Design and Areas of Application<br />

Room Pressure Control<br />

Extract<br />

air<br />

TVA<br />

TVR<br />

TVJ<br />

Order Example<br />

as per sales leaflet and price list:<br />

TVZ-R-1/160/B13/E2-25-250 l/s<br />

TVR/160/BG3/F2- -25 Pa, Extract Air<br />

Duct Pressure Control<br />

Order Example<br />

as per sales leaflet and price list:<br />

TVR/160/BH3/F2-110 Pa, Supply Air<br />

t<br />

TVZ<br />

TVS<br />

TVR<br />

TVJ<br />

Supply<br />

air<br />

7<br />

Room Pressure Control<br />

In sealed rooms, as a result of control deviations, with<br />

supply air/extract air slave control systems, unacceptably<br />

high room pressure differences can occur. It is therefore<br />

recommended that the room pressure be controlled. In<br />

the example shown, the room temperature is controlled<br />

via variable supply air (VAV). The room pressure is also<br />

controlled via the extract air. The room pressure controller<br />

acts directly on the actuator of the extract air<br />

damper. The membrane pressure transducer is connected<br />

to the room and a reference room (e.g. corridor) with<br />

measurement tubing. The specified maximum permitted<br />

tube length and installation position of the transducer<br />

must be observed. If an additional extract air volume flow<br />

controller is integrated, the extract air volume flow may<br />

be limited. This avoids extreme positions on the extract<br />

air damper (open or closed) when the doors are open or<br />

if there is any room leakage. This type of control is not<br />

possible with all controllers.<br />

The following combinations are possible:<br />

Supply air Extract air<br />

Constant/variable Room pressure<br />

positive or negative<br />

Room pressure Constant/variable<br />

positive or negative<br />

The proposed application and positive or negative pressure<br />

in Pa must be stated at the time of order.<br />

Duct Pressure Control<br />

All single duct VAV terminal units can have duct pressure<br />

control. A controller with a membrane pressure transducer<br />

acts directly on the damper actuator. The existing<br />

differential pressure sensor can also be fitted with a<br />

transducer to measure the actual volume flow for secondary<br />

control. The order should state the application of<br />

supply or extract air and the pressure to be calibrated in<br />

Pa. The reference pressure connection of the duct<br />

pressure transducer remains open. The duct pressure<br />

take-off is connected by the customer. The measurement<br />

point must be selected according to flow and system<br />

related criteria. The measurement connection must be<br />

mounted at right angles, without burrs, and connected<br />

via tubing to the plus (high) or minus (low) connection of<br />

the transducer. The notes in the controller descriptions<br />

on maximum tubing lengths, installation position must be<br />

observed.