SeaMach Reverse Cycle <strong>Air</strong> Conditioners<br />

Instructions for the Manual Thermostat for use with SeaMach models <strong>SP</strong>M or<br />

<strong>SC</strong>M.<br />

Cooling Cycle<br />

1. Set the compressor time delay to 3 minutes<br />

2. Adjust the cooling temperature set point on the thermostat higher than the cabin temperature.<br />

3. Slowly lower the thermostat’s cooling set point until the set point is below the cabin temperature.<br />

The blower, compressor and pump should be operating.<br />

4. Close all doors and hatches.<br />

5. Allow the unit to operate 10 minutes.<br />

6. After 10 minutes, there should be a 15°F (8°C) to 20°F (11°C) difference in the supply and return air<br />

temperatures.<br />

Heating Cycle<br />

Note: Do not turn unit “OFF” and then immediately back “ON”. Wait three minutes to<br />

allow refrigerant pressures to equalize.<br />

1. Adjust the heating temperature set point on the display module or the thermostat higher than the<br />

cabin’s temperature.<br />

2. Slowly raise the thermostat’s heating set point until the set point is above the cabin temperature. The<br />

blower, compressor and pump should be operating.<br />

3. Close all doors and hatches.<br />

4. Allow the unit to operate 5 minutes.<br />

5. After 5 minutes there should be a 15°F (8°C) to 25°F (11°C) difference in the supply and return air<br />

temperature.<br />

SeaMach Owner’s Manual 5/05 Page 13 of 24