MIAMI-DADE FIRE RESCUE DEPARTMENT - INSPECTION REPORT<br />
FIRE PREVENTION DIVISION<br />
9300 NW 41 STREET, MIAMI, FLORIDA 33178<br />
PHONE 786.331.4800 FAX 786.331.4801<br />
PERMIT # 00121-00204<br />
Permit Type: Education Inspection Month: October<br />
Billing Address:<br />
DCPS CORAL REEF SENIOR HIGH SCHOOL<br />
1450 NE 2ND AVE RM 602 MIAMI, FL 33132<br />
Inspection Date: 09/20/2012<br />
Inspector: JOSE GARCIA<br />
Inspector phone: (786) 336-6814<br />
Results: Inspected / N.O.V. (30)<br />
DCPS CORAL REEF SENIOR HIGH SCHOOL<br />
10101 SW 152 ST<br />
MIAMI, FL 33157<br />
NOTICE OF VIOLATIONS AND ORDER TO CORRECT<br />
The hazards noted are in violation of the Florida Fire Prevention Code and/or Miami-Dade County Code. Nothing in this <strong>report</strong> supersedes any<br />
previously written, still existing violations for this occupancy. You are ordered to comply with the corrective measures within the time<br />
prescribed.<br />
Please Note: A life safety permit required by County Code# 14-53 to operate within Miami-Dade County will be issued upon correction of all outstanding<br />
violations and payment of fees assessed. Failure to obtain the required Life Safety Permit will result in Enforcement Actions including fines,<br />
citations, liens and/or orders to cease and desist operation.<br />
APPEALS<br />
In accordance with the Code of Metropolitan Dade County part III, chapter 8CC-5; A violator who has been served with a civil violation notice may request<br />
an administrative hearing before a Hearing Officer to appeal the decision of the Code Inspector which resulted in the issuance of the civil violation notice.<br />
The request for appeal must be submitted in writing no later than twenty (20) calendar days after the service of the notice. Failure of the named violator<br />
to appeal the decision of the Code Inspector within the prescribed time period shall constitute a waiver of the violator's right to administrative hearing<br />
before the Hearing Officer. A waiver of the right to administrative hearing shall be treated as an admission of the violation and penalties may be assessed<br />
accordingly.<br />
Viol.<br />
Inspection<br />
Date<br />
Comply<br />
by<br />
Date<br />
VIOLATION, CORRECTION & COMMENTS<br />
1 8/25/12 7/19/12<br />
Violation: Code of Miami-Dade County 14-53(F) All applications for permits pursuant to this<br />
section shall be on a form prescribed by the Fire Department having jurisdiction and accompanied<br />
by the required fee. The fees shall be established by administrative order of the County Manager<br />
and approved by the Board of County Commissioners for permits within the jurisdiction of the<br />
Metropolitan Dade County Fire Department. The fees shall be established by the governing body of<br />
the City of Miami Beach, the City of Miami, the City of Hialeah and the City of <strong>Coral</strong> Gables for such<br />
permits within the respective jurisdictions of the aforesaid municipalities.<br />
Correction: Call 786-331-4800. Request the total amount of fees owed for the Life Safety Permit.<br />
Arrange payment of all fees owed.<br />
Comments:<br />
2 8/25/12 7/19/12<br />
Violation: NFPA 1 13.3.3.5.3.5* Sprinklers shall not be altered in any respect or have any type of<br />
ornamentation, paint, or coatings applied after shipment from the place of manufacture. [25:5.4.1.8]<br />
Correction: Maintain <strong>fire</strong> sprinkler free of alteration from the manufacture specs.<br />
Comments:<br />
3 8/25/12 7/19/12<br />
Violation: NFPA 1 13.3.3.3 Ceiling Tiles and Ceiling Assemblies. Where automatic sprinklers are<br />
installed, ceilings necessary for the proper actuation of the <strong>fire</strong> protection device in accordance with<br />
NFPA 13 shall be maintained.<br />
Correction: Maintain ceilings necessary for proper actuation of <strong>fire</strong> protection device in accordance<br />
with NFPA 13.<br />
Comments:<br />
Printed:<br />
9/20/12<br />
Please Note: A life safety permit will be issued upon compliance of outstanding violations and payment of fees assesed. One (1)<br />
re-<strong>inspection</strong> will be performed at no additional cost. All subsequent re-<strong>inspection</strong>s will be billed at one-half the original permit fee amount.<br />
Customer sign off: Contact A. MEJIA<br />
Page 1 of 5
4 8/25/12 7/19/12<br />
INSPECTION REPORT PERMIT # 00121-00204 Page 2 of 5<br />
Violation: NFPA 1 13.6.8.1.3.1 Fire extinguishers shall be conspicuously located where they are<br />
readily accessible and immediately available in the event of <strong>fire</strong>. [10:6.1.3.1]<br />
Correction: Locate <strong>fire</strong> extinguishers where they are readily accessible and immediately available in<br />
the event of <strong>fire</strong>.<br />
Comments:<br />
5 8/25/12 7/19/12<br />
Violation: NFPA 1 11.1.10 Covers. All panel board and switch boards, pull boxes,<br />
junction boxes, switches, receptacles,and conduit bodies shall<br />
be provided with covers compatible with the box or conduit<br />
body construction and suitable for the conditions of use.<br />
Correction: Provide proper covers in accordance with 11.1.10.<br />
Comments:<br />
6 8/25/12 7/19/12<br />
Violation: NFPA 1 10.19.5.1 Combustible material shall not be stored in boiler rooms,<br />
mechanical rooms, or electrical equipment rooms.<br />
Correction: Do not store combustible material in boiler rooms, mechanical rooms, or electrical<br />
equipment rooms.<br />
Comments:<br />
7 8/25/12 7/19/12<br />
Violation: NFPA 1 10.19.3.2* The clearance between the deflector and the top of storage shall<br />
be 18 in. (457 mm) or greater. [13:8.6.6.1]<br />
Correction: Maintain a minimum of 18 inch clearance between storage and the sprinkler deflector.<br />
Comments:<br />
8 8/25/12 7/19/12<br />
Violation: NFPA 101 7.10.5.1* General. Every sign required by 7.10.1.2, 7.10.1.5, or 7.10.8.1,<br />
other than where operations or processes require low lighting levels, shall be suitably illuminated by<br />
a reliable light source. Externally and internally illuminated signs shall be legible in both the normal<br />
and emergency lighting mode.<br />
Correction: Provide continuous illumination of exit signs other than where operations or processes<br />
require low lighting levels, shall be suitably illuminated by a reliable light source. Externally and<br />
internally illuminated signs shall be legible in both the normal and emergency lighting mode..<br />
Comments:<br />
9 8/25/12 7/19/12<br />
Violation: NFPA 1 14.4.4 There shall be no storage above any component of the means of egress<br />
unless it is on a separate floor or mezzanine constructed in accordance with the Florida Building<br />
Code.<br />
Correction: Remove all storage above any component of the means of egress<br />
Comments:<br />
10 8/25/12 7/19/12<br />
Violation: NFPA 1 11.1.7.5 Extension cords and flexible cords shall not be affixed to structures;<br />
extend through walls, ceilings, or floors, or under doors or floor coverings; or be subject to<br />
environmental or physical damage.<br />
Correction: Cease use of extension cords affixed to structures extend through walls, ceilings, or<br />
floors, or under doors or floor coverings; or be subject to environmental or physical damage.<br />
Comments:<br />
Printed:<br />
9/20/12<br />
Please Note: A life safety permit will be issued upon compliance of outstanding violations and payment of fees assesed. One (1)<br />
re-<strong>inspection</strong> will be performed at no additional cost. All subsequent re-<strong>inspection</strong>s will be billed at one-half the original permit fee amount.<br />
Customer sign off: Contact A. MEJIA<br />
Page 2 of 5
11 8/25/12 7/19/12<br />
INSPECTION REPORT PERMIT # 00121-00204 Page 3 of 5<br />
Violation: NFPA 101 7.2.1.5.2 Locks, if provided, shall not require the use of a key, a tool, or<br />
special knowledge or effort for operation from the egress side.<br />
Correction: Provide locks that do not require the use of a key, a tool, or special knowledge or effort<br />
for operation from the egress side.<br />
Comments:<br />
12 8/25/12 7/19/12<br />
Violation: NFPA 1 13.7.4.4.1 The <strong>inspection</strong>, testing, and maintenance for <strong>fire</strong> alarm<br />
and <strong>fire</strong> detection systems shall be in accordance with Chapter 10<br />
of NFPA 72.<br />
Correction: Perform required testing.<br />
Comments:<br />
13 8/25/12 7/19/12<br />
Violation: Code of Miami-Dade County (a) The service contract shall include a provision for<br />
runner service available to respond to the protected premises at any and all times within two (2)<br />
hours of notification of the runner service of any alarm or supervisory signal, and within four (4)<br />
hours of notification of any trouble signal. Existing <strong>fire</strong> alarm systems shall comply with Section<br />
14-66 (4) of this Code not later than five hundred forty-five (545) days after the effective date of this<br />
ordinance. The authority having jurisdiction shall have the authority to extend the time for<br />
compliance with Section 14-66 (4) of this Code for existing <strong>fire</strong> alarm systems to not later than one<br />
thousand ninety-five (1,095) days after the effective date of this ordinance if the authority having<br />
jurisdiction determines that compliance within five hundred forty-five (545) days is not reasonable<br />
under all the facts and circumstances.<br />
Correction: Enter into a contract with a <strong>fire</strong> alarm contractor for both the service of the <strong>fire</strong> alarm<br />
system and for runner service for any alarm, supervisory signal, or trouble signal. Service must<br />
include all tests, <strong>inspection</strong>s, and repairs required by NFPA 72. Runner must be at the premises and<br />
initiate corrective action within 2 hours of an alarm or supervisory signal and within 4 hours of a<br />
trouble signal. Provide a copy of the contract for review by the <strong>fire</strong> inspector.<br />
Comments:<br />
Printed:<br />
9/20/12<br />
Please Note: A life safety permit will be issued upon compliance of outstanding violations and payment of fees assesed. One (1)<br />
re-<strong>inspection</strong> will be performed at no additional cost. All subsequent re-<strong>inspection</strong>s will be billed at one-half the original permit fee amount.<br />
Customer sign off: Contact A. MEJIA<br />
Page 3 of 5
14 8/25/12 7/19/12<br />
INSPECTION REPORT PERMIT # 00121-00204 Page 4 of 5<br />
Violation: NFPA 101 7.1.3.2.1 Where this Code requires an exit to be separated from other<br />
parts of the building, the separating construction shall meet the requirements of Section 8.2 and the<br />
following: 1) The separation shall have a minimum 1-hour <strong>fire</strong> resistance rating where the exit<br />
connects three or fewer stories. 2) The separation shall have a minimum 2-hour <strong>fire</strong> resistance<br />
rating where the exit connects four or more stories, unless one of the following conditions exists: a)<br />
In existing non-high-rise buildings, existing exit stair enclosures shall have a minimum 1-hour <strong>fire</strong><br />
resistance rating. b) In existing buildings protected throughout by an approved, supervised<br />
automatic sprinkler system in accordance with Section 9.7, existing exit stair enclosures shall have<br />
a minimum 1-hour <strong>fire</strong> resistance rating. c) the minimum One-hour enclosures in accordance with<br />
28.2.2.1.2, 29.2.2.1.2, 30.2.2.1.2, and 31.2.2.1.2 shall be permitted as an alternative to the<br />
requirement of 7.1.3.2.1(2). 3) Reserved. (4) The minimum 2-hour <strong>fire</strong> resistance rated separation<br />
required<br />
by 7.1.3.2.1(2) shall be constructed of an assembly of<br />
noncombustible or limited-combustible materials and shall be<br />
supported by construction having a minimum 2-hour <strong>fire</strong><br />
resistance rating, unless otherwise permitted by 7.1.3.2.1(6).<br />
(5)* Structural elements, or portions thereof, that support exit<br />
components and either penetrate into a <strong>fire</strong> resistance rated<br />
assembly or are installed within a <strong>fire</strong> resistance rated wall<br />
assembly shall be protected, as a minimum to the <strong>fire</strong> resistance<br />
rating required by 7.1.3.2.1(1) or (2).<br />
(6) In Type III, Type IV, and Type V construction, as defined in<br />
NFPA 220, Standard on Types of Building Construction(see<br />
8.2.1.2), <strong>fire</strong>-retardant-treated wood enclosed in noncombustible<br />
or limited-combustible materials shall be permitted.<br />
(7) Openings in the separation shall be protected by <strong>fire</strong> door<br />
assemblies equipped with door closers complying with 7.2.1.8.<br />
(8)* Openings in exit enclosures shall be l<br />
Correction: Provide required separation that meets the requirements of section 8.2 and 7.1.3.2.2.<br />
Approvals and building permits required for any modifications, additions or changes to structure.<br />
Comments:<br />
15 8/25/12 7/19/12<br />
Violation: NFPA 101 9.7.5 Maintenance and Testing. All automatic sprinkler and standpipe<br />
systems required by this Code shall be inspected, tested, and maintained in accordance with NFPA<br />
25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection<br />
Systems.<br />
Correction: Have a <strong>fire</strong> protection contractor perform all required <strong>inspection</strong>s, tests, and<br />
maintenance in accordance with NFPA 25. Provide copy of records for review.<br />
Comments:<br />
16 8/25/12 7/19/12<br />
Violation: NFPA 101 7.10.1.2* Exits. Exits, other than main exterior exit doors that obviously and<br />
clearly are identifiable as exits, shall be marked by an approved sign that is readily visible from any<br />
direction of exit access.<br />
Correction: Provide required exit signs.<br />
Comments:<br />
17 8/25/12 7/19/12<br />
Violation: NFPA 101 7.2.1.8.1* A door leaf normally required to be kept closed shall not be<br />
secured in the open position at any time and shall be self-closing or automatic-closing in<br />
accordance with 7.2.1.8.2, unless otherwise permitted by 7.2.1.8.3.<br />
Correction: Discontinue the use of hold-open devices on self closing doors.<br />
Comments:<br />
Printed:<br />
9/20/12<br />
Please Note: A life safety permit will be issued upon compliance of outstanding violations and payment of fees assesed. One (1)<br />
re-<strong>inspection</strong> will be performed at no additional cost. All subsequent re-<strong>inspection</strong>s will be billed at one-half the original permit fee amount.<br />
Customer sign off: Contact A. MEJIA<br />
Page 4 of 5
18 9/20/12 10/20/12<br />
INSPECTION REPORT PERMIT # 00121-00204 Page 5 of 5<br />
Violation: NFPA 1 11.3.1.2 All existing elevators having a travel distance of 25 ft (7620 mm) or<br />
more above or below the level that best serves the needs of emergency personnel for <strong>fire</strong> fighting<br />
or <strong>rescue</strong> purposes shall conform to the Fire Fighters' Emergency Operations requirements of<br />
ASME A17.3, Safety Code for Existing Elevators and Escalators. [101:9.4.3.2]<br />
Correction: Provide/Maintain existing elevators having a travel distance of 25 ft (7620 mm) or more<br />
above or below the level that best serves the needs of emergency personnel for <strong>fire</strong> fighting or<br />
<strong>rescue</strong> purposes shall conform to the Fire Fighters' Emergency Operations requirements of ASME<br />
A17.3, Safety Code for Existing Elevators and Escalators. [101:9.4.3.2]<br />
Comments: PROVIDE FIRE OVVERRIDE KEYS FOR NEW WING<br />
19 9/20/12 10/20/12<br />
20 9/20/12 10/20/12<br />
Violation: NFPA 101 7.2.1.15.8 Door openings not in proper operating condition shall be repaired<br />
or replaced without delay.<br />
Correction: Repair or replace door openings to provide/maintain proper operating condition without<br />
delay.<br />
Comments: SERVICE DOORS THAT DO NOT CLOSE UNDER OWN POWER,414A AND<br />
THROUGHOUT AS NEEDED<br />
Violation: NFPA 1 13.6.2* Where Required. Fire extinguishers shall be provided where required<br />
by this Code as specified in Table 13.6.2 and the referenced codes and standards listed in Chapter<br />
2.<br />
Correction: Have <strong>fire</strong> extinguisher dealer provide and install <strong>fire</strong> extinguishers, distributed in<br />
accordance with NFPA1:13.6.8<br />
Comments: PROVIDE MISSING FIRE EXTINGUISHER IN LOCKER ROOM HALLWAY<br />
21 9/20/12 10/20/12<br />
Violation: NFPA 101 7.9.2.6* Existing battery-operated emergency lights shall use only reliable<br />
types of rechargeable batteries provided with suitable facilities for maintaining them in properly<br />
charged condition. Batteries used in such lights or units shall be approved for their intended use<br />
and shall comply with NFPA 70, National Electrical Code.<br />
Correction: Provide reliable type batteries.<br />
Comments: PROVIDE EMERGENCY LIGHTING IN WEIGHT ROOM<br />
22 9/20/12 10/20/12<br />
Violation: NFPA 101 7.8.1.2 Illumination of means of egress shall be continuous during the time<br />
that the conditions of occupancy require that the means of egress be available for use, unless<br />
otherwise provided in 7.8.1.2.2.<br />
Correction: Provide illumination of means of egress continuously during the time that the conditions<br />
of occupancy require that the means of egress be available for use, unless otherwise provided in<br />
7.8.1.2.2.<br />
Comments: PROVIDE EMERGENCY LIGHTING IN WEIGHT ROOM<br />
Printed:<br />
9/20/12<br />
Please Note: A life safety permit will be issued upon compliance of outstanding violations and payment of fees assesed. One (1)<br />
re-<strong>inspection</strong> will be performed at no additional cost. All subsequent re-<strong>inspection</strong>s will be billed at one-half the original permit fee amount.<br />
Customer sign off: Contact A. MEJIA<br />