Belimo VRD2 - TROX
Belimo VRD2 - TROX Belimo VRD2 - TROX
Belimo VRP Slave Control RT Controller Master Controller Operating Mode M, E Slave Controller Supply/Extract Air Slave Control for Dual Duct Unit TVM Operating Mode S RT Controller Cold Controller Warm Controller Operating Mode M, (E,F) Slave Controller Operating Mode S TVM 9 Supply/Extract Air Slave Control (Master/Slave) With parallel control of the units, an undesirable difference between supply and extract air can occur if the pressure in one duct is to low. It is therefore preferable to use the volume flow actual value, usually of the supply air, as the control signal for the slave volume flow controller. Volume Flow Control of TVM Units The two controllers fitted to the dual duct unit TVM (cold, warm) must be wired by the customer as shown in the circuit diagram opposite (including the 24 VAC crossconnection). The room temperature controller provides the cold duct controller with its set point signal. In most cases, the proportion of warm air is increased from 0 to the required ‡ warm as a maximum set point. The warm duct controller (‡ total is measured) is therefore set as a constant value controller and does not require a control signal. For a more detailed functional description, refer to the TVM literature. Supply/Extract Air Slave Control with Dual Duct TVM The actual value output signal U5 of the warm duct controller is proportional to the total volume flow ‡ total. It can therefore be used as the control signal for a slave controller.
Function Test Fault Finding Check Check wiring Connect supply voltage Connect air supply system Pressure transducer zero point Measure actuator signal U 6 Record actual value signal U 5 for override control ‡ min Record actual value signal U 5 for override control ‡ max Supply voltage due to Belimo requirements? Signals U 5 and U 6 consistent? Actuator opening and closing? Volume flow ‡ min ? Volume flow ‡ max ? Volume flow control signal? Override controls? Check transformer etc. Controller faulty, replace Actuator rotation correct? Damper blocked? Duct pressure sufficient? Measurement tubes to transducer damaged? Protective wrapping removed? Check room temperature controller Check window switch, relay etc. Order Example Replacement Controller Belimo VRP, preset for TVZ 125, 60...140 l/s and VFP 300 Belimo VFP 300 10 Commissioning Belimo VRP A function test for commissioning can be carried out by measuring the actuator signal U 6 (terminal 6 to 1). If U 6 is between 5.8 and 6.2 VDC, the required volume flow is controlled. If U 6 deviates from this range, wait for the actuator to settle. If the commissioning procedure is to include verification of the set volume flows ‡ min and ‡ max, these must be set as described below. The actual value signal U 5 is measured in each operating situation (check U 6 first) and the volume flow is then calculated using the formulae given on page 4. NOTE Severe vibration during transport or caused by different installation conditions can necessitate subsequent zero point adjustment. The procedure is described in the product information for VFP. In many cases, incorrect wiring can be the cause of the faults. Therefore a careful check should be carried out to ensure that all connections are secure. Wires in terminals 3 to 7 should be disconnected and the actuator connection plug removed before the following checks are made. If the actuator drive is disengaged and the damper opened manually, the voltage U5 must increase and the voltage U6 deviate from 6 VDC. Connect the actuator plug, link terminals 1 and 7: The actuator must close. Change link to terminals 2 and 7: The actuator must open. Remove the link. The controller must control ‡ min. If U6 is approx. 6 volts, measure U5, calculate the volume flow and compare it with the design value. Link terminals 2 and 7: Repeat measurement for ‡ max, as above. Remove link. Apply the control signal U3 . Calculate the set volume flow and compare it with the actual volume flow. Apply the override control (terminal 7) and test the desired functions in sequence. Replacement Controller When replacing faulty controllers, calibrated controllers set for the terminal box type and size must be used. Uncalibrated controllers can only be used as a temporary solution. When ordering replacement controllers, specify ‡ min and ‡ max.
- Page 1 and 2: VARYCONTROL Reference List Design a
- Page 3 and 4: Reference list VARYCONTROL KADEWE-B
- Page 5 and 6: TVZ · TVA TVM TVR TVRK TVJ/TVT Des
- Page 7 and 8: Room Temperature Control Circuit Se
- Page 9 and 10: Single Duct System with Reheat Coil
- Page 11 and 12: Explanation of Order Codes The cont
- Page 13 and 14: Installation 1 Contents Subject Pag
- Page 15 and 16: Installation TVZ . TVA Delivery and
- Page 17 and 18: Installation TVJ with TX TVJ/TVT wi
- Page 19 and 20: Disengaging the Drive Function Test
- Page 21 and 22: TVRK Volume Flow Controller and Tra
- Page 23 and 24: Removing tubes Maintenance 1 Specia
- Page 25 and 26: VRD2 VRD2 Tube connection for trans
- Page 27 and 28: Pressure Independent Control Charac
- Page 29 and 30: Volume Flow Ranges TVZ, TVA, TVR, T
- Page 31 and 32: Volume Flow Ranges TVM Size V · mi
- Page 33 and 34: Override Controls RT Controller Ope
- Page 35 and 36: Function Test Fault Finding Check C
- Page 37 and 38: VRP � � � � Characteristic
- Page 39 and 40: VRP Adjustment Knobs � � �
- Page 41 and 42: Volume Flow Control Tolerances 1) V
- Page 43: Terminal Connections Plug connectio
- Page 47 and 48: VRP-STP Area of Application ��
- Page 49 and 50: Room Pressure Ranges Differential p
- Page 51 and 52: Parallel Differential Pressure Cont
- Page 53 and 54: Belimo VFP 1 Contents Subject Page
- Page 55 and 56: Belimo VFP Zero Point Adjustment
- Page 57 and 58: NM 24-V � Shaft clamp � Directi
- Page 59 and 60: Belimo VAV-Compact NMV-D2 1 Content
- Page 61 and 62: Belimo VAV-Compact NMV-D2 Character
- Page 63 and 64: Belimo VAV-Compact NMV-D2 Volume Fl
- Page 65 and 66: Belimo VAV-Compact NMV-D2 Volume Fl
- Page 67 and 68: Belimo VAV-Compact NMV-D2 Variable
- Page 69 and 70: Belimo VAV-Compact NMV-D2 Slave Con
- Page 71 and 72: Belimo VAV-Compact NMV-D2M 1 Conten
- Page 73 and 74: Belimo VAV-Compact NMV-D2M Characte
- Page 75 and 76: Belimo VAV-Compact NMV-D2M Volume F
- Page 77 and 78: Belimo VAV-Compact NMV-D2M Volume F
- Page 79 and 80: Belimo VAV-Compact NMV-D2M Variable
- Page 81 and 82: Belimo VAV-Compact NMV-D2M Slave Co
- Page 83 and 84: Belimo Adjuster ZEV 1 Contents Subj
- Page 85 and 86: Belimo Adjuster ZEV Condition: Para
- Page 87 and 88: PRVU Characteristic Curve of Actual
- Page 89 and 90: Service Unit ZS 1 Parameters of Vol
- Page 91 and 92: Volume Flow Control Deviations 1) V
- Page 93 and 94: Terminal Identification PRVU IMPORT
<strong>Belimo</strong> VRP<br />
Slave Control<br />
RT Controller<br />
Master Controller<br />
Operating Mode M, E<br />
Slave Controller<br />
Supply/Extract Air Slave Control<br />
for Dual Duct Unit TVM<br />
Operating Mode S<br />
RT Controller<br />
Cold Controller<br />
Warm Controller<br />
Operating Mode M, (E,F)<br />
Slave<br />
Controller<br />
Operating Mode S<br />
TVM<br />
9<br />
Supply/Extract Air Slave Control (Master/Slave)<br />
With parallel control of the units, an undesirable difference<br />
between supply and extract air can occur if the<br />
pressure in one duct is to low. It is therefore preferable to<br />
use the volume flow actual value, usually of the supply<br />
air, as the control signal for the slave volume flow controller.<br />
Volume Flow Control of TVM Units<br />
The two controllers fitted to the dual duct unit TVM (cold,<br />
warm) must be wired by the customer as shown in the<br />
circuit diagram opposite (including the 24 VAC crossconnection).<br />
The room temperature controller provides the cold duct<br />
controller with its set point signal.<br />
In most cases, the proportion of warm air is increased<br />
from 0 to the required ‡ warm as a maximum set point. The<br />
warm duct controller (‡ total is measured) is therefore set<br />
as a constant value controller and does not require a<br />
control signal.<br />
For a more detailed functional description, refer to the<br />
TVM literature.<br />
Supply/Extract Air Slave Control<br />
with Dual Duct TVM<br />
The actual value output signal U5 of the warm duct controller<br />
is proportional to the total volume flow ‡ total. It can<br />
therefore be used as the control signal for a slave controller.