2.4.2 AC Operated<br />
Part number 24H350-3501A<br />
The AC- DC power supply is in a stainless steel enclosure which is remotely mounted.<br />
Refer to Figure 2.5 for mounting dimensions.<br />
When one power supply is used to power two indicators then the combination cannot<br />
be used in a Zone 1 or a IIC gas group hazard.<br />
The AC to DC supply has a conduit fitting on the bottom where the power cable is<br />
attached to the unit. This fitting is 1" in diameter and has a 1/2" thread. Ensure that the<br />
conduit is correctly connected using suitable ATEX approved conduit fittings and seals.<br />
The AC power supply cable must be mechanically protected in conduit when the AC<br />
Power Supply is installed in the hazardous area.<br />
Figure 2.5 AC to DC Power Supply Outline Drawing<br />
2.4.3 AC To DC Power Supply Extension Cable<br />
The extension cable comes in either 25' or 50' length. This cable is used for mounting<br />
the AC to DC converter away from the indicator. Fifty feet is the maximum allowed from<br />
power supply to indicator.<br />
14<br />
Model 350 I.S. and Model <strong>355</strong> I.S. <strong>User</strong> Instructions