODS 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 5/8" 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 21.7 37.7 37.7 6.5 10.8<br />
Rows / Fins Per Inch (FPI) 4 / 14 2 / 14 3 / 14 3 / 14 3 / 14<br />
Total CFM 14,400 26,<strong>20</strong>0 24,800 5,500 7,500<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 2 / 28" 4 / 28" 4 / 28" 1 / 24" 1 / 28"<br />
Horsepower - Each 1 1 1 1/2 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 6,900 8,060<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
CS 10<br />
CS 15<br />
CS <strong>20</strong><br />
CS 25<br />
CS 30<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 11.78 12.87 10.98 11.01 13.69 9.65 10.22 14.44 8.49<br />
40° 12.90 13.29 11.65 12.06 14.17 10.21 2 2 2<br />
45° 14.10 13.72 12.33 13.16 14.66 10.78 2 2 2<br />
50° 15.36 14.16 13.01 14.34 15.17 11.34 2 2 2<br />
35° 15.62 17.08 10.97 14.64 18.17 9.67 13.64 19.16 8.54<br />
40° 17.10 17.68 11.61 16.01 18.83 10.<strong>20</strong> 2 2 2<br />
45° 18.68 18.28 12.26 17.46 19.51 10.74 2 2 2<br />
50° <strong>20</strong>.34 18.91 12.91 18.99 <strong>20</strong>.19 11.29 2 2 2<br />
35° 16.73 18.18 11.04 15.46 19.<strong>20</strong> 9.66 2 2 2<br />
40° 18.40 18.95 11.65 16.99 <strong>20</strong>.04 10.17 2 2 2<br />
45° <strong>20</strong>.13 19.76 12.23 18.57 <strong>20</strong>.91 10.66 2 2 2<br />
50° 21.95 <strong>20</strong>.58 12.80 <strong>20</strong>.23 21.80 11.13 2 2 2<br />
35° 21.72 22.74 11.46 <strong>20</strong>.32 24.18 11.46 18.88 25.50 8.88<br />
40° 23.86 23.70 12.08 22.33 25.26 10.61 2 2 2<br />
45° 26.15 24.69 12.71 24.45 26.36 11.13 2 2 2<br />
50° 28.53 25.74 13.30 26.65 27.52 11.62 2 2 2<br />
35° 25.06 28.85 10.42 23.38 30.49 9.<strong>20</strong> 2 2 2<br />
40° 2.49 30.14 10.94 25.65 31.92 9.64 2 2 2<br />
45° 30.07 31.49 11.46 28.04 33.42 10.07 2 2 2<br />
50° 32.77 32.92 11.95 2 2 2 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
CS 10 CS 15 CS <strong>20</strong> CS 25 CS 30<br />
Nominal Tons* 13.2 17.5 18.7 24.5 28.9<br />
L" x W" x H" 1<strong>20</strong>" x 34" x 46" 1<strong>20</strong>" x 34" x 46" 1<strong>20</strong>" x 34" x 46" 143" x 34" x 53" 143" x 34" x 53"<br />
Shipping Weight 1,388 lbs. 1,441 lbs. 1,5<strong>20</strong> lbs. 1,754 lbs. 1,849 lbs.<br />
Refrigerant Circuits 1 1 1 1 1<br />
Refrigerant Charge (R-22) 12 lbs. 18 lbs. 24 lbs. 33 lbs. 37 lbs.<br />
Coil Pumpdown Capacity** 27.9 lbs. 41.8 lbs. 41.8 lbs. 70.9 lbs. 70.9 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 10 15 <strong>20</strong> 25 30<br />
Oil Charge 144 oz. 144 oz. 136 oz. 136 oz. 152 oz.<br />
Crankcase Heater Watts 70 70 100 100 100<br />
Suction Connection - ODS 1 3/8" 1 3/8" 1 5/8" 1 5/8" 2 1/8"<br />
Liquid Line Connection - ODS 7/8" 7/8" 7/8" 1 1/8" 1 1/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 19 19 19 24.2 24.2<br />
Rows / Fins Per Inch (FPI) 2 / 14 3 / 14 3 / 14 4 / 14 4 / 14<br />
Total CFM 15,400 15,400 15,400 14,500 19,500<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 2 / 28" 2 / 28" 2 / 28" 2 / 28" 3 / 28"<br />
Horsepower - Each 1 1 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 8,060<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
CS 35<br />
CS 40<br />
CS 50<br />
CS 60<br />
CD 10<br />
10<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 31.27 33.02 11.36 29.18 35.<strong>20</strong> 9.95 27.07 37.25 8.72<br />
40° 34.32 34.38 11.98 32.00 36.71 10.46 29.65 38.89 9.15<br />
45° 37.57 35.78 12.60 35.02 38.25 10.99 2 2 2<br />
50° 41.01 37.27 13.<strong>20</strong> 38.18 39.90 11.49 2 2 2<br />
35° 37.24 41.48 10.77 34.82 44.08 9.48 2 2 2<br />
40° 40.83 43.30 11.32 38.16 46.07 9.94 2 2 2<br />
45° 44.60 45.24 11.83 41.67 48.<strong>20</strong> 10.37 2 2 2<br />
50° 48.59 47.31 12.32 45.38 50.47 10.79 2 2 2<br />
35° 43.66 48.74 10.75 40.85 51.75 9.47 2 2 2<br />
40° 47.90 50.98 11.28 44.75 54.24 9.90 2 2 2<br />
45° 52.36 53.38 11.77 48.91 56.84 10.33 2 2 2<br />
50° 57.06 55.93 12.24 2 2 2 2 2 2<br />
35° 51.96 59.98 10.40 48.65 64.03 9.12 2 2 2<br />
40° 56.93 63.82 10.71 53.25 68.38 9.34 2 2 2<br />
45° 62.10 68.31 10.91 2 2 2 2 2 2<br />
50° 67.47 73.55 11.01 2 2 2 2 2 2<br />
35° 11.47 11.45 12.02 10.68 12.19 10.52 9.89 12.84 9.24<br />
40° 12.71 11.92 12.80 11.86 12.72 11.19 11.00 13.45 9.81<br />
45° 14.04 12.40 13.59 13.11 13.27 11.86 2 2 2<br />
50° 15.45 12.91 14.37 14.44 13.86 12.50 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
CS 35 CS 40 CS 50 CS 60 CD 10<br />
Nominal Tons* 34.7 42 49.8 57.4 13<br />
L" x W" x H" 180" x 44" x 53" 180" x 44" x 53" 146" x 68" x 63" 146" x 68" x 63" 87" x 68" x 63"<br />
Shipping Weight 2,477 lbs. 2,655 lbs. 3,310 lbs. 3,456 lbs. 2,129 lbs.<br />
Refrigerant Circuits 1 1 1 1 2<br />
Refrigerant Charge (R-22) 45 lbs. 47 lbs. 59 lbs. 70 lbs. 12 lbs.<br />
Coil Pumpdown Capacity** 119.4 lbs. 119.4 lbs. 141.8 lbs. 141.8 lbs. 31.8 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 35 40 50 60 5 5<br />
Oil Charge 160 oz. 242 oz. 260 oz. 260 oz. 112 oz. 112 oz.<br />
Crankcase Heater Watts 100 100 <strong>20</strong>0 <strong>20</strong>0 70 70<br />
Suction Connection - ODS 2 1/8" 2 1/8" 2 5/8" 3 1/8" 1 1/8" 1 1/8"<br />
Liquid Line Connection - ODS 1 1/8" 1 1/8" 1 5/8" 1 5/8" 5/8" 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 40.7 40.7 48.3 48.3 21.7<br />
Rows / Fins Per Inch (FPI) 4 / 14 4 / 14 4 / 14 4 / 14 2 / 14<br />
Total CFM 22,500 26,000 28,500 40,800 12,000<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 3 / 28" 4 / 28" 4 / 28" 6 / 28" 2 / 24"<br />
Horsepower - Each 1 1 1 1 1/2<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 6,900<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
CD 15<br />
CD <strong>20</strong><br />
CD 30<br />
CD 40<br />
CD 45<br />
<strong>20</strong>AO<br />
Saturated<br />
Suction<br />
Temperature<br />
Unit Model Numbers<br />
CD 15 CD <strong>20</strong> CD 30 CD40 CD 45<br />
Nominal Tons* 17.8 25.9 35.0 39.0 43.5<br />
L" x W" x H" 87" x 68" x 63" 123" x 68" x 63" 123" x 68" x 63" 146" x 68" x 63" 146" x 68" x 63"<br />
Shipping Weight 2,263 lb. 2,632 lb. 2,863 lb. 3,245 lb. 3,280 lb.<br />
Refrigerant Circuits 2 2 2 2 2<br />
Refrigerant Charge (R-22) 18 lbs. 24 lbs. 38 lbs. 46 lbs. 55 lbs.<br />
Coil Pumpdown Capacity** 47.6 lbs. 55.8 lbs. 83.6 lbs. 106.4 lbs. 106.4 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 7.5 7.5 10 10 15 15 <strong>20</strong> <strong>20</strong> 25 25<br />
Oil Charge 144 oz. 144 oz. 144 oz. 144 oz. 144 oz. 144 oz. 136 oz. 136 oz. 136 oz. 136 oz.<br />
Crankcase Heater Watts 70 70 70 70 70 70 100 100 100 100<br />
Suction Connection - ODS 1 1/8" 1 1/8 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8"<br />
Liquid Line Connection - ODS 5/8" 5/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 1 1/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 21.7 37.7 37.7 48.3 48.3<br />
Rows / Fins Per Inch (FPI) 3 / 14 2 / 14 3 / 14 3 / 14 3 / 14<br />
Total CFM 15,000 26,<strong>20</strong>0 24,800 27,000 31,000<br />
CONDENSER FANS(s)<br />
Qty. / Diameter 2 / 28" 4 / 24" 4 / 28" 4 / 28" 4 / 28"<br />
Horsepower - Each 1 1/2 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 6,900 8,060 8,060 8,060<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 16.29 16.76 11.67 15.21 17.84 10.24 14.13 18.81 9.02<br />
40° 18.04 17.38 12.45 16.86 18.55 10.91 15.68 19.63 9.59<br />
45° 19.90 18.03 13.25 18.62 19.31 11.57 2 2 2<br />
50° 21.88 18.72 14.02 <strong>20</strong>.50 <strong>20</strong>.09 12.24 2 2 2<br />
35° 23.27 24.07 11.60 21.72 25.65 10.16 2 2 2<br />
40° 25.47 24.96 12.25 23.76 26.68 10.69 2 2 2<br />
45° 27.80 25.91 12.88 25.92 27.73 11.22 2 2 2<br />
50° 30.24 26.89 13.49 28.18 28.85 11.72 2 2 2<br />
35° 31.34 33.95 11.08 29.38 36.16 9.75 27.6 36.3 9.1<br />
40° 34.32 35.12 11.73 32.14 37.46 10.30 2 2 2<br />
45° 37.51 36.31 12.40 35.07 38.77 10.86 2 2 2<br />
50° 40.87 37.53 13.07 38.18 40.08 11.43 2 2 2<br />
35° 33.96 35.68 11.42 31.42 37.83 9.97 28.83 39.71 8.71<br />
40° 37.37 37.15 12.07 34.59 39.41 10.53 31.37 41.47 9.18<br />
45° 41.00 38.62 12.74 37.89 41.03 11.08 2 2 2<br />
50° 44.75 40.16 13.37 41.34 42.69 11.62 2 2 2<br />
35° 38.10 41.64 11.04 35.40 44.03 9.69 2 2 2<br />
40° 41.84 43.47 11.62 38.86 46.04 10.18 2 2 2<br />
45° 45.78 45.39 12.19 42.47 48.14 10.65 2 2 2<br />
50° 49.87 47.40 12.72 2 2 2 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Physical Data<br />
Capacity Data<br />
11
Model<br />
<strong>20</strong>AO<br />
CD 50<br />
CD 55<br />
CD 60<br />
CD 65<br />
CD 70<br />
12<br />
<strong>20</strong>AO<br />
Saturated<br />
Suction<br />
Temperature<br />
Unit Model Numbers<br />
CD 50 CD 55 CD 60 CD 65 CD 70<br />
Nominal Tons* 49.0 54.1 57.9 66.4 73.8<br />
L" x W" x H" 146" x 68" x 63" 146" x 68" x 63" 146" x 68" x 63" 180" x 88" x 63" 180" x 88" x 63"<br />
Shipping Weight 3,344 lbs. 3,504 lbs. 3,519 lbs. 4,577 lbs. 4,892 lbs.<br />
Refrigerant Circuits 2 2 2 2 2<br />
Refrigerant Charge (R-22) 63 lbs. 71 lbs. 71 78 lbs. 86 lbs.<br />
Coil Pumpdown Capacity** 141.8 lbs. 141.8 lbs. 141.8 lbs. 179.2 lbs. 238.8 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 25 25 25 30 30 30 30 35 35 35<br />
Oil Charge 136 oz. 136 oz. 136 oz. 152 oz. 152 oz. 152 oz. 152 oz. 160 oz. 160 oz. 160 oz.<br />
Crankcase Heater Watts 100 100 100 100 100 100 100 100 100 100<br />
Suction Connection - ODS 1 5/8" 1 5/8" 1 5/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8"<br />
Liquid Line Connection - ODS 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 48.3 48.3 48.3 81.4 81.4<br />
Rows / Fins Per Inch (FPI) 4 / 14 4 / 14 4 / 14 3 / 14 4 / 14<br />
Total CFM 28,500 40,800 40,800 49,000 46,000<br />
CONDENSER FANS(s)<br />
Qty. / Diameter 4 / 28" 6 / 28" 6 / 28" 6 / 28" 6 / 28"<br />
Horsepower - Each 1 1 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 8,060<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 43.18 45.94 11.28 40.40 48.77 9.94 2 2 2<br />
40° 47.46 47.91 11.89 44.34 50.99 10.44 2 2 2<br />
45° 51.94 50.00 12.47 48.52 53.26 10.93 2 2 2<br />
50° 56.65 52.15 13.04 2 2 2 2 2 2<br />
35° 46.71 52.76 10.66 43.64 55.83 9.40 2 2 2<br />
40° 51.31 55.01 11.24 47.92 58.35 9.90 2 2 2<br />
45° 56.14 57.38 11.80 52.41 60.98 10.37 2 2 2<br />
50° 61.22 59.87 12.35 2 2 2 2 2 2<br />
35° 49.76 58.24 10.26 46.41 61.47 9.06 2 2 2<br />
40° 54.60 60.92 10.76 50.88 64.43 9.48 2 2 2<br />
45° 59.69 63.72 11.24 2 2 2 2 2 2<br />
50° 65.02 66.68 11.70 2 2 2 2 2 2<br />
35° 56.67 61.18 11.13 52.92 65.11 9.77 49.11 68.73 8.59<br />
40° 62.22 63.68 11.74 58.08 67.90 10.29 53.87 71.84 9.02<br />
45° 68.11 66.29 12.36 63.56 70.80 10.80 2 2 2<br />
50° 74.34 69.05 12.96 69.36 73.84 11.30 2 2 2<br />
35° 62.54 66.04 11.36 58.36 70.40 9.95 54.13 74.50 8.72<br />
40° 68.65 68.77 11.98 64.00 73.41 10.46 59.31 77.79 9.15<br />
45° 75.15 71.56 12.60 70.03 76.50 10.99 2 2 2<br />
50° 82.02 74.55 13.<strong>20</strong> 76.37 79.79 11.49 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Physical Data<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
CD 75<br />
CD 80<br />
CD 90<br />
CD 100<br />
CD 110<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 68.13 74.11 11.06 63.62 78.82 9.71 2 2 2<br />
40° 74.69 77.40 11.62 69.68 82.44 10.18 2 2 2<br />
45° 81.61 80.87 12.16 76.10 86.25 10.63 2 2 2<br />
50° 88.92 84.58 12.68 82.88 90.27 11.07 2 2 2<br />
35° 74.48 82.97 10.77 69.64 88.15 9.48 2 2 2<br />
40° 81.66 86.59 11.32 76.33 92.14 9.94 2 2 2<br />
45° 89.<strong>20</strong> 90.48 11.83 83.33 96.41 10.37 2 2 2<br />
50° 97.18 94.62 12.32 90.76 100.94 10.79 2 2 2<br />
35° 81.98 88.16 11.18 76.77 93.94 9.82 71.45 99.37 8.64<br />
40° 89.98 91.91 11.78 84.23 98.10 10.33 2 2 2<br />
45° 98.45 95.91 12.36 92.16 102.51 10.82 2 2 2<br />
50° 107.39 100.18 12.90 100.46 107.21 11.28 2 2 2<br />
35° 87.86 96.51 10.92 82.21 102.63 9.61 2 2 2<br />
40° 96.43 100.83 11.48 90.18 107.40 10.08 2 2 2<br />
45° 105.45 105.46 12.00 98.59 112.50 10.52 2 2 2<br />
50° 114.97 110.38 12.50 107.40 117.90 10.93 2 2 2<br />
35° 97.73 102.<strong>20</strong> 11.48 91.76 109.26 10.09 85.52 116.66 8.81<br />
40° 107.35 107.50 12.01 100.76 115.27 10.52 93.90 123.38 9.16<br />
45° 117.51 113.42 12.48 110.27 121.95 10.90 2 2 2<br />
50° 128.16 1<strong>20</strong>.15 12.89 1<strong>20</strong>.23 129.46 11.22 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
CD 75 CD 80 CD 90 CD 100 CD 110<br />
Nominal Tons* 78.2 84 93.5 99.2 109.6<br />
L" x W" x H" 180" x 88" x 63" 180" x 88" x 63" 180" x 88" x 63" 180" x 88" x 63" 264" x 96" x 63"<br />
Shipping Weight 4,998 lbs. 5,268 lbs. 5,540 lbs. 5,814 lbs. 6,860 lbs.<br />
Refrigerant Circuits 2 2 2 2 2<br />
Refrigerant Charge (R-22) 94 lbs. 102 lbs. 114 lbs. 128 lbs. 137 lbs.<br />
Coil Pumpdown Capacity** 238.8 lbs. 238.8 lbs. 282.4 lbs. 282.4 lbs. 356.4 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 35 40 40 40 40 50 50 50 50 60<br />
Oil Charge 160 oz. 242 oz. 242 oz. 242 oz. 242 oz. 260 oz. 260 oz. 260 oz. 260 oz. 260 oz.<br />
Crankcase Heater Watts 100 100 100 100 100 <strong>20</strong>0 <strong>20</strong>0 <strong>20</strong>0 <strong>20</strong>0 <strong>20</strong>0<br />
Suction Connection - ODS 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 5/8" 2 5/8" 2 5/8" 2 5/8" 3 1/8"<br />
Liquid Line Connection - ODS 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 81.4 81.4 96 96 162<br />
Rows / Fins Per Inch (FPI) 4 / 14 4 / 14 4 / 14 4 / 14 3 / 14<br />
Total CFM 46,000 56,000 61,600 61,000 70,400<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 6 / 28" 8 / 28" 8 / 28" 8 / 28" 8 / 28"<br />
Horsepower - Each 1 1 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 8,060<br />
Capacity Data<br />
13
Model<br />
<strong>20</strong>AO<br />
CD 1<strong>20</strong><br />
CM 90<br />
CM 100<br />
CM 110<br />
CM 1<strong>20</strong><br />
14<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 105.77 111.71 11.36 99.38 119.39 9.99 2 2 2<br />
40° 116.08 118.52 11.75 109.00 127.16 10.29 2 2 2<br />
45° 126.89 126.47 12.04 119.17 136.09 10.51 2 2 2<br />
50° 134.19 135.73 12.22 129.69 146.44 10.63 2 2 2<br />
35° 81.54 85.28 11.47 76.37 90.90 10.08 71.05 96.11 8.87<br />
40° 89.58 88.76 12.11 83.86 94.81 10.62 77.98 100.50 9.31<br />
45° 98.08 92.44 12.73 91.83 98.86 11.14 2 2 2<br />
50° 107.06 96.30 13.34 100.19 103.15 11.65 2 2 2<br />
35° 86.97 90.76 11.50 81.42 96.55 10.12 75.63 101.84 8.91<br />
40° 95.63 94.53 12.14 89.46 100.83 10.65 2 2 2<br />
45° 104.71 98.52 12.75 97.94 105.<strong>20</strong> 11.17 2 2 2<br />
50° 114.32 102.63 13.37 106.84 109.77 11.68 2 2 2<br />
35° 95.30 97.62 11.72 89.29 104.17 10.29 83.00 110.21 9.04<br />
40° 104.84 101.56 12.39 98.<strong>20</strong> 108.69 10.84 91.33 115.24 9.51<br />
45° 114.98 105.64 13.06 107.62 113.30 11.40 2 2 2<br />
50° 125.64 109.91 13.72 117.60 118.10 11.95 2 2 2<br />
35° 101.74 108.27 11.28 95.10 115.16 9.91 88.24 121.50 8.71<br />
40° 111.76 113.02 11.87 104.46 1<strong>20</strong>.48 10.04 2 2 2<br />
45° 122.43 117.87 12.46 114.38 126.01 10.89 2 2 2<br />
50° 133.62 123.06 13.03 124.83 131.82 11.36 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
CD 1<strong>20</strong> CM 90 CM 100 CM 110 CM 1<strong>20</strong><br />
Nominal Tons* 115.2 92.6 98.5 108.9 116.3<br />
L" x W" x H" 264" x 96" x 63" 180" x 88" x 63" 180" x 88" x 63" 264" x 96" x 63" 264" x 96" x 63"<br />
Shipping Weight 6,866 lbs. 5,788 lbs. 6,<strong>20</strong>5 lbs. 7,346 lbs. 7,358 lbs.<br />
Refrigerant Circuits 2 2 2 2 2<br />
Refrigerant Charge (R-22) 148 lbs. 119 lbs. 136 lbs. 145 lbs. 161 lbs.<br />
Coil Pumpdown Capacity** 356.4 lbs. 282.4 lbs. 282.4 lbs. 356.4 lbs. 356.4 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 60 60 (1) 40 (2) 25 (2) 25 (2) 25 25/30 25/30 (2) 30 (2) 30<br />
Oil Charge 260 oz. 260 oz. 242 oz. 272 oz. 272 oz. 272 oz. 288 oz. 288 oz. 304 oz. 304 oz.<br />
Crankcase Heater Watts <strong>20</strong>0 <strong>20</strong>0 100 100 100 100 100 100<br />
Suction Connection - ODS 3 1/8" 3 1/8" 2 1/8" 2 5/8" 2 5/8" 2 5/8" 2 5/8" 2 5/8" 2 5/8" 2 5/8"<br />
Liquid Line Connection - ODS 1 5/8" 1 5/8" 1 1/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 5/8" 1 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 162 96 96 162 162<br />
Rows / Fins Per Inch (FPI) 3 /14 4 / 14 4 / 14 3 /14 3 / 14<br />
Total CFM 70,400 61,600 61,600 70.400 70,400<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 8 / 28" 8 / 28" 8 / 28" 8 / 28" 8 /28"<br />
Horsepower - Each 1 1 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 8,060<br />
Capacity Data
Model<br />
<strong>20</strong>AO<br />
CM 122<br />
CM 130<br />
CM 140<br />
CM 150<br />
CM 160<br />
<strong>20</strong>AO<br />
* Based on ARI Standard 5<strong>20</strong> (95°F Ambient and 45°F Saturated Suction Temperature)<br />
** Based on 80% of the coil volume at 90°F ambient.<br />
Saturated<br />
Suction<br />
Temperature<br />
85° Ambient 95° Ambient 105° Ambient<br />
Capacity KW 1 EER 1 Capacity KW 1 EER 1 Capacity KW 1 EER 1<br />
35° 107.28 110.79 11.62 100.48 118.42 10.18 93.46 125.45 8.94<br />
40° 117.87 114.95 12.30 110.35 123.09 10.76 102.60 130.69 9.42<br />
45° 129.11 119.25 12.99 1<strong>20</strong>.85 127.91 11.34 112.27 136.09 9.90<br />
50° 141.05 123.64 13.69 131.93 132.83 11.92 2 2 2<br />
35° 112.78 1<strong>20</strong>.98 11.19 105.35 129.12 9.79 98.03 136.81 8.60<br />
40° 124.29 125.89 11.85 116.16 134.59 10.36 108.08 142.89 9.08<br />
45° 136.65 131.03 12.51 127.72 140.30 10.92 2 2 2<br />
50° 149.88 136.46 13.18 140.04 146.43 11.48 2 2 2<br />
35° 123.95 134.06 11.09 115.51 142.67 9.72 107.04 150.65 8.53<br />
40° 135.97 139.77 11.67 126.63 148.86 10.21 2 2 2<br />
45° 148.65 145.73 12.24 138.35 155.41 10.68 2 2 2<br />
50° 162.13 152.02 12.80 150.73 162.30 11.14 2 2 2<br />
35° 135.53 147.14 11.05 126.77 156.85 9.70 118.06 166.12 8.53<br />
40° 148.81 153.55 11.63 139.21 163.89 10.19 2 2 2<br />
45° 162.95 160.31 12.<strong>20</strong> 152.39 171.44 10.67 2 2 2<br />
50° 177.93 167.64 12.74 166.31 179.46 11.12 2 2 2<br />
35° 149.66 164.63 10.90 140.03 175.06 9.60 130.25 184.93 8.46<br />
40° 164.05 171.72 11.46 153.46 182.93 10.07 2 2 2<br />
45° 179.35 179.26 12.01 167.76 191.15 10.53 2 2 2<br />
50° 195.45 187.34 12.52 182.71 <strong>20</strong>0.01 10.96 2 2 2<br />
1 KW and EER ratings are for the entire unit. 2 Consult factory.<br />
Unit Model Numbers<br />
CM 122 CM 130 CM 140 CM 150 CM 160<br />
Nominal Tons* 125.3 132.4 144 156.4 167.9<br />
L" x W" x H" 264" x 96" x 63" 264" x 96" x 63" 264" x 96" x 63" 264" x 96" x 63" 264" x 96" x 63"<br />
Shipping Weight 7,912 lbs. 7,954 lbs. 8,260 lbs. 8,856 lbs. 9,386 lbs.<br />
Refrigerant Circuits 2 2 2 2 2<br />
Refrigerant Charge (R-22) 161 lbs. 167 lbs. 183 lbs. <strong>20</strong>9 lbs. 225 lbs.<br />
Coil Pumpdown Capacity** 356.4 lbs. 356.4 lbs. 356.4 lbs. 475.2 lbs. 475.2 lbs.<br />
COMPRESSOR(s)<br />
Nominal Horsepower 25/35 25/35 30/35 30/35 (2) 35 (2) 35 35/40 35/40 (2) 40 (2) 40<br />
Oil Charge 296 oz. 296 oz. 312 oz. 312 oz. 3<strong>20</strong> oz. 3<strong>20</strong> oz. 402 oz. 402 oz. 484 oz. 484 oz.<br />
Crankcase Heater Watts 100 100 100 100 100 100 100 100 100 100<br />
Suction Connection - ODS 2 5/8" 2 5/8" 3 1/8" 3 1/8" 3 1/8" 3 1/8" 3 1/8" 3 1/8" 3 1/8" 3 1/8"<br />
Liquid Line Connection - ODS 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8" 1 5/8"<br />
CONDENSER<br />
Face Area - Sq. Ft. 162 162 162 162 162<br />
Rows / Fins Per Inch (FPI) 3 / 14 3 / 14 3 / 14 4 / 14 4 / 14<br />
Total CFM 97,<strong>20</strong>0 97,<strong>20</strong>0 97,<strong>20</strong>0 90,000 105,000<br />
CONDENSER FANS(s)<br />
Physical Data<br />
Qty. / Diameter 12 / 28" 12 / 28" 12 / 28" 12 / 28" 16 / 28"<br />
Horsepower - Each 1 1 1 1 1<br />
RPM 1,100 1,100 1,100 1,100 1,100<br />
Tip Speed (FPM) 8,060 8,060 8,060 8,060 8,060<br />
Capacity Data<br />
15
Model<br />
<strong>20</strong>AO<br />
16<br />
LS 3<br />
LS 5<br />
LS 8<br />
LS 9<br />
LS 10<br />
LS 13<br />
LS 15<br />
LD 10<br />
LD 15<br />
LD 18<br />
LD <strong>20</strong><br />
LD 26<br />
LD 30<br />
CS 5<br />
CS 8<br />
CS 10<br />
CS 15<br />
CS <strong>20</strong><br />
CS 25<br />
CS 30<br />
CS 35<br />
CS 40<br />
CS 50<br />
CS 60<br />
CD 10<br />
CD 15<br />
Compressor Fan Motors Single Power Supply Dual Power Supply Control<br />
Electrical<br />
RLA<br />
LRA<br />
HP Amps Unit Rec. Max. Unit Rec. Max. Amps<br />
Supply<br />
Qty<br />
#1 #2 #3 #4 #1 #2 #3 #4 (ea) (ea) MCA Fuse Fuse MCA Fuse Fuse 115 V<br />
230/1 17.9 — — — 88 — — —<br />
3.3 26 30 40 — — — 0.5<br />
<strong>20</strong>8-230/3 11.4 — — — 77 — — — 1 0.5 2.2 17 <strong>20</strong> 25 — — — 0.5<br />
460-3 5.7 — — — 39 — — — 1 9 10 15 — — — 0.5<br />
230/1 32.1 — — — 169 — — —<br />
3.3 44 50 75 — — — 0.5<br />
<strong>20</strong>8-230/3 19.3 — — — 123 — — — 1 .05 2.2 27 30 45 — — — 0.5<br />
460-3 10.0 — — — 62 — — — 1 14 15 <strong>20</strong> — — — 0.5<br />
<strong>20</strong>8-230/3 27.2 — — — 189 — — — 4.6 39 45 60 — — — 0.5<br />
1 1<br />
460-3 14.3 — — — 99 — — — 2.3 21 25 35 — — — 0.5<br />
<strong>20</strong>8-230/3 34.3 — — — 232 — — — 4.6 48 60 80 — — — 0.5<br />
1 1<br />
460-3 17.5 — — — 125 — — — 2.3 25 30 40 — — — 0.5<br />
<strong>20</strong>8-230/3 38.6 — — — 278 — — — 4.6 53 60 90 — — — 0.5<br />
1 1<br />
460-3 18.9 — — — 127 — — — 2.3 26 30 40 — — — 0.5<br />
<strong>20</strong>8-230/3 47.1 — — — 350 — — — 4.6 69 80 110 — — — 0.5<br />
2 1<br />
460-3 25,0 — — — 158 — — — 2.3 36 45 60 — — — 0.5<br />
<strong>20</strong>8-230/3 55.2 — — — 425 — — — 4.6 79 100 125 — — — 0.5<br />
2 1<br />
460-3 27.2 — — — 187 — — — 2.3 39 45 60 — — — 0.5<br />
230/1 32.1 32.1 — — 169 169 — —<br />
3.3 79 90 110 — — — 0.8<br />
<strong>20</strong>8-230/3 19.3 19.3 — — 123 123 — — 2 .05 2.2 48 50 60 — — — 0.8<br />
460-3 10.0 10.0 — — 62 62 — — 1 25 30 35 — — — 0.8<br />
<strong>20</strong>8-230/3 27.2 27.2 — — 189 189 — — 4.6 71 75 90 — — — 0.8<br />
2 1<br />
460-3 14.3 14.3 — — 99 99 — — 2.3 37 40 50 — — — 0.8<br />
<strong>20</strong>8-230/3 34.3 34.3 — — 232 232 — — 4.6 87 100 110 — — — 0.8<br />
2 1<br />
460-3 17.5 17.5 — — 125 125 — — 2.3 44 50 60 — — — 0.8<br />
<strong>20</strong>8-230/3 38.6 38.6 — — 278 278 — — 4.6 97 110 125 — — — 0.8<br />
2 1<br />
460-3 18.9 18.9 — — 127 127 — — 2.3 48 50 60 — — — 0.8<br />
<strong>20</strong>8-230/3 47.1 47.1 — — 350 350 — — 4.6 125 150 150 — — — 0.8<br />
4 1<br />
460-3 25.0 25.0 — — 158 158 — — 2.3 66 75 90 — — — 0.8<br />
<strong>20</strong>8-230/3 55.2 55.2 — — 425 425 — — 4.6 143 150 <strong>20</strong>0 — — — 0.8<br />
4 1<br />
460-3 27.2 27.2 — — 187 187 — — 2.3 71 75 90 — — — 0.8<br />
<strong>20</strong>8-230/3 22.3 — — — 1<strong>20</strong> — — — 2.2 31 35 50 — — — 0.5<br />
1 0.5<br />
460-3 10.5 — — — 60 — — — 1 15 <strong>20</strong> 25 — — — 0.5<br />
<strong>20</strong>8-230/3 32.0 — — — 169 — — — 4.6 45 60 75 — — — 0.5<br />
1 1<br />
460-3 14.1 — — — 85 — — — 2.3 <strong>20</strong> 25 30 — — — 0.5<br />
<strong>20</strong>8-230/3 43.6 — — — 215 — — — 4.6 64 75 100 — — — 0.5<br />
2 1<br />
460-3 <strong>20</strong>.0 — — — 106 — — — 2.3 30 35 50 — — — 0.5<br />
<strong>20</strong>8-230/3 59.6 — — — 275 — — — 4.6 84 100 125 — — — 0.5<br />
2 1<br />
460-3 29.0 — — — 138 — — — 2.3 41 50 60 — — — 0.5<br />
<strong>20</strong>8-230/3 66.0 — — — 308 — — — 4.6 92 110 150 — — — 0.9<br />
2 1<br />
460-3 33.0 — — — 154 — — — 2.3 46 60 75 — — — 0.9<br />
<strong>20</strong>8-230/3 82.2 — — — 428 — — — 4.6 112 150 175 — — — 0.9<br />
2 1<br />
460-3 41.1 — — — 214 — — — 2.3 56 70 90 — — — 0.9<br />
<strong>20</strong>8-230/3 94.0 — — — 470 — — — 4.6 132 175 225 — — — 0.9<br />
3 1<br />
460-3 47.0 — — — 235 — — — 2.3 66 80 110 — — — 0.9<br />
<strong>20</strong>8-230/3 125.1 — — — 565 — — — 4.6 171 <strong>20</strong>0 300 — — — 0.9<br />
3 1<br />
460-3 62.6 — — — 283 — — — 2.3 86 100 150 — — — 0.9<br />
<strong>20</strong>8/3 150.0 — — — 754 — — —<br />
4.6 <strong>20</strong>6 250 350 — — — 2<br />
<strong>20</strong>8-230/3 142.0 — — — 594 — — — 4 1 4.6 196 250 300 — — — 2<br />
460-3 71.0 — — — 297 — — — 2.3 98 125 150 — — — 2<br />
<strong>20</strong>8-230/3 180.0 — — — 1070 — — — 4.6 244 300 400 — — — 2<br />
4 1<br />
460-3 90.0 — — — 535 — — — 2.3 122 150 <strong>20</strong>0 — — — 2<br />
<strong>20</strong>8-230/3 224.0 — — — 1070 — — — 4.6 308 400 500 — — — 2<br />
6 1<br />
460-3 112.0 — — — 535 — — — 2.3 154 <strong>20</strong>0 250 — — — 2<br />
<strong>20</strong>8-230/3 22.3 22.3<br />
1<strong>20</strong> 1<strong>20</strong> — — 2.2 55 60 75 — — — 2<br />
2 0.5<br />
460-3 10.5 10.5<br />
60 60 — — 1 26 30 35 — — — 2<br />
<strong>20</strong>8-230/3 32.0 32.0<br />
169 169 — — 4.6 82 90 110 — — — 2<br />
2 1<br />
460-3 14.1 14.1<br />
85 85 — — 2.3 37 40 50 — — — 2<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
—<br />
Electrical Data<br />
NOTES: 1 - Voltage limits are as follows: Normal Voltage Min. Max.<br />
<strong>20</strong>8 187 229<br />
230 <strong>20</strong>8 253<br />
460 414 506<br />
2 - MCA (Minimum Circuit Ampacity) is calculated based on all concurrent loads applied<br />
to the circuit. (Largest load x 1.25 + 100% of all other loads excluding the control<br />
circuit.) Use copper conductors only.<br />
3 - “Max Fuse” refers to the maximum size dual element fuse allowed. Fuse clips<br />
should be provided based on this rating. (Largest load x 2.25 + 100% of all other loads.)
Electrical Data<br />
Compressor Fan Motors Single Power Supply Dual Power Supply Control<br />
Model Electrical<br />
RLA<br />
LRA<br />
HP Amps Unit Rec. Max. Unit Rec. Max. Amps<br />
<strong>20</strong>AO Supply<br />
Qty<br />
#1 #2 #3 #4 #1 #2 #3 #4 (ea) (ea) MCA Fuse Fuse MCA Fuse Fuse 115 V<br />
CD <strong>20</strong><br />
<strong>20</strong>8-230/3 43.6 43.6 — — 215 215 — — 2.2 107 125 150 — — — 2<br />
4 0.5<br />
460-3 <strong>20</strong>.0 <strong>20</strong>.0 — — 106 106 — — 1 49 60 60 — — — 2<br />
CD 30<br />
<strong>20</strong>8-230/3 59.6 59.6 — — 275 275 — — 4.6 153 175 <strong>20</strong>0 — — — 2<br />
4 1<br />
460-3 29.0 29.0 — — 138 138 — — 2.3 75 80 100 — — — 2<br />
CD 40<br />
<strong>20</strong>8-230/3 66.0 66.0 — — 308 308 — — 4.6 167 <strong>20</strong>0 225 — — — 2<br />
4 1<br />
460-3 33.0 33.0 — — 154 154 — — 2.3 84 90 110 — — — 2<br />
CD 45<br />
<strong>20</strong>8-230/3 82.2 66.0 — — 428 308 — — 4.6 188 225 250 — — — 2<br />
4 1<br />
460-3 41.1 33.0 — — 214 154 — — 2.3 94 110 125 — — — 2<br />
CD 50<br />
<strong>20</strong>8-230/3 82.2 82.2 — — 428 428 — — 4.6 <strong>20</strong>4 225 250 — — — 2<br />
4 1<br />
460-3 41.1 41.1 — — 214 214 — — 2.3 102 110 125 — — — 2<br />
CD 55<br />
<strong>20</strong>8-230/3 94.0 82.2 — — 470 428 — — 4.6 228 250 300 — — — 2<br />
6 1<br />
460-3 47.0 41.1 — — 235 214 — — 2.3 114 125 150 — — — 2<br />
CD 60<br />
<strong>20</strong>8-230/3 94.0 94.0 — — 470 470 — — 4.6 240 300 300 — — — 2<br />
6 1<br />
460-3 47.0 47.0 — — 235 235 — — 2.3 1<strong>20</strong> 150 150 — — — 2<br />
CD 65<br />
<strong>20</strong>8-230/3 125.1 94.0 — — 565 470 — — 4.6 278 350 400 — — — 2<br />
6 1<br />
460-3 62.6 47.0 — — 283 235 — — 2.3 140 150 <strong>20</strong>0 — — — 2<br />
CD 70<br />
<strong>20</strong>8-230/3 125.1 125.1 — — 565 565 — — 4.6 310 350 400 — — — 2<br />
6 1<br />
460-3 62.6 62.6 — — 283 283 — — 2.3 155 175 <strong>20</strong>0 — — — 2<br />
<strong>20</strong>8/3 150.0 125.1 — — 754 565 — —<br />
4.6 341 400 450 — — — 3<br />
CD 75 230/3 142.0 125.1 — — 594 565 — — 6 1 4.6 331 400 450 — — — 3<br />
460-3 71.0 62.6 — — 297 283 — — 2.3 166 <strong>20</strong>0 225 — — — 3<br />
<strong>20</strong>8/3 150.0 150.0 — — 754 754 — —<br />
4.6 — — — <strong>20</strong>6 250 350 4<br />
CD 80 230/3 142.0 142.0 — — 594 594 — — 8 1 4.6 357 400 500 — — — 4<br />
460-3 71.0 71.0 — — 297 297 — — 2.3 179 <strong>20</strong>0 225 — — — 4<br />
<strong>20</strong>8/3 180.0 150.0 — — 754 1070 — —<br />
4.6 — — — 244 300 400 4<br />
CD 90 <strong>20</strong>8-230/3 180.0 142.0 — — 594 1070 — — 8 1 4.6 — — — 244 300 400 4<br />
460-3 90.0 71.0 — — 297 535 — — 2.3 <strong>20</strong>2 225 300 — — — 4<br />
CD 100 <strong>20</strong>8-230/3 180 180 — — 1070 1070 — — 4.6 — — — 244 300 400 4<br />
8 1<br />
460-3 90 90 — — 535 535 — — 2.3 221 250 300 — — — 4<br />
CD 110 <strong>20</strong>8-230/3 224 180 — — 1070 1070 — — 4.6 — — — 299 350 500 4<br />
8 1<br />
460-3 112 90 — — 535 535 — — 2.3 249 275 350 — — — 4<br />
CD 1<strong>20</strong> <strong>20</strong>8-230/3 224 224 — — 1070 1070 — — 4.6 — — — 299 350 500 4<br />
8 1<br />
460-3 112 112 — — 535 535 — — 2.3 271 300 350 — — — 4<br />
<strong>20</strong>8/3 150.0 82.2 82.2 — 754 428 428 —<br />
4.6 — — — <strong>20</strong>6 250 350 4<br />
CM 90 230/3 142.0 82.2 82.2 — 594 428 428 — 8 1 4.6 379 450 500 — — — 4<br />
460-3 71.0 41.1 41.1 — 297 214 214 — 2.3 190 <strong>20</strong>0 250 — — — 4<br />
CM 100 <strong>20</strong>8-230/3 82.2 82.2 82.2 82.2 428 428 428 428 4.6 — — — <strong>20</strong>4 225 275 4<br />
8 1<br />
460-3 41.1 41.1 41.1 41.1 214 214 214 214 2.3 194 <strong>20</strong>0 225 — — — 4<br />
CM 110 <strong>20</strong>8-230/3 94.0 94.0 82.2 82.2 470 470 428 428 4.6 — — — 219 250 300 4<br />
8 1<br />
460-3 47.0 47.0 41.1 41.1 235 235 214 214 2.3 <strong>20</strong>7 225 250 — — — 4<br />
CM 1<strong>20</strong> <strong>20</strong>8-230/3 94.0 94.0 94.0 94.0 470 470 470 470 4.6 — — — 230 250 300 4<br />
8 1<br />
460-3 47.0 47.0 47.0 47.0 235 235 235 235 2.3 219 225 250 — — — 4<br />
CM 122 <strong>20</strong>8-230/3 125.1 125.1 82.2 82.2 565 565 428 428 4.6 — — — 267 300 400 4<br />
12 1<br />
460-3 62.6 62.6 41.1 41.1 283 283 214 214 2.3 251 275 300 — — — 4<br />
CM 130 <strong>20</strong>8-230/3 125.1 125.1 94.0 94.0 565 565 470 470 4.6 — — — 278 350 400 4<br />
12 1<br />
460-3 62.6 62.6 47.0 47.0 283 283 235 235 2.3 263 275 300 — — — 4<br />
CM 140 <strong>20</strong>8-230/3 125.1 125.1 125.1 125.1 565 565 565 565 4.6 — — — 310 350 400 4<br />
12 1<br />
460-3 62.6 62.6 62.6 62.6 283 283 283 283 2.3 294 350 350 — — — 4<br />
<strong>20</strong>8/3 150.0 150.0 125.1 125.1 754 754 565 565<br />
4.6 — — — 341 400 450 6<br />
CM 150 230/3 142.0 142.0 125.1 125.1 594 594 565 565 12 1 4.6 — — — 331 400 450 6<br />
460-3 71.0 71.0 62.6 62.6 297 297 283 283 2.3 313 350 350 — — — 6<br />
<strong>20</strong>8/3 150.0 150.0 150.0 150.0 754 754 754 754<br />
4.6 — — — 375 400 500 7<br />
CM 160 230/3 142.0 142.0 142.0 142.0 594 594 594 594 16 1 4.6 — — — 357 400 500 7<br />
460-3 71.0 71.0 71.0 71.0 297 297 297 297 2.3 339 350 400 — — — 7<br />
NOTES: 1 - Voltage limits are as follows: Normal Voltage Min. Max.<br />
<strong>20</strong>8 187 229<br />
230 <strong>20</strong>8 253<br />
460 414 506<br />
2 - MCA (Minimum Circuit Ampacity) is calculated based on all concurrent loads applied to the<br />
circuit. (Largest load x 1.25 + 100% of all other loads excluding the control circuit.) Use copper<br />
conductors only.<br />
3 - “Max Fuse” refers to the maximum size dual element fuse allowed. Fuse clips should be<br />
provided based on this rating. (Largest load x 2.25 + 100% of all other loads.)<br />
4 - Dual power supply amperages are shown for circuit with highest amperage where applicable.<br />
17
Typical Wiring Diagram<br />
LEGEND<br />
CD UNITS<br />
18
Dimensional Data<br />
B<br />
L<br />
B<br />
C<br />
W<br />
C<br />
Recommended Minimum<br />
Service Clearance<br />
Compressor<br />
Access Panel<br />
3 3/4"<br />
Electrical<br />
Entrance<br />
Hinged<br />
Control<br />
Panel<br />
H<br />
1 1/8" 1 1/8"<br />
W<br />
2.5"ø Diameter Rigging Holes<br />
* 5/8"ø Diameter Mounting Holes<br />
3 1/2" D<br />
3 1/2"<br />
L<br />
MODEL NUMBER<br />
W L H<br />
UNIT DIMENSIONS<br />
Fans<br />
Qty./Dia.<br />
Recommended Minimum<br />
Service Clearance<br />
<strong>20</strong>AO LS 3 34" 76" 46" 1 / 24" 60" 34" —<br />
<strong>20</strong>AO LS 5 34" 76" 46" 1 / 24" 60" 34" —<br />
<strong>20</strong>AO LS 8 34" 87" 46" 1 / 28" 60" 34" —<br />
<strong>20</strong>AO LS 9 34" 87" 46" 1 / 28" 60" 34" —<br />
<strong>20</strong>AO LS 10 34" 87" 46" 1 / 28" 60" 34" —<br />
<strong>20</strong>AO LS 13 34" 1<strong>20</strong>" 46" 2 / 28" 60" 34" 56.5"<br />
<strong>20</strong>AO LS 15 34" 1<strong>20</strong>" 46" 2 / 28" 60" 34" 56.5"<br />
B<br />
C<br />
D<br />
<strong>20</strong>AO CS 5 34" 76" 46" 1 / 24" 60" 34" —<br />
<strong>20</strong>AO CS 8 34" 87" 46" 1 / 28" 60" 34" —<br />
<strong>20</strong>AO CS 10 34" 1<strong>20</strong>" 46" 2 / 28" 60" 34" 56.5"<br />
<strong>20</strong>AO CS 15 34" 1<strong>20</strong>" 46" 2 / 28" 60" 34" 56.5"<br />
<strong>20</strong>AO CS <strong>20</strong> 34" 1<strong>20</strong>" 46" 2 / 28" 60" 34" 56.5"<br />
<strong>20</strong>AO CS 25 34" 143" 53" 2 / 28" 60" 34" 68"<br />
<strong>20</strong>AO CS 30 34" 143" 53" 3 / 28" 60" 34" 68"<br />
<strong>20</strong>AO CS 35 44" 180" 53" 3 / 28" 60" 44" 86.5"<br />
<strong>20</strong>AO CS 40 44" 180" 53" 4 / 28" 60" 44" 86.5"<br />
<strong>20</strong>AO CS 50 68" 146" 63" 4 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CS 60 68" 146" 63" 6 / 28" 60" 68" 68"<br />
19
Dimensional Data<br />
B<br />
L<br />
B<br />
C<br />
W<br />
W<br />
C<br />
Recommended Minimum<br />
Service Clearance<br />
Compressor<br />
Access Panel<br />
3 3/4"<br />
Electrical<br />
Hinged<br />
Entrance<br />
Control Panel<br />
H<br />
1 1/8" 1 1/8" 3 1/2" D<br />
3 1/2"<br />
W<br />
L<br />
2.5"ø Diameter Rigging Holes<br />
* 5/8"ø Diameter Mounting Holes<br />
MODEL NUMBER<br />
W L H<br />
UNIT DIMENSIONS<br />
Fans<br />
Qty./Dia.<br />
Recommended Minimum<br />
Service Clearance<br />
<strong>20</strong>AO LD 10 68" 76" 63" 2 / 24" 60" 68" —<br />
<strong>20</strong>AO LD 15 68" 87" 63" 2 / 28" 60" 68" —<br />
<strong>20</strong>AO LD 18 68" 87" 63" 2 / 28" 60" 68" —<br />
<strong>20</strong>AO LD <strong>20</strong> 68" 87" 63" 2 / 28" 60" 68" —<br />
<strong>20</strong>AO LD 26 68" 123" 63" 4 / 28" 60" 68" 56.5"<br />
<strong>20</strong>AO LD 30 68" 123" 63" 4 / 28" 60" 68" 56.5"<br />
B<br />
C<br />
D<br />
<strong>20</strong><br />
<strong>20</strong>AO CD 10 68" 87" 63" 2 / 24" 60" 68" —<br />
<strong>20</strong>AO CD 15 68" 87" 63" 2 / 28" 60" 68" —<br />
<strong>20</strong>AO CD <strong>20</strong> 68" 123" 63" 4 / 24" 60" 68" 56.5"<br />
<strong>20</strong>AO CD 30 68" 123" 63" 4 / 28" 60" 68" 56.5"<br />
<strong>20</strong>AO CD 40 68" 146" 63" 4 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CD 45 68" 146" 63" 4 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CD 50 68" 146" 63" 4 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CD 55 68" 146" 63" 6 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CD 60 68" 146" 63" 6 / 28" 60" 68" 68"<br />
<strong>20</strong>AO CD 65 88" 180" 63" 6 / 28" 60" 88" 86.5"<br />
<strong>20</strong>AO CD 70 88" 180" 63" 6 / 28" 60" 88" 86.5"<br />
<strong>20</strong>AO CD 75 88" 180" 63" 6 / 28" 60" 88" 86.5"<br />
<strong>20</strong>AO CD 80 88" 180" 63" 8 / 28" 60" 88" 86.5"
Dimensional Data<br />
B<br />
L<br />
B<br />
C<br />
W<br />
C<br />
Recommended Minimum<br />
Service Clearance<br />
Compressor<br />
Access Panel<br />
3 3/4"<br />
Hinged<br />
Control Panel<br />
H<br />
1 1/8" 1 1/8"<br />
W<br />
3 1/2" D<br />
D<br />
3 1/2"<br />
L<br />
*<br />
2.5"ø Diameter Rigging Holes<br />
5/8"ø Diameter Mounting Holes<br />
MODEL NUMBER<br />
W L H<br />
UNIT DIMENSIONS<br />
Fans<br />
Qty./Dia.<br />
Recommended Minimum<br />
Service Clearance<br />
<strong>20</strong>AO CD 90 88" 180" 63" 8 / 28" 60" 88" 57.67"<br />
<strong>20</strong>AO CD 100 88" 180" 63" 8 / 28" 60" 88" 57.67"<br />
<strong>20</strong>AO CD 110 96" 264" 63" 8 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CD 1<strong>20</strong> 96" 264" 63" 8 / 28" 60" 96" 85.67"<br />
B<br />
C<br />
D<br />
<strong>20</strong>AO CM 90 88" 180" 63" 8 / 28" 60" 88" 57.67"<br />
<strong>20</strong>AO CM 100 88" 180" 63" 8 / 28" 60" 88" 57.67"<br />
<strong>20</strong>AO CM 110 96" 264" 63" 8 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 1<strong>20</strong> 96” 264" 63" 8 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 122 96" 264" 63" 12 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 130 96" 264" 63" 12 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 140 96" 264" 63" 12 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 150 96" 264" 63" 12 / 28" 60" 96" 85.67"<br />
<strong>20</strong>AO CM 160 96" 264" 63" 16 / 28" 60" 96" 85.67"<br />
21
Installation and Application<br />
<strong>Units</strong> are designed for outdoor installation and<br />
must be installed to allow unrestricted air flow.<br />
Unit must be mounted on a level, solid surface to<br />
minimize vibration and noise.<br />
The following must be observed:<br />
1. Wiring to the unit to follow recommendations<br />
on unit wiring diagram, and in accordance with all<br />
state and local codes.<br />
2. Piping to be sized on velocities and pressure<br />
drop at design conditions, and not be based on<br />
condensing unit or evaporator connection sizes.<br />
3. All piping to be type “K” or “L” and installed in<br />
accordance with good piping practices. Interior<br />
of all piping to be clean and dry, and a nitrogen<br />
purge used during soldering.<br />
4. If units are mounted on vibration isolator bases,<br />
all lines must have vibrasorbers installed and<br />
properly secured.<br />
5. After piping is completed, a good vacuum pump<br />
must be used to evacuate the refrigerant system<br />
before charging with refrigerant.<br />
6. After system charging, a qualified service<br />
technician should put the system into operation.<br />
All safety controls should be functioned to insure<br />
that controls are properly adjusted and functional.<br />
All operating controls should be cycled to<br />
determine that control points are correct for design<br />
requirements.<br />
NOTE: Consult IOM manuals for further information on<br />
<strong>Condensing</strong> Unit Installation and Application.<br />
Sequence Of Operation<br />
The <strong>Series</strong> <strong>20</strong> <strong>Air</strong> <strong>Cooled</strong> <strong>Condensing</strong> <strong>Units</strong> are<br />
standard with the following safety and operation<br />
controls and features:<br />
A. High Pressure Failure Control (Manual Reset)<br />
B. Low Pressure Operating Control (Auto Pumpdown)<br />
C. Oil Failure Control (Manual Reset) - C <strong>Series</strong> Only<br />
D. Compressor Crankcase Heater<br />
E. Compressor and Condenser Fan Motor Contactors<br />
F. Compressor Fusing<br />
G. Control Circuit Fusing<br />
H. Fan Cycling Control for Low Ambient Operation<br />
The following sequence assumes a single compressor unit.<br />
On an initial start-up, with the application temperature<br />
above the temperature control setting, typical<br />
sequence is as follows:<br />
When the temperature control (remote thermostat)<br />
normally open contacts close, the liquid line solenoid<br />
will be energized, and liquid refrigerant will flow into<br />
evaporator circuit. As low side pressure builds to<br />
set point of low pressure control (auto pumpdown)<br />
the flow pressure control will make and energize<br />
the compressor and compressor will run. Discharge<br />
pressure will rise and condenser fans will be energized<br />
as discharge pressure reaches set point of fan cycle<br />
control.<br />
As the cooling requirements are satisfied, the<br />
temperature control will open and de-energize the<br />
liquid line solenoid. The flow of liquid refrigerant<br />
will stop and compressors will pump the remaining<br />
refrigerant out of the evaporator circuit.<br />
When the low side pressure reaches the low set point<br />
of low pressure control, the control will open and deenergize<br />
compressor contactor and compressor will<br />
cycle off. Compressor will remain off until additional<br />
cooling is required and a repeat of this sequence will<br />
be followed.<br />
On dual compressor units, the second compressor<br />
circuit will follow the same sequence as outlined<br />
above on call of the second step of temperature<br />
control.<br />
On multiple compressor (3 or more) units, two<br />
independent circuits are utilized and sequence will<br />
be identical to a dual compressor unit. The only<br />
difference is that each compressor will be cycled to<br />
give steps of control equal to number of compressors.<br />
Lead compressors of a circuit will operate on<br />
pumpdown control and lag compressor of circuit<br />
will be controlled directly by step of temperature or<br />
pressure control.<br />
Compressor and fan contactors are wired in series<br />
with all safety controls and a failure of any safety<br />
control will be de-energize compressor and fans<br />
without pumpdown. Safety controls require manual<br />
reset and cause of failure should be determined and<br />
corrected before returning unit to operation.<br />
22
Low Ambient Operation<br />
LOW AMBIENT OPERATION - <strong>Air</strong> conditioning<br />
systems utilizing air cooled condensing<br />
units when operated at ambient temperatures<br />
well below design, will require some type of<br />
control to stabilize high side pressure. In order<br />
to maintain sufficient high side pressure, the<br />
condenser capacity must be reduced in response<br />
to decreasing head pressure. This may be<br />
accomplished by either reducing the air flow across<br />
the condenser, or reducing the effective condenser<br />
surface by “flooding” the condenser coil with liquid<br />
refrigerant. <strong>Air</strong> reduction by fan staging is standard<br />
on all air cooled condensing units, with condenser<br />
flooding available as an option.<br />
PRESSURE SETTINGS<br />
R-22 (PSIG)<br />
CONTROL<br />
CUT IN CUT OUT<br />
High Pressure Manual 400<br />
Low Pressure 50 <strong>20</strong><br />
Freeze Control Manual 54<br />
Unloader “A” 60 *<br />
Unloader “B” 55 *<br />
Fan Cycle/Delay 250 <strong>20</strong>0<br />
2 Step Step 1 2<strong>20</strong> <strong>20</strong>0<br />
Fan Cycle Step 2 250 230<br />
Step 1 2<strong>20</strong> <strong>20</strong>0<br />
3 Step<br />
Step 2 230 210<br />
Fan Cycle<br />
Step 3 250 230<br />
Step 1 2<strong>20</strong> <strong>20</strong>0<br />
4 Step Step 2 230 210<br />
Fan Cycle Step 3 240 230<br />
Step 4 250 240<br />
* Adjusted per application requirements.<br />
FAN CYCLING +<strong>20</strong>°F (Standard) - Fan<br />
cycling operates by staging condenser fans in<br />
response to decreasing high side pressure. This<br />
system is normally satisfactory for unit operation<br />
down to ambients of <strong>20</strong>°F. An additional feature of<br />
this system is the energy savings realized by having<br />
fans inoperative during low load or low ambient<br />
conditions.<br />
The staging arrangement and pressure settings are<br />
as shown. Numerals indicate the pressure steps at<br />
which the fans are staged.<br />
FAN CYCLING 0°F (OPTIONAL) - In<br />
addition to the cycling controls, a “positive start”<br />
electrical circuit is added to insure system operation.<br />
Normal operating sequence is for compressor<br />
operation to be obtained when the low pressure<br />
switch closes upon an increase in low side pressure.<br />
Since low ambients may preclude sufficient pressure<br />
being obtained, this option momentarily shunts the<br />
low pressure switch, enabling the compressor to operate. At<br />
the end of 90 seconds, the timer opens the shunt, returning<br />
control to the low pressure switch.<br />
FLOOD CONTROL B<strong>20</strong> (Optional) - B<strong>20</strong> flood<br />
control utilizes a valve (or valves) mounted, piped and<br />
adjusted to regulate condensing pressure by flooding the<br />
condenser coil with liquid refrigerant. This option does require<br />
additional refrigerant (flooding charge) in the system and<br />
liquid receivers.<br />
During the normal cycle, the valve will prevent flow from the<br />
discharge line into the receiver, and allow free flow of liquid<br />
from the condenser. As the receiver pressure drops below 180<br />
PSIG the valve will modulate allowing discharge gas to enter<br />
the receiver, and restrict flow from the condenser. The valve<br />
continues to modulate in this manner, maintaining a constant<br />
receiver pressure, and coil flooding level to maintain a<br />
minimum 180 PSIG liquid pressure for proper expansion valve<br />
operation. In addition, a positive start electrical circuit will<br />
shunt around the low pressure (pumpdown) control and force<br />
the compressor to run whenever a call for cooling is initiated.<br />
A B C<br />
1 1 2 1 2 3<br />
D<br />
1 2 3 4<br />
E F G<br />
1<br />
1<br />
H<br />
1 2 3 4<br />
1 2 3 4<br />
1 2<br />
1 2<br />
J<br />
1 1 2 2 3 3 4 4<br />
1 1 2 2 3 3 4 4<br />
1 2 3<br />
1 2 3<br />
I<br />
1 1 2 2 3 4<br />
1 1 2 2 3 4<br />
A B C D E F G H I J<br />
LS3 LS13 CS30 CS40 LD10 LD26 CS60 CD80 CM122 CM160<br />
LS5 LS15 CS35 LD15 LD30 CD55 CD90 CM130<br />
LS8 CS10 LD18 CS50 CD60 CD100 CM140<br />
LS9 CS15 LD<strong>20</strong> CD<strong>20</strong> CD65 CD110 CM150<br />
LS10 CS<strong>20</strong> CD10 CD30 CD70 CD1<strong>20</strong><br />
CS5 CS25 CD15 CD40 CD75 CM90<br />
CS8 CD45 CM100<br />
CD50 CM110<br />
CM1<strong>20</strong><br />
23
Engineering Specifications<br />
CABINET<br />
<strong>Units</strong> shall be constructed of mill galvanized sheet steel<br />
having formed frame members and removable access<br />
panels. <strong>Units</strong> shall have a formed steel perimeter<br />
base rail, except for CD90 and larger units shall have<br />
structural steel welded bases. All refrigerant containing<br />
vessels are to be constructed in accordance with ANSI<br />
B9.1 code. Each electrical component is to be U.L.<br />
approved and applied in accordance with its appropriate<br />
usage. All wiring and electrical construction shall be in<br />
accordance with the NEC. <strong>Units</strong> shall be ETL certified<br />
and labeled. Each unit shall be given a complete factory<br />
electrical run test.<br />
COMPRESSOR(S)<br />
All CS, CD and CM models shall have accessible hermetic<br />
design motor/compressor unit having all rotating<br />
parts statically and dynamically balanced, full pressure<br />
lubrication, automatically reversible oil pump, oil charge,<br />
suction and oil strainer, and sight glass for visual oil<br />
check. Compressor to have crankcase heater, suction<br />
and discharge service valve. Compressor shall be rated<br />
in accordance with ASHRAE 23. Motor shall be suction<br />
gas cooled. Compressor shall contain inherent overload<br />
and overheat protector, consisting of winding embedded<br />
sensors. Four and six cylinder compressors shall<br />
be connected to a solid state protection module. Protection<br />
module shall open all three phases in the event of<br />
overload in one phase. External thermal protection shall<br />
not be acceptable.<br />
All LS and LD models shall incorporate hermetic<br />
sealed scroll compressors having all rotating parts<br />
statically and dynamically balance with full pressure<br />
lubrication and charged with oil. Compressor to have<br />
crankcase heater, suction and discharge service valve.<br />
Compressor shall be rated in accordance with ASHRAE<br />
23. Motor shall be suction gas cooled. Compressor<br />
shall contain inherent overload and overheat protector<br />
consisting of winding embedded sensors.<br />
CONDENSER(S)<br />
The condenser coil shall be constructed of 1/2” O.D.<br />
copper tube with die formed tempered aluminum plate<br />
fins. Fins are formed with full collars and tubes are<br />
mechanically expanded for full contact and optimum<br />
heat transfer. Fin collar to completely cover tube<br />
surface. Condenser coils shall be tested to 400 PSIG.<br />
Casings are mill galvanized 16-gauge steel. Tube<br />
sheets are die formed and full collared for the tube<br />
support. Condenser coils shall be circuited to match<br />
refrigerant circuits and baffled to prevent crossover<br />
flow. Headers are constructed of heavy wall<br />
seamless copper tubing.<br />
SUB COOLING COIL<br />
A separate sub cooling coil, integral with the main<br />
condenser coil, shall be provided for each circuit.<br />
CONDENSER FANS<br />
Fans are direct drive propeller type with aluminum<br />
blades. <strong>Air</strong> discharge to be vertical to minimize noise<br />
generation and air recirculation. Fan to rotate within<br />
a formed (spun) venturi and shall be protected with<br />
epoxy powder coated fan guard. Condenser plenum<br />
shall be compartmentalized to prevent air crossover.<br />
Unit shall be equipped with a fan cycle control to<br />
allow mechanical cooling operation at ambient as<br />
low as +<strong>20</strong>°F. Motors are three-phase, 1140 RPM<br />
specifically designed for vertical shaft, direct drive<br />
fan application and utilize permanently lubricated<br />
ball bearings. Motor to contain inherent, overload<br />
protection. Fan/motor assembly to be mounted in<br />
steel rod mounting bracket to reduce air turbulence<br />
and vibration.<br />
REFRIGERATION CIRCUIT<br />
Single or dual compressor models shall have totally<br />
independent refrigeration circuits with a liquid line<br />
shut-off and charging connection. On multiple<br />
compressor machines, an oil equalization system<br />
utilizing an oil reservoir, oil level regulator, and a<br />
regulating valve shall be employed.<br />
CONTROL CIRCUIT AND PANEL<br />
Shall include all safety and operating controls<br />
required to meet ARI, UL and NEC requirements.<br />
Controls to include branch and sub-circuit fusing,<br />
contactors, relays and pressure controls. Unit to<br />
operate on demand cycle pumpdown control and<br />
have low charge protection through a pressure<br />
sensing device. All safety controls to be manual<br />
reset. Panel to be constructed to NEMA 3R<br />
requirements and UL 508 listed and labeled.