BID Document for Guest House with Boundary Wall.pdf - Integrated ...
BID Document for Guest House with Boundary Wall.pdf - Integrated ... BID Document for Guest House with Boundary Wall.pdf - Integrated ...
The water cement ratio is to be determined by proper slump test or as per provision of relevant I.S. In case of slump test the slump cones 30 cm. high 20 cm. dia. at bottom and 10 cm. at top are to be kept at site at the cost of the contractor. 8.3 Finishing: If the surface of the concrete is found uneven or spongy in the appearance, the contractor will have to rectify or reconstruct at his own cost. All R.C.C. work in wall, column, beam, roof, foundation etc., not forming part of water retaining structure shall be done in M20 grade concrete as per I.S.: 456 with cement content not less than 300 Kg/cu.m. of concrete. Plasticizer @ 0.2% by weight of cement shall be used. The water cement ratio should not exceed 0.45. All R.C.C. work forming part of water retaining structure shall be done in M25 grade of concrete as per IS: 456 ;with cement content not less than 350 Kg/cu.m. of concrete. Plasticizer @ 0.2% by weight of cement shall be used. The water cement ratio should not exceed 0.50.The concrete shall be cured as per I.S.: 456 8.4 Cement and Aggregate: 8.4.1 Cement: The cement shall be OPC, Slag or Pozolana conform to relevant I.S. grade not less 43. Selection of type and grade of cement shall be approved by the EIC. Cement tests shall have to be carried out at contractor’s expenses as and when directed. The contractor shall make arrangement with necessary equipment to carry out crushing strength of 150 cm. Cube concrete block for 7 day’s & 28 day’s of proper curing. Testing procedure, sample size shall be in accordance with relevant I.S. 8.4.2 Aggregate: The fine and course aggregates shall conform to relevant I.S. Stone chips and sand for construction work shall have to be supplied as per clause 3.0 of this specification. Concrete shall be sampled, analysed tested in accordance with I.S. as furnished in the list. 8.5 Joints in Concrete Structure: Type of joints, spacing of joints, use of all jointing materials and other features pertaining to the provision of movement joints in liquid-retaining structures shall be as per relevant I.S. Codes. 8.6 Reinforcement of R.C.C. Works: The M.S. work should include cutting to sizes, bending, hooking and fabricating including the supply of B.W.G. wire, and all other works according to specification, drawing or otherwise. The M.S. reinforcement rods if to be procured by the tenderer shall be HYSD bars (Fe-415) as per relevant IS Code. The contractor shall intimate the department regarding the quantity of steel to be procured by him in the works and the same may be supplied at the agreed rate specified in General terms and conditions. 8.7 Clear Cover: The clear cover to reinforcement shall be maintained as per IS-456-2000 based on the actual exposure conditions which shall not be less than the followings unless otherwise specified in drawing. a) Water retaining face 30 mm b) Other than water retaining face 25 mm for beam and 15 mm for roof and floor c) Column, Pedestal Foundation and Pile 50 mm 8.8 Lap Length: The Lap length of reinforcement shall be provided as given below; unless otherwise specified in drawing. Compression members like column, struts @ 40 times the dia of bar. Tension members like beam, slab, wall etc @ 50 times the dia of bar. Following Development length/Anchorage length shall be provided. 74
8.9 Bar Bending Schedule: Concrete Grade M 15 M 20 M 25 Development Length 68 D 51 D 46 D Anchorage As per I.S. – 456-2000 The reinforcement work will include cutting to sizes, bending, hooking binding with 14 to 18 S.W.G. soft pliable wire etc. as per P.W.D. schedule. The work shall also be inclusive of stirrups, distributors, binders etc. The contractor shall prepare his “Bar Bending Schedule” for the entire construction work in phases before starting the work and shall submit it to the EIC for his approval. Cutting of M.S. rods in an unplanned way will not be allowed and for that if any material is found to be wasted or have to be used in excess due to the fault of the contractor , no payment shall be made on this score and the cost of such excess material shall be realised from the contractor’s bill at penal rate as specified elsewhere of this tender document The item of M.S work should include the cost of reinforcement, cutting to sizes, bending and fabricating including the supply of R.W.G wire, bolts and nuts etc. and all other work according to specifications, drawing or otherwise. Cut pieces of steel materials less than 1 mtr cannot be used as a main bar. 8.10 Form Work The form work shall conform to relevant I.S. Code of practice Shuttering in form work shall be either made of steel or ply board. Surface of shuttering in contact with concrete shall be made smooth & at joints rendered smooth. In every case the joints of the shuttering are to be such as to prevent the loss of liquid from the concrete. All shuttering form work must be adequately stayed and braced to the satisfaction of the Engineerin-charge for properly supporting the concrete during the period of hardening. All form works shall be removed without shock or vibration. Before the form work is stripped, concrete surface shall be exposed when necessary in order to ascertain that the concrete has set and hardened sufficiently. 8.11 Staging & scaffolding: Whenever necessary staging and scaffolding must be provided .All shuttering and framing must adequately be stayed and braced to the satisfaction of the Engineer-in-charge for properly supporting the concrete during the period of hardening. It shall be so constructed that it may withstand the jerk and shock of vibration of concrete. Scaffolding must be strong and rigid stiffened with necessary cross bracings and proper deck at every stage where casting work is in progress to prevent any injuries to persons and to facilitate inspection, supervision and taking measurement at any time. The hire and labour charges for staging, scaffolding, platform etc. as provided in the schedule of works is for the entire construction work including shell wall of reservoir etc till completion of work and removing the same as per direction and instruction of EIC. 8.12 Curing and Finishing: The joint shall be cleaned off the gray cement slurry with wire/coir brush or trowel to a depth of 2 mm to 3 mm and all dust and loose mortar removed. Joints shall then be flush pointed with white cement . The floor shall then be kept wet for 7 days. After curing the surface shall be washed and finished clean. The finished floor and wall shall not sound hollow when tapped with a wooden mallet. 8.13 Verticality of structure: The vertical members should be perfectly vertical and no deviation in x – axis and /or y- axis is admissible. The Contractor should take adequate precautionary measures to ensure that the structure is constructed true to plumb. Similarly all horizontal members of the structures should be truly horizontal. 9.0 TESTING OF CONCRETE: 75
- Page 23 and 24: Qualification Information The infor
- Page 25 and 26: 1.6 Qualifications and experience o
- Page 27 and 28: Integrated Coastal Zone Management
- Page 29 and 30: 2 To be used only if the Contractor
- Page 31 and 32: Agreement Form Agreement This agree
- Page 33 and 34: SECTION 3: CONDITIONS OF CONTRACT 3
- Page 35 and 36: Conditions of Contract A. General 1
- Page 37 and 38: (5) Conditions of Contract includin
- Page 39 and 40: 16. Contractor to Construct the Wor
- Page 41 and 42: 28.1 The Engineer-in-charge shall e
- Page 43 and 44: timing of the work in the Variation
- Page 45 and 46: 47. Price Adjustment 47.1 Contract
- Page 47 and 48: the Engineer-in-charge shall issue
- Page 49 and 50: (i) (ii) (iii) (iv) (v) “corrupt
- Page 51 and 52: d) Maternity Benefit Act 1951: The
- Page 53 and 54: 3. Assignment of the contract may b
- Page 55 and 56: S. No. Activity 3. Consultation and
- Page 57 and 58: S. No. Activity Measures to be Impl
- Page 59 and 60: Contract Data Items marked "N/A" do
- Page 61 and 62: (iv) Personal injury or death insur
- Page 63 and 64: The advance shall be repaid from ea
- Page 65 and 66: GENERAL SPECIFICATIONS 1.0 SCOPE OF
- Page 67 and 68: S. No. IS No. DESCRIPTION 1 IS-1200
- Page 69 and 70: 82 IS:2963 83 IS:3004 84 IS:3311 Wa
- Page 71 and 72: Bricks shall be of first class qual
- Page 73: e moved around the top edge of the
- Page 77 and 78: 9.3 Protections And Curing The cont
- Page 79 and 80: DETAILED TECHNICAL SPECIFICATION FO
- Page 81 and 82: 6.0 SHORING WORKS 6.1 General: Shor
- Page 83 and 84: When testing a pipeline hydraulical
- Page 85 and 86: (i) (ii) (iii) procurement & supply
- Page 87 and 88: the worst weather and flooding cond
- Page 89 and 90: All valves shall be provided with c
- Page 91 and 92: SECTION 6: Layout Drawings of the w
- Page 93 and 94: SCHEDULE OF QUANTITIES FOR GUEST HO
- Page 95 and 96: 2 Brick work with 1st class bricks
- Page 97 and 98: smooth finish acrylic exterior emul
- Page 99 and 100: complete.(Payment to be made on bas
- Page 101 and 102: approved brand (size not less than
- Page 103 and 104: and including smoothening surface b
- Page 105 and 106: 8.1 5/6 amps switch Each 30 8.2 15/
- Page 107 and 108: sets of G.I. nut bolt & spring wash
- Page 109 and 110: power unit having suitable rating S
- Page 111 and 112: as required. 19.0 Installation of e
- Page 113 and 114: 40.2 63 Amp DP Each 1 41.0 Providin
- Page 115 and 116: (i) 590 mm X 390 mm X 380 mm 9 Supp
- Page 117 and 118: clamps 750 mm long 4 Installation o
- Page 119 and 120: all specials . No separate payment
- Page 121 and 122: stacking the spills within a lead o
- Page 123 and 124: cc manhole cover of approved make s
The water cement ratio is to be determined by proper slump test or as per provision of relevant I.S. In case of<br />
slump test the slump cones 30 cm. high 20 cm. dia. at bottom and 10 cm. at top are to be kept at site at the<br />
cost of the contractor.<br />
8.3 Finishing:<br />
If the surface of the concrete is found uneven or spongy in the appearance, the contractor will have to rectify<br />
or reconstruct at his own cost.<br />
All R.C.C. work in wall, column, beam, roof, foundation etc., not <strong>for</strong>ming part of water retaining structure<br />
shall be done in M20 grade concrete as per I.S.: 456 <strong>with</strong> cement content not less than 300 Kg/cu.m. of<br />
concrete. Plasticizer @ 0.2% by weight of cement shall be used. The water cement ratio should not exceed<br />
0.45.<br />
All R.C.C. work <strong>for</strong>ming part of water retaining structure shall be done in M25 grade of concrete as per IS:<br />
456 ;<strong>with</strong> cement content not less than 350 Kg/cu.m. of concrete. Plasticizer @ 0.2% by weight of cement<br />
shall be used. The water cement ratio should not exceed 0.50.The concrete shall be cured as per I.S.: 456<br />
8.4 Cement and Aggregate:<br />
8.4.1 Cement: The cement shall be OPC, Slag or Pozolana con<strong>for</strong>m to relevant I.S. grade not less 43. Selection of<br />
type and grade of cement shall be approved by the EIC. Cement tests shall have to be carried out at<br />
contractor’s expenses as and when directed. The contractor shall make arrangement <strong>with</strong> necessary equipment<br />
to carry out crushing strength of 150 cm. Cube concrete block <strong>for</strong> 7 day’s & 28 day’s of proper curing.<br />
Testing procedure, sample size shall be in accordance <strong>with</strong> relevant I.S.<br />
8.4.2 Aggregate:<br />
The fine and course aggregates shall con<strong>for</strong>m to relevant I.S. Stone chips and sand <strong>for</strong> construction work shall<br />
have to be supplied as per clause 3.0 of this specification.<br />
Concrete shall be sampled, analysed tested in accordance <strong>with</strong> I.S. as furnished in the list.<br />
8.5 Joints in Concrete Structure:<br />
Type of joints, spacing of joints, use of all jointing materials and other features pertaining to the provision of<br />
movement joints in liquid-retaining structures shall be as per relevant I.S. Codes.<br />
8.6 Rein<strong>for</strong>cement of R.C.C. Works:<br />
The M.S. work should include cutting to sizes, bending, hooking and fabricating including the supply of<br />
B.W.G. wire, and all other works according to specification, drawing or otherwise.<br />
The M.S. rein<strong>for</strong>cement rods if to be procured by the tenderer shall be HYSD bars (Fe-415) as per relevant IS<br />
Code. The contractor shall intimate the department regarding the quantity of steel to be procured by him in the<br />
works and the same may be supplied at the agreed rate specified in General terms and conditions.<br />
8.7 Clear Cover:<br />
The clear cover to rein<strong>for</strong>cement shall be maintained as per IS-456-2000 based on the actual exposure<br />
conditions which shall not be less than the followings unless otherwise specified in drawing.<br />
a) Water retaining face 30 mm<br />
b) Other than water retaining face 25 mm <strong>for</strong> beam and 15 mm <strong>for</strong> roof and floor<br />
c) Column, Pedestal Foundation and Pile 50 mm<br />
8.8 Lap Length:<br />
The Lap length of rein<strong>for</strong>cement shall be provided as given below; unless otherwise specified in drawing.<br />
Compression members like column, struts @ 40 times the dia of bar. Tension members like beam, slab,<br />
wall etc @ 50 times the dia of bar.<br />
Following Development length/Anchorage length shall be provided.<br />
74