Supply/Extract Air Slave Control<br />
for Dual Duct Unit TVM<br />
Commissioning Signal<br />
Adjuster ZEV Connections<br />
Room temperature<br />
controller<br />
Cold duct controller <strong>VRD2</strong><br />
Warm duct controller <strong>VRD2</strong><br />
Slave controller<br />
<strong>VRD2</strong> (NMV-D2)<br />
Operating mode S<br />
Room temperature<br />
controller<br />
Operating mode M, F<br />
Room Temperature<br />
controller, switch<br />
cabinet or step<br />
distributor<br />
11<br />
Volume Flow Control of TVM Units<br />
The two controllers fitted to the dual duct unit TVM (cold,<br />
warm) must be wired by the customer as shown in the<br />
circuit diagram opposite (including the 24 VAC/VDC<br />
cross-connection).<br />
The room temperature controller provides the cold duct<br />
controller with its set point signal.<br />
In most cases, the proportion of warm air is increased<br />
from 0 to the required V · warm as a maximum set point.<br />
The warm duct controller (V · total is measured) is therefore<br />
set as a constant value controller and does not require<br />
a control signal.<br />
For a more detailed functional description, refer to the<br />
TVM literature.<br />
Supply/Extract Air Slave Control with<br />
Dual Duct TVM<br />
The actual value output signal U5 of the warm duct controller<br />
is proportional to the total volume flow V · total. It<br />
can therefore be used as the control signal for a slave<br />
controller.<br />
Commissioning Connections<br />
It is advisable that the signal line for connecting the adjuster<br />
ZEV is linked up in an easily accessible location.<br />
This means that ceiling panels do not need be removed<br />
in order to take measurements.<br />
Suitable locations include: spare terminals in room temperature<br />
controller or wall mounted enclosure.<br />
It is important to ensure that the ground (and 24 V) is also<br />
available. Therefore, a 3-wire connection is required to<br />
the commissioning point connection.<br />
IMPORTANT<br />
The commissioning connection will also work if the U5 signal is used for slave circuits or monitoring. However,<br />
the U5 signal differs from the actual value when the ZEV<br />
unit is connected.<br />
ZEV Function<br />
The indicating lights come on when the control knob<br />
settings match the current values. To adjust the control<br />
mode, set the mode knob, for example to 0 - 10 VDC,<br />
and press the Set button. The volume settings can only<br />
be read.