Characteristic of Actual Value Signal Description of Function<br />

V · nom<br />

(100 %)<br />

Volume flow<br />

V · min pub.<br />

A 2 to 10 VDC (standard)<br />

V · actual = V · nom<br />

U 5 - 2<br />

8<br />

B 0 to 10 VDC<br />

V · actual = V · nom<br />

Adjustment<br />

range<br />

0<br />

0 2 Actual value signal U5 10 VDC<br />

U 5<br />

10<br />

Characteristic of Volume Flow Control Variable<br />

Volume flow<br />

V · max<br />

V · min<br />

A 2 to 10 VDC (standard)<br />

V · set = U3 - 2<br />

(V<br />

8<br />

· max -V · min) + V · min<br />

V · nom<br />

(100 %)<br />

V · min pub.<br />

0<br />

0 2 Control signal U3 10 VDC<br />

B 0 to 10 VDC<br />

V · set = U 3<br />

10<br />

(V · max -V · min) + V · min<br />

3<br />

The volume flow is measured on the dynamic differential<br />

pressure principle. The effective pressure ∆p w of the<br />

differential pressure sensor in the terminal unit allows the<br />

detection of a partial volume flow passing trough the<br />

transducer. This partial volume flow which is proportional<br />

to the total volume flow is measured, temperature compensated<br />

and linearised with two temperature-dependent<br />

resistors.<br />

The measurement range is set to suit the unit size during<br />

factory calibration, so that 10 VDC always corresponds<br />

to the unit nominal volume flow rate (V · nom).<br />

The signal is processed by a microprocessor. The actual<br />

volume flow is available as a linear voltage signal U 5.<br />

The required volume flow is set by the room temperature<br />

controller via the control signal within the limits of V · min<br />

and V · max.<br />

It is possible to select either 2 to 10 VDC (standard) or<br />

0 to 10 VDC as the voltage range for signal transmission.<br />

This facilitates an adjustment to the working ranges<br />

of different room temperature controllers or DDC outstations.<br />

The set volume flow can be overridden using<br />

switched controls.<br />

The <strong>VRD2</strong> determines the required volume flow in<br />

accordance with the characteristic shown and compares<br />

this with the actual value. The damper actuator is controlled<br />

according to the deviation.<br />

The <strong>Belimo</strong> volume flow controller <strong>VRD2</strong> can only operate<br />

with the matched <strong>Belimo</strong> actuators which are optimised<br />

for volume flow control. It is not possible to connect<br />

other 3-point or 0 to 10 VDC actuators.