7.4 150 mm X 150 mm X 60 mm deep Each 7 7.5 200 mm X 125 mm X 60 mm deep Each 2 7.6 250 mm X 200 mm X 60 mm deep Each 4 7.7 300 mm X 250 mm X 60 mm deep Each 1 8.0 Supplying and fixing following piano type switch / socket on the existing switch box / cover including connections etc. as required. 8.1 5/6 amps switch Each 33 8.2 15/16 amp switch Each 9 8.3 3 pin 5/6 amp socket outlet Each 33 8.4 6 pin 15/16 amp socket outlet Each 9 8.5 Telephone socket outlet Each 8 8.6 TV antenna socket outlet Each 5 8.7 Bell push Each 5 9.0 Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. Each 17 10.0 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box / wooden block including connection etc. as required. Each 41 11.0 Supplying and fixing brass batten / angle holder including connection etc. as required. Each 16 12.0 Erection of wall bracket / ceiling fittings of all sizes and shapes containing upto two CFL / GLS lamps per fitting, complete with all accessories including connection etc. as required. Each 39 13.0 Supplying and fixing call bell / buzzer suitable for single phase, 230 volts, complete as required. Each 5 14.0 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required. Each 34 15.0 Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable etc. as required. Each 17 16.0 Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) Each 20 17.0 Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) Each 17 18.0 Numbering of ceiling fan / exhaust fan / fluorescent fittings Each 103 110
as required. 19.0 Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep Each 7 20.0 Extra for fixing the louvers / shutters complete with frame for a exhaust fan of all sizes. Each 7 21.0 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 21.1 32 Amp TP&N Each 1 21.2 63 Amp TP&N Each 1 22.0 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator) 22.1 2 + 4 way, Double door Each 1 22.2 2 + 6 way, Double door Each 2 22.3 2 + 8 way, Double door Each 2 22.4 2 + 12 way, Double door Each 1 23.0 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator) 4 way (4 + 12), Double door Each 1 24.0 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 24.1 Single pole Each 36 24.2 Double pole Each 4 24.3 Triple pole Each 1 24.4 Triple pole & neutral Each 1 25.0 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. Each 1 26.0 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Each 1 27.0 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal / coke and salt as required. Each 1 28.0 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection / termination with GI thimble etc. as required. Metre 5 111
- Page 59 and 60: Contract Data Items marked "N/A" do
- Page 61 and 62: (iv) Personal injury or death insur
- Page 63 and 64: The advance shall be repaid from ea
- Page 65 and 66: GENERAL SPECIFICATIONS 1.0 SCOPE OF
- Page 67 and 68: S. No. IS No. DESCRIPTION 1 IS-1200
- Page 69 and 70: 82 IS:2963 83 IS:3004 84 IS:3311 Wa
- Page 71 and 72: Bricks shall be of first class qual
- Page 73 and 74: e moved around the top edge of the
- Page 75 and 76: 8.9 Bar Bending Schedule: Concrete
- Page 77 and 78: 9.3 Protections And Curing The cont
- Page 79 and 80: DETAILED TECHNICAL SPECIFICATION FO
- Page 81 and 82: 6.0 SHORING WORKS 6.1 General: Shor
- Page 83 and 84: When testing a pipeline hydraulical
- Page 85 and 86: (i) (ii) (iii) procurement & supply
- Page 87 and 88: the worst weather and flooding cond
- Page 89 and 90: All valves shall be provided with c
- Page 91 and 92: SECTION 6: Layout Drawings of the w
- Page 93 and 94: SCHEDULE OF QUANTITIES FOR GUEST HO
- Page 95 and 96: 2 Brick work with 1st class bricks
- Page 97 and 98: smooth finish acrylic exterior emul
- Page 99 and 100: complete.(Payment to be made on bas
- Page 101 and 102: approved brand (size not less than
- Page 103 and 104: and including smoothening surface b
- Page 105 and 106: 8.1 5/6 amps switch Each 30 8.2 15/
- Page 107 and 108: sets of G.I. nut bolt & spring wash
- Page 109: power unit having suitable rating S
- Page 113 and 114: 40.2 63 Amp DP Each 1 41.0 Providin
- Page 115 and 116: (i) 590 mm X 390 mm X 380 mm 9 Supp
- Page 117 and 118: clamps 750 mm long 4 Installation o
- Page 119 and 120: all specials . No separate payment
- Page 121 and 122: stacking the spills within a lead o
- Page 123 and 124: cc manhole cover of approved make s
- Page 125 and 126: acing for concrete slabs , beams, a
- Page 127 and 128: 4.0 Laying and fixing of one number
- Page 129 and 130: The rate shall be inclusive of supp
- Page 131 and 132: Note: (1) Item for which no rate or
- Page 133 and 134: Forms of Securities Acceptable form
- Page 135 and 136: PERFORMANCE BANK GUARANTEE To: ____
- Page 137: BANK GUARANTEE FOR ADVANCE PAYMENT
7.4 150 mm X 150 mm X 60 mm deep Each 7<br />
7.5 200 mm X 125 mm X 60 mm deep Each 2<br />
7.6 250 mm X 200 mm X 60 mm deep Each 4<br />
7.7 300 mm X 250 mm X 60 mm deep Each 1<br />
8.0 Supplying and fixing following piano type switch / socket<br />
on the existing switch box / cover including connections etc.<br />
as required.<br />
8.1 5/6 amps switch Each 33<br />
8.2 15/16 amp switch Each 9<br />
8.3 3 pin 5/6 amp socket outlet Each 33<br />
8.4 6 pin 15/16 amp socket outlet Each 9<br />
8.5 Telephone socket outlet Each 8<br />
8.6 TV antenna socket outlet Each 5<br />
8.7 Bell push Each 5<br />
9.0 Supplying and fixing stepped type electronic fan regulator<br />
on the existing modular plate switch box including<br />
connections but excluding modular plate etc. as required.<br />
Each 17<br />
10.0 Supplying and fixing 3 pin, 5 amp ceiling rose on the<br />
existing junction box / wooden block including connection<br />
etc. as required.<br />
Each 41<br />
11.0 Supplying and fixing brass batten / angle holder including<br />
connection etc. as required.<br />
Each 16<br />
12.0 Erection of wall bracket / ceiling fittings of all sizes and<br />
shapes containing upto two CFL / GLS lamps per fitting,<br />
complete <strong>with</strong> all accessories including connection etc. as<br />
required.<br />
Each 39<br />
13.0 Supplying and fixing call bell / buzzer suitable <strong>for</strong> single<br />
phase, 230 volts, complete as required.<br />
Each 5<br />
14.0 Installation, testing and commissioning of pre-wired,<br />
fluorescent fitting / compact fluorescent fitting of all types,<br />
<strong>with</strong> all accessories and tube etc. directly on ceiling/ wall,<br />
including connection <strong>with</strong> 1.5 sq. mm FR PVC insulated,<br />
copper conductor, single core cable and earthing etc. as<br />
required.<br />
Each 34<br />
15.0 Installation, testing and commissioning of ceiling fan,<br />
including wiring the down rods of standard length (upto 30<br />
cm) <strong>with</strong> 1.5 sq. mm FR PVC insulated, copper conductor,<br />
single core cable etc. as required.<br />
Each 17<br />
16.0 Supplying and fixing extra down rod of 10 cm length G.I.<br />
pipe, 15 mm dia, heavy gauge including painting etc. as<br />
required. (Note : More than 5 cm length shall be rounded to<br />
the nearest 10 cm and 5 cm or less shall be ignored)<br />
Each 20<br />
17.0 Supplying and fixing extra conduit down rod of 20 cm<br />
length G.I. pipe 15 mm dia, heavy gauge including painting<br />
etc. as required. (Note : More than 5 cm length shall be<br />
rounded to the nearest 10 cm and 5 cm or less shall be<br />
ignored)<br />
Each 17<br />
18.0 Numbering of ceiling fan / exhaust fan / fluorescent fittings Each 103<br />
110