Design and Areas of Application<br />

Single Duct with Supply Air/<br />

Extract Air Dependent Control<br />

Extract<br />

air<br />

TVA<br />

TVR<br />

TVJ<br />

Constant Differential Control<br />

Extract air volume flow<br />

Ratio Control<br />

Extract air volume flow<br />

250<br />

l/s<br />

200<br />

150<br />

100<br />

50<br />

Differential ± 0<br />

TVR + 50 m 3 /h<br />

TVJ - 50 m 3 /h<br />

Ratio ± 0<br />

Ratio + 10 %<br />

Ratio - 10 %<br />

TVZ<br />

TVS<br />

TVR<br />

TVJ<br />

0<br />

0 50 100 150 200 l/s 250<br />

250<br />

l/s<br />

200<br />

150<br />

100<br />

50<br />

t<br />

Supply air volume flow (actual value)<br />

0<br />

0 50 100 150 200 l/s 250<br />

Supply air volume flow (actual value)<br />

Supply<br />

air<br />

5<br />

Single Duct System<br />

The supply air volume flow controller receives a control<br />

signal from the room temperature controller and holds<br />

the supply air volume flow, at the specified set value. The<br />

controller adjusts the air quantity between the specified<br />

V · min and V · max values.<br />

Suply Air/Extract Air Slave Control<br />

In individual rooms and closed office areas, the balance<br />

between supply air and extract air must be maintained to<br />

avoid whistling noises through gaps around doors etc.,<br />

or making doors difficult to open and close. For this, the<br />

actual value of the supply air is monitored at the extract<br />

air volume flow controller. Thus the extract air volume<br />

flow in every operating situation follows the supply air.<br />

When designing the required volume flow differences,<br />

it must be ensured that the proposed controller can<br />

achieve the required constant differential or ratio control.<br />

When ordering VAV terminal units, the allocation by room<br />

numbers must be given. This allocation must be taken<br />

into account when the units are installed. VAV terminal<br />

units types TVA, TVR and TVJ are designed for use in<br />

normal air conditioning systems with extract air without<br />

high dust levels and without aggressive elements in the<br />

air. For extremely dusty extract air (grease, sticky dust),<br />

membrane pressure transducers must be provided and<br />

regular maintenance planned. For aggressive extract air,<br />

volume flow controllers of suitable materials are available.<br />

Order Example<br />

In accordance with sales leaflet and price list for ratio<br />

control:<br />

TVZ-R/160/B13/M2-30-250 l/s<br />

TVA -R/160/B13/S2-27-225 l/s