Design and Areas of Application<br />
Room Pressure Control<br />
Extract<br />
air<br />
TVA<br />
TVR<br />
TVJ<br />
Order Example<br />
as per sales leaflet and price list:<br />
TVZ-R-1/160/B13/E2-25-250 l/s<br />
TVR/160/BG3/F2- -25 Pa, Extract Air<br />
Duct Pressure Control<br />
Order Example<br />
as per sales leaflet and price list:<br />
TVR/160/BH3/F2-110 Pa, Supply Air<br />
t<br />
TVZ<br />
TVS<br />
TVR<br />
TVJ<br />
Supply<br />
air<br />
7<br />
Room Pressure Control<br />
In sealed rooms, as a result of control deviations, with<br />
supply air/extract air slave control systems, unacceptably<br />
high room pressure differences can occur. It is therefore<br />
recommended that the room pressure be controlled. In<br />
the example shown, the room temperature is controlled<br />
via variable supply air (VAV). The room pressure is also<br />
controlled via the extract air. The room pressure controller<br />
acts directly on the actuator of the extract air<br />
damper. The membrane pressure transducer is connected<br />
to the room and a reference room (e.g. corridor) with<br />
measurement tubing. The specified maximum permitted<br />
tube length and installation position of the transducer<br />
must be observed. If an additional extract air volume flow<br />
controller is integrated, the extract air volume flow may<br />
be limited. This avoids extreme positions on the extract<br />
air damper (open or closed) when the doors are open or<br />
if there is any room leakage. This type of control is not<br />
possible with all controllers.<br />
The following combinations are possible:<br />
Supply air Extract air<br />
Constant/variable Room pressure<br />
positive or negative<br />
Room pressure Constant/variable<br />
positive or negative<br />
The proposed application and positive or negative pressure<br />
in Pa must be stated at the time of order.<br />
Duct Pressure Control<br />
All single duct VAV terminal units can have duct pressure<br />
control. A controller with a membrane pressure transducer<br />
acts directly on the damper actuator. The existing<br />
differential pressure sensor can also be fitted with a<br />
transducer to measure the actual volume flow for secondary<br />
control. The order should state the application of<br />
supply or extract air and the pressure to be calibrated in<br />
Pa. The reference pressure connection of the duct<br />
pressure transducer remains open. The duct pressure<br />
take-off is connected by the customer. The measurement<br />
point must be selected according to flow and system<br />
related criteria. The measurement connection must be<br />
mounted at right angles, without burrs, and connected<br />
via tubing to the plus (high) or minus (low) connection of<br />
the transducer. The notes in the controller descriptions<br />
on maximum tubing lengths, installation position must be<br />
observed.