Air circuit breakers ARION WL


WWW.OEZ.COM


Air circuit breakers ARION WL<br />

CONTENT – Commercial information<br />

CONTENT – Technical information<br />

DATA FOR SELECTION OF CIRCUIT BREAKER AND SWITCH-DISCONNECTOR .........................................................2<br />

ADVANTAGES OF CIRCUIT BREAKERS ARION WL .........................................................................................................5<br />

OVERVIEW OF TYPES AND ACCESSORIES .......................................................................................................................6<br />

DATA FOR SELECTION OF OVERCURRENT RELEASE .....................................................................................................9<br />

MEANING OF TYPE DESIGNATION POSITIONS ............................................................................................................10<br />

STANDARD EQUIPMENT OF CIRCUIT BREAKER/SWITCH-DISCONNECTOR ..........................................................10<br />

QUICK COMPOSITION OF TYPE DESIGNATION ............................................................................................................11<br />

PROCEDURE FOR TYPE DESIGNATION COMPOSITION ..............................................................................................<strong>12</strong><br />

OFFER OF STANDARD CIRCUIT BREAKERS AND SWITCH-DISCONNECTORS ........................................................14<br />

COMPOSITION OF TYPE DESIGNATION of 3-pole circuit breakers, switch-disconnectors for AC operation<br />

Fixed design ................................................................................................................................................................18<br />

Withdrawable design ..................................................................................................................................................20<br />

COMPOSITION OF TYPE DESIGNATION of 4-pole circuit breakers, switch-disconnectors for AC operation<br />

Fixed design ................................................................................................................................................................22<br />

Withdrawable design ..................................................................................................................................................24<br />

COMPOSITION OF TYPE DESIGNATION of 3 and 4-pole switch-disconnectors for DC operation<br />

Fixed design ................................................................................................................................................................26<br />

Withdrawable design ..................................................................................................................................................27<br />

BASIC ACCESSORIES - drives, auxiliary releases and switches ....................................................................................28<br />

ADDITIONAL ACCESSORIES<br />

Method of connection, terminal boards of auxiliary circuits ........................................................................................29<br />

Closing release and motor drives with different operating voltage, opening release ..................................................30<br />

Rated voltage 1000 V ..................................................................................................................................................31<br />

Rated current modules ................................................................................................................................................31<br />

Signal switches ...........................................................................................................................................................31<br />

Control presentation ...................................................................................................................................................32<br />

Data communication and measurement .....................................................................................................................32<br />

Blocking and locking ...................................................................................................................................................33<br />

Covers, door sealing frame ..........................................................................................................................................34<br />

SEPARATELY DELIVERED ACCESSORIES<br />

Connecting sets ..........................................................................................................................................................35<br />

Withdrawable design ..................................................................................................................................................37<br />

Rated current modules ................................................................................................................................................39<br />

Test device ..................................................................................................................................................................39<br />

CubicleBUS modules and cables ..................................................................................................................................39<br />

Voltage sources ...........................................................................................................................................................39<br />

Data communication – BDA adapter, parameterization software ...............................................................................40<br />

Voltage transformers ..................................................................................................................................................40<br />

External current transformers for N conductor ............................................................................................................40<br />

Auxiliary power source for shunt release .....................................................................................................................41<br />

Bowden cables for mechanical interlocking ................................................................................................................41<br />

Sealable covers of overcurrent release ........................................................................................................................41<br />

Door sealing frame ......................................................................................................................................................41<br />

Transparent cover ........................................................................................................................................................41<br />

Arc chute cover for withdrawable device .....................................................................................................................41<br />

Bearing angle .............................................................................................................................................................41<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE ...........................................................................42<br />

see page 49<br />

1


ARION WL - Commercial information<br />

Data for selection of circuit breakers<br />

››› for AC operation<br />

Size I II III<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

2500 A<br />

4000 A<br />

5000 A<br />

6300 A<br />

3200 A<br />

Rated operating voltage U e<br />

690 V a.c. 690 V a.c.<br />

(1000 A a.c.)<br />

690 V a.c.<br />

(1000 A a.c.)<br />

Rated frequency f n<br />

50/60 Hz 50/60 Hz 50/60 Hz<br />

Rated short-circuit ultimate<br />

breaking capacity<br />

I cu<br />

N - 50 kA/440 V a.c.<br />

S - 65 kA/440 V a.c.<br />

Rated short-time withstand current I cw<br />

N - 42 kA /1 s<br />

S - 50 kA/1 s<br />

Rated short-circuit<br />

making capacity<br />

I cm<br />

N - 105 kA/440 V a.c.<br />

S - 143 kA/440 V a.c.<br />

N - 55 kA/440 V a.c.<br />

S - 80 kA/440 V a.c.<br />

H - 100 kA/440 V a.c.<br />

N - 55 kA /1 s<br />

S - 65 kA /1 s<br />

H - 80 kA /1 s<br />

N - <strong>12</strong>1 kA/440 V a.c.<br />

S - 176 kA/440 V a.c.<br />

H - 220 kA/440 V a.c.<br />

H - 100 kA/440 V a.c.<br />

H - 80 kA /1 s (I n<br />

= 4000, 5000 A)<br />

H - 100 kA /1 s (I n<br />

= 6300 A)<br />

H - 220 kA/440 V a.c.<br />

Number of poles 3, 4 3, 4 3, 4<br />

Max. rated current of the circuit breaker I n<br />

[A]<br />

Rated short-circuit ultimate<br />

breaking capacity<br />

I cu<br />

at 440 V [kA] a.c.<br />

fi x e d<br />

3/4 pole<br />

Dimensions<br />

withdrawable<br />

3/4 pole<br />

630<br />

291 / 291<br />

385 / 385<br />

depth<br />

Dimensions III Dimensions II Dimensions I<br />

800<br />

1000<br />

<strong>12</strong>50<br />

1600<br />

800<br />

1000<br />

<strong>12</strong>50<br />

1600<br />

2000<br />

2500<br />

3200<br />

4000<br />

5000<br />

6300<br />

N<br />

S<br />

55 65<br />

N S H<br />

50 80 100<br />

H<br />

100<br />

434 / 434<br />

320 / 410<br />

291 / 291<br />

434 / 434<br />

460 / 590<br />

291 / 291<br />

434 / 434<br />

704 / 914<br />

460 / 460<br />

320 / 410<br />

385 / 385<br />

460 / 460<br />

460 / 590<br />

385 / 385<br />

460 / 460<br />

704 / 914<br />

height<br />

width<br />

depth<br />

height<br />

width<br />

depth<br />

height<br />

width<br />

2


ARION WL - Commercial information<br />

Data for selection of switch-disconnector<br />

››› for AC operation<br />

Size I II III<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

2500 A<br />

4000 A<br />

5000 A<br />

6300 A<br />

3200 A<br />

Rated operating voltage U e<br />

690 V a.c. 690 V a.c.<br />

(1000 A a.c.)<br />

690 V a.c.<br />

(1000 A a.c.)<br />

Rated frequency f n<br />

50/60 Hz 50/60 Hz 50/60 Hz<br />

Rated short-circuit<br />

making capacity<br />

I cu<br />

N - 105 kA/440 V a.c.<br />

S - 143 kA/440 V a.c.<br />

Rated short-time withstand current I cw<br />

N - 42 kA /1 s<br />

S - 50 kA/1 s<br />

N - <strong>12</strong>1 kA/440 V a.c.<br />

S - 176 kA/440 V a.c.<br />

H - 220 kA/440 V a.c.<br />

N - 65 kA /1 s<br />

S - 55 kA /1 s<br />

H - 80 kA /1 s<br />

H - 220 kA/440 V a.c.<br />

H - 80 kA /1 s (I n<br />

= 4000, 5000 A)<br />

H - 100 kA /1 s (I n<br />

= 6300 A)<br />

Number of poles 3, 4 3, 4 3, 4<br />

Data for selection of switch-disconnector<br />

››› for DC operation<br />

Size<br />

II<br />

Rated current I n<br />

1000 A<br />

2000 A<br />

4000 A<br />

Rated operating voltage U e<br />

300 V d.c.<br />

600 V d.c.<br />

1000 V d.c.<br />

Rated conditional short-circuit current I cc<br />

30 kA/300 V d.c.<br />

25 kA/600 V d.c.<br />

20 kA/1000 V d.c.<br />

Rated short-time withstand current I cw<br />

55 kA /1 s<br />

65 kA /1 s<br />

80 kA /1 s<br />

Rated short-circuit<br />

making capacity<br />

I cm<br />

30 kA/300 V d.c.<br />

25 kA/600 V d.c.<br />

20 kA/1000 V d.c.<br />

Number of poles 3, 4<br />

for possible protection of DC circuits, please call technical assistance. See the cover sheet for contact.<br />

3


ARION WL - Commercial information<br />

NOTES<br />

4


ARION WL - Commercial information<br />

NOTES<br />

5


ARION WL - Commercial information<br />

OVERVIEW OF TYPES AND ACCESSORIES<br />

1 Withdrawable device<br />

2 Front, flanged, horizontal and vertical connection<br />

3 Position signal switches<br />

4 Earthing contact<br />

5 Insulation cover<br />

2<br />

6 COM 15 PROFIBUS module<br />

7 Cubicle BUS modules<br />

8 Closing/shunt release, undervoltage release<br />

9 Connector and terminal boards of auxiliary circuits<br />

10 Auxiliary switches<br />

11 Door sealing frame<br />

<strong>12</strong> Protective caps for mechanical On/Off<br />

13 Emergency OFF push-button<br />

3<br />

1<br />

4<br />

14 Locking device against unauthorized closing<br />

15 Motor drive<br />

16 Cycle counter<br />

17 BSS module<br />

18 Overcurrent release<br />

19 Remote reset electromagnet<br />

20 BDA adapter<br />

21<br />

19<br />

21 Display<br />

22 Earth-fault protection module<br />

23 Rated current module (rating plug)<br />

24 Measuring function module<br />

22<br />

25 Air circuit breaker ARION WL<br />

18<br />

23<br />

24<br />

20<br />

6


ARION WL - Commercial information<br />

DATA FOR SELECTION OF OVERCURRENT<br />

6<br />

7<br />

5<br />

8<br />

9<br />

11<br />

25 10<br />

<strong>12</strong><br />

17<br />

15<br />

13 14<br />

16<br />

7


ARION WL - Commercial information<br />

NOTES<br />

8


ARION WL - Commercial information<br />

DATA FOR SELECTION OF OVERCURRENT RELEASE<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

I R<br />

I sd<br />

t sd<br />

Overcurrent release name ETU15B ETU25B ETU27B ETU45B ETU55B ETU76B<br />

Overload protection L + + + + + +<br />

Short-time delayed short-circuit protection S – + + + + +<br />

Instantaneous short-circuit protection I + + + + + +<br />

Neutral conductor protection N – – + + + +<br />

Earth-fault protection G – – + <br />

Additional functions +<br />

Neutral conductor protection On/Off – – +/+ +/+ +/+ +/+<br />

Short-time delayed short-circuit protection On/Off – – – +/+ +/+ +/+<br />

Instantaneous short-circuit protection On/Off – – – +/+ +/+ +/+<br />

Thermal memory On/Off – – – + + +<br />

Load guarding – – – + + +<br />

Short-time delayed short-circuit protection<br />

switchable to I 2 t<br />

– – – + + +<br />

Instantaneous short-circuit protection adjustable + – – + + +<br />

Overload protection switchable to I 4 t – – – + + +<br />

Overload protection On/Off – – – – + +<br />

Adjustable neutral conductor protection N – – – + + +<br />

Switchable parameter sets – – – – + +<br />

Parameterization and display<br />

Parameterization by rotary switches (10 positions) + + + + – –<br />

Parameterization by means of communication<br />

(absolute values)<br />

– – – – + +<br />

Parameterization by means of menu (absolute values) – – – – – +<br />

Remote parameterization of basic functions – – – – + +<br />

Remote parameterization of additional functions – – – + + +<br />

4-line LCD – – – – –<br />

Graphic LCD – – – – – +<br />

Measuring function<br />

Measuring function Plus – – – <br />

Communication<br />

CubicleBUS – – – + + +<br />

PROFIBUS-DP/MODBUS – – – <br />

Ethernet – – – <br />

+ YES, – NO, Optional<br />

9


ARION WL - Commercial information<br />

MEANING OF TYPE DESIGNATION POSITIONS<br />

Example of type designation: ARION WL<strong>12</strong>20-3CB36-4GA2-Z +K07<br />

Position number: 5 6 - 7 8 9 - 10 11 <strong>12</strong> 13 14 15 16<br />

Type designation: ARION WL1 2 20 - 3 CB 3 6 - 4 G A 2 - Z +K07<br />

Size<br />

Rated current<br />

Rated short-circuit ultimate breaking capacity<br />

Overcurrent release<br />

Number of poles<br />

Design and type of connection<br />

Drive<br />

1st auxiliary release<br />

2nd auxiliary release<br />

Auxiliary switches<br />

Accessories (it is possible to fill in more codes at a time)<br />

ARION WL<strong>12</strong>20-3CB36-4GA2-Z +K07<br />

Parameters and description of circuit breaker according to positions:<br />

5) size II<br />

6 - 7) rated current I n<br />

= 2000 A<br />

8) rated short-circuit ultimate breaking capacity I cu<br />

= 80 kA<br />

9 - 10) overcurrent release ETU25B<br />

11) 3-pole design<br />

<strong>12</strong>) withdrawable design, rear horizontal connection<br />

13) hand and motor drive with closing release for 230 V a.c./220 V d.c.<br />

14) shunt release 230 V a.c./220 V d.c.<br />

15) without 2nd auxiliary release<br />

16) 2 closing and 2 opening auxiliary contacts<br />

Accessory code - signal switch „switched off by overcurrent release“ - K07<br />

STANDARD EQUIPMENT OF CIRCUIT BREAKER/SWITCH-DISCONNECTOR<br />

Each circuit breaker/switch-disconnector has the following standard equipment<br />

Fixed design<br />

Push-button for mechanical ON<br />

Push-button for mechanical OFF<br />

Hand drive with energy-storing mechanism<br />

Mechanical indicator of circuit breakers On/Off state<br />

Mechanical indicator of energy-storing mechanism state - wound up/released<br />

Mechanical indicator of „ready-to-close“ state<br />

Auxiliary switches - 2 closing and 2 break contacts<br />

Terminal board and connectors for connection of auxiliary circuits - the circuit<br />

breaker/switch-disconnector is always equipped with all necessary terminal<br />

boards and connectors; terminal board has screw terminals<br />

Mechanical indicator of switching off by overcurrent release<br />

Mechanical interlocking of reset after switching off by overcurrent release<br />

Withdrawable design - withdrawable design contains additionally:<br />

Mechanical indicator of the circuit breaker position in the<br />

withdrawable device<br />

Locking device against circuit breaker shifting using a padlock<br />

10


ARION WL - Commercial information<br />

QUICK COMPOSITION OF TYPE DESIGNATION<br />

The table can be used for quick and simple selection and composition of type designation of a circuit breaker/switch-disconnector ARION WL.<br />

The table contains only common types of circuit breakers/switch-disconnectors. For complete offer, use the catalogue.<br />

Type designation: ARION WL1 2 20 - 3 CB 3 6 - 4 G A 2 - Z +K07<br />

Size<br />

size I from 630 to 1600 A 1<br />

size II from 800 to 3200 A 2<br />

size III from 4000 to 6300 A 3<br />

Rated current<br />

630 A only size I 06<br />

800 A recommended size I 08<br />

1000 A recommended size I 10<br />

<strong>12</strong>50 A recommended size I <strong>12</strong><br />

1600 A recommended size I 16<br />

2000 A only size II 20<br />

2500 A only size II 25<br />

3200 A only size II 32<br />

4000 A only size III 40<br />

5000 A only size III 50<br />

6300 A only size III 63<br />

Rated short-circuit ultimate breaking capacity<br />

N – ECO 50 kA for size I, 55 kA for size II 2<br />

S – STANDARD 80 kA for size II, 65 kA for size I 3<br />

H – HIGH 100 kA for size II and size III 4<br />

Overcurrent release<br />

without overcurrent release Switch-disconnector AA<br />

ETU25B Circuit breaker CB<br />

ETU45B - without display Circuit breaker EB<br />

ETU45B - with display Circuit breaker FB<br />

ETU76B - with graphic display Circuit breaker NB<br />

Design<br />

3 – pole 3<br />

4 – pole 4<br />

Design<br />

fixed rear vertical connection 1<br />

fixed rear horizontal connection 2<br />

fixed front connection 4<br />

withdrawable rear horizontal connection 6<br />

withdrawable rear vertical connection 7<br />

Drive<br />

hand drive 1<br />

hand and motor drive, closing release 230 V a.c./220 V d.c. 4<br />

hand and motor drive, closing release 110 V a.c./d.c. 5<br />

hand and motor drive, closing release 24 V d.c. 6<br />

1st auxiliary release<br />

without 1st auxiliary release A<br />

shunt release 24 V d.c. B<br />

shunt release 110 V a.c./d.c. F<br />

shunt release 230 V a.c./220 V d.c. G<br />

2nd auxiliary release<br />

without 2nd auxiliary release A<br />

shunt release 24 V d.c. B<br />

shunt release 110 V a.c./d.c. F<br />

shunt release 230 V a.c./220 V d.c. G<br />

undervoltage release 24 V d.c. J<br />

undervoltage release 110 V a.c./d.c. M<br />

undervoltage release 230 V a.c./220 V d.c. N<br />

Auxiliary switches<br />

2 NO + 2 NC 2<br />

4 NO + 4 NC 4<br />

Accessories (it is possible to fill in more codes at a time)<br />

Push-button electrically ON on the front panel C11<br />

Signal switch of the energy-storing mechanism state C20<br />

Signal switch „ready-to-close” C22<br />

Signal switch „switched off by release“ K07<br />

Position signal switches in the plug-in frame R15<br />

Door sealing frame T40<br />

Locking device against unauthorized tripping on the front control panel S01<br />

Example of type designation: ARION WL<strong>12</strong>20-3CB36-4GA2-Z +K07<br />

11


ARION WL - Commercial information<br />

PROCEDURE FOR TYPE DESIGNATION COMPOSITION<br />

Steps for correct composition<br />

For correct composition of type designation, follow the following steps as described and illustrated on the example.<br />

1. Determination of circuit breaker type in the catalogue content - 3 or 4-pole circuit breaker/switch-disconnector for AC or DC application of fixed or withdrawable design<br />

2. Determination of type designation basis according to: - connection type<br />

- rated current<br />

- rated ultimate short-circuit breaking capacity<br />

3. Determination of overcurrent release - for selection it is possible to use detailed table on page 9 „Data for selection of overcurrent release“<br />

4. Selection of basic accessories - drives, auxiliary releases and switches<br />

5. Selection of additional accessories<br />

It is also possible to order separately delivered accessories for the circuit breakers.<br />

Steps 1 - 4 are mandatory for the composition of complete type designation for ordering. Step 5 depends on other requirements for the circuit breaker.<br />

Example of type designation composition<br />

1. Determination of the circuit breaker/switch-disconnector type in the catalogue content<br />

Catalogue content<br />

Page 1<br />

2. Determination of the type designation basis according to: - connection type<br />

- rated current<br />

- rated ultimate short-circuit breaking capacity<br />

Type designation basis: ARION WL <strong>12</strong>20-232-<br />

Page 18<br />

3. Determination of overcurrent release<br />

Type designation including overcurrent release: ARION WL<strong>12</strong>20-2CB32-<br />

Page 18<br />

<strong>12</strong>


ARION WL - Commercial information<br />

PROCEDURE IN COMPOSITION OF TYPE DESIGNATION<br />

4. Selection of basic accessories<br />

Type designation: ARION WL <strong>12</strong>20-2CB32-4GA2<br />

Page 28<br />

5. Selection of additional accessories<br />

Complete type designation: ARION WL <strong>12</strong>20-2CB32-4GA2-Z K07<br />

Page 31<br />

13


ARION WL - Commercial information<br />

OFFER OF STANDARD CIRCUIT BREAKERS AND SWITCH-DISCONNECTORS<br />

3P<br />

Circuit breakers, 3-pole design<br />

Fixed design<br />

Withdrawable design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3CB32-1GA2 19209 I n<br />

= 1000 A, size 1, I cu<br />

= 65 kA 43<br />

ARION WL1116-3CB32-1GA2 19211 I n<br />

= 1600 A, size 1, I cu<br />

= 65 kA 43<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3CB32-1GA2 19216 I n<br />

= 2000 A, size 2, I cu<br />

= 80 kA 56<br />

ARION WL<strong>12</strong>25-3CB32-1GA2 19217 I n<br />

= 2500 A, size 2, I cu<br />

= 80 kA 59<br />

ARION WL<strong>12</strong>32-3CB32-1GA2 19218 I n<br />

= 3200 A, size 2, I cu<br />

= 80 kA 64<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4CB32-1GA2 19226 I n<br />

= 4000 A, size 3, I cu<br />

= 100 kA 82<br />

ARION WL1350-4CB32-1GA2 19227 I n<br />

= 5000 A, size 3, I cu<br />

= 100 kA 82<br />

ARION WL1363-4CB31-1GA2 19228 I n<br />

= 6300 A, size 3, I cu<br />

= 100 kA 90<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3CB36-1GA2 18238 I n<br />

= 1000 A, size 1, I cu<br />

= 65 kA 70<br />

ARION WL1116-3CB36-1GA2 19240 I n<br />

= 1600 A, size 1, I cu<br />

= 65 kA 70<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3CB36-1GA2 19245 I n<br />

= 2000 A, size2, I cu<br />

= 80 kA 91<br />

ARION WL<strong>12</strong>25-3CB36-1GA2 19246 I n<br />

= 2500 A, size 2, I cu<br />

= 80 kA 102<br />

ARION WL<strong>12</strong>32-3CB36-1GA2 19247 I n<br />

= 3200 A, size 2, I cu<br />

= 80 kA 113<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4CB36-1GA2 19255 I n<br />

= 4000 A, size 3, I cu<br />

= 100 kA 148<br />

ARION WL1350-4CB36-1GA2 19256 I n<br />

= 5000 A, size 3, I cu<br />

= 100 kA 148<br />

ARION WL1363-4CB37-1GA2 19257 I n<br />

= 6300 A, size 3, I cu<br />

= 100 kA 178<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

In your order always state both type designation and product code, if any<br />

14


ARION WL - Commercial information<br />

OFFER OF STANDARD CIRCUIT BREAKERS AND SWITCH-DISCONNECTORS<br />

4P<br />

Circuit breakers, 4-pole design<br />

Fixed design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3CB42-1GA2 19267 I n<br />

= 1000 A, size 1, I cu<br />

= 65 kA 50<br />

ARION WL1116-3CB42-1GA2 19269 I n<br />

= 1600 A, size 1, I cu<br />

= 65 kA 50<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3CB42-1GA2 19247 I n<br />

= 2000 A, size 2, I cu<br />

= 80 kA 67<br />

ARION WL<strong>12</strong>25-3CB42-1GA2 19275 I n<br />

= 2500 A, size 2, I cu<br />

= 80 kA 71<br />

ARION WL<strong>12</strong>32-3CB42-1GA2 19276 I n<br />

= 3200 A, size 2, I cu<br />

= 80 kA 77<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4CB42-1GA2 19284 I n<br />

= 4000 A, size 3, I cu<br />

= 100 kA 99<br />

ARION WL1350-4CB42-1GA2 19285 I n<br />

= 5000 A, size 3, I cu<br />

= 100 kA 99<br />

ARION WL1363-4CB41-1GA2 19286 I n<br />

= 6300 A, size 3, I cu<br />

= 100 kA 108<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3CB46-1GA2 19296 I n<br />

= 1000 A, size 1, I cu<br />

= 65 kA 84<br />

ARION WL1116-3CB46-1GA2 19298 I n<br />

= 1600 A, size 1, I cu<br />

= 65 kA 84<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3CB46-1GA2 19303 I n<br />

= 2000 A, size 2, I cu<br />

= 80 kA 106<br />

ARION WL<strong>12</strong>25-3CB46-1GA2 19304 I n<br />

= 2500 A, size 2, I cu<br />

= 80 kA <strong>12</strong>3<br />

ARION WL<strong>12</strong>32-3CB46-1GA2 19305 I n<br />

= 3200 A, size 2, I cu<br />

= 80 kA 136<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4CB46-1GA2 19313 I n<br />

= 4000 A, size 3, I cu<br />

= 100 kA 190<br />

ARION WL1350-4CB46-1GA2 19314 I n<br />

= 5000 A, size 3, I cu<br />

= 100 kA 190<br />

ARION WL1363-4CB47-1GA2 19315 I n<br />

= 6300 A, size 3, I cu<br />

= 100 kA 227<br />

- overcurrent release ETU25B<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

In your order always state both type designation and product code, if any<br />

15


ARION WL - Commercial information<br />

OFFER OF STANDARD CIRCUIT BREAKERS AND SWITCH-DISCONNECTORS<br />

3P<br />

Switch-disconnector, 3-pole design<br />

Fixed design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3AA32-1GA2 19319 I n<br />

= 1000 A, size 1 43<br />

ARION WL1116-3AA32-1GA2 19320 I n<br />

= 1600 A, size 1 43<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3AA32-1GA2 19380 I n<br />

= 2000 A, size 2 56<br />

ARION WL<strong>12</strong>25-3AA32-1GA2 19410 I n<br />

= 2500 A, size 2 59<br />

ARION WL<strong>12</strong>32-3AA32-1GA2 19411 I n<br />

= 3200 A, size 2 64<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4AA32-1GA2 194<strong>12</strong> I n<br />

= 4000 A, size 3 82<br />

ARION WL1350-4AA32-1GA2 19413 I n<br />

= 5000 A, size 3 82<br />

ARION WL1363-4AA31-1GA2 19414 I n<br />

= 6300 A, size 3 90<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

Withdrawable design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3AA36-1GA2 19415 I n<br />

= 1000 A, size 1 70<br />

ARION WL1116-3AA36-1GA2 19416 I n<br />

= 1600 A, size 1 70<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3AA36-1GA2 19417 I n<br />

= 2000 A, size 2 91<br />

ARION WL<strong>12</strong>25-3AA36-1GA2 19418 I n<br />

= 2500 A, size 2 102<br />

ARION WL<strong>12</strong>32-3AA36-1GA2 19419 I n<br />

= 3200 A, size 2 113<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4AA36-1GA2 19420 I n<br />

= 4000 A, size 3 148<br />

ARION WL1350-4AA36-1GA2 19392 I n<br />

= 5000 A, size 3 148<br />

ARION WL1363-4AA37-1GA2 19393 I n<br />

= 6300 A, size 3 178<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

In your order always state both type designation and product code, if any<br />

16


ARION WL - Commercial information<br />

OFFER OF STANDARD CIRCUIT BREAKERS AND SWITCH-DISCONNECTORS<br />

4P<br />

Switch-disconnector, 4-pole design<br />

Fixed design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3AA42-1GA2 19394 I n<br />

= 1000 A, size 1 50<br />

ARION WL1116-3AA42-1GA2 19395 I n<br />

= 1600 A, size 1 50<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3AA42-1GA2 19396 I n<br />

= 2000 A, size 2 67<br />

ARION WL<strong>12</strong>25-3AA42-1GA2 19397 I n<br />

= 2500 A, size 2 71<br />

ARION WL<strong>12</strong>32-3AA42-1GA2 19398 I n<br />

= 3200 A, size 2 77<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4AA42-1GA2 19399 I n<br />

= 4000 A, size 3 99<br />

ARION WL1350-4AA42-1GA2 19400 I n<br />

= 5000 A, size 3 99<br />

ARION WL1363-4AA41-1GA2 19401 I n<br />

= 6300 A, size 3 108<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

Withdrawable design<br />

Type Product code Description Weight [kg]<br />

ARION WL1110-3AA46-1GA2 19402 I n<br />

= 1000 A, size 1 84<br />

ARION WL1116-3AA46-1GA2 19403 I n<br />

= 1600 A, size 1 84<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL<strong>12</strong>20-3AA46-1GA2 19404 I n<br />

= 2000 A, size 2 106<br />

ARION WL<strong>12</strong>25-3AA46-1GA2 19405 I n<br />

= 2500 A, size 2 <strong>12</strong>3<br />

ARION WL<strong>12</strong>32-3AA46-1GA2 19406 I n<br />

= 3200 A, size 2 136<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection<br />

ARION WL1340-4AA46-1GA2 19407 I n<br />

= 4000 A, size 3 190<br />

ARION WL1350-4AA46-1GA2 19408 I n<br />

= 5000 A, size 3 190<br />

ARION WL1363-4AA47-1GA2 19409 I n<br />

= 6300 A, size 3 227<br />

- hand drive, mechanical On/Off<br />

- shunt release 230 V a.c./ 220 V d.c.<br />

- auxiliary switch S1 and S2 (2Z + 2R)<br />

- rear horizontal connection (6300 A - rear vertical connection)<br />

In your order always state both type designation and product code, if any<br />

17


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Fixed design, 3-pole, AC<br />

Rear horizontal connection<br />

<br />

Rear vertical connection<br />

<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

[A]<br />

50 kA – size I 55 kA – size II 65 kA – size I<br />

N N S<br />

630 ARION WL1106-232- - ARION WL1106-332-<br />

800 ARION WL1108-232- - ARION WL1108-332-<br />

1000 ARION WL1110-232- - ARION WL1110-332-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-232- - ARION WL11<strong>12</strong>-332-<br />

1600 ARION WL1116-232- - ARION WL1116-332-<br />

2000 - ARION WL<strong>12</strong>20-232- -<br />

2500 - ARION WL<strong>12</strong>25-232- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-231- - ARION WL1106-331-<br />

800 ARION WL1108-231- - ARION WL1108-331-<br />

1000 ARION WL1110-231- - ARION WL1110-331-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-231- - ARION WL11<strong>12</strong>-331-<br />

1600 ARION WL1116-231- - ARION WL1116-331-<br />

2000 - ARION WL<strong>12</strong>20-231- -<br />

2500 - ARION WL<strong>12</strong>25-231- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Front connection one series of holes<br />

Front connection two series of holes<br />

<br />

<br />

630 ARION WL1106-233- - ARION WL1106-333-<br />

800 ARION WL1108-233- - ARION WL1108-333-<br />

1000 ARION WL1110-233- - ARION WL1110-333-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-233- - ARION WL11<strong>12</strong>-333-<br />

1600 ARION WL1116-233- - ARION WL1116-333-<br />

2000 - ARION WL<strong>12</strong>20-233- -<br />

2500 - ARION WL<strong>12</strong>25-233- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-234- - ARION WL1106-334-<br />

800 ARION WL1108-234- - ARION WL1108-334-<br />

1000 ARION WL1110-234- - ARION WL1110-334-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-234- - ARION WL11<strong>12</strong>-334-<br />

1600 ARION WL1116-234- - ARION WL1116-334-<br />

2000 - ARION WL<strong>12</strong>20-234- -<br />

2500 - ARION WL<strong>12</strong>25-234- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

3)<br />

Current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

18


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Fixed design, 3-pole, AC<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

80 kA – size II 100 kA – size II 100 kA – size III<br />

Rear horizontal connection<br />

630<br />

S<br />

-<br />

H<br />

-<br />

H<br />

-<br />

800 ARION WL<strong>12</strong>08-332- ARION WL<strong>12</strong>08-432- -<br />

1000 ARION WL<strong>12</strong>10-332- ARION WL<strong>12</strong>10-432- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-332- ARION WL<strong>12</strong><strong>12</strong>-432- -<br />

1600 ARION WL<strong>12</strong>16-332- ARION WL<strong>12</strong>16-432- -<br />

2000 ARION WL<strong>12</strong>20-332- ARION WL<strong>12</strong>20-432- -<br />

2500 ARION WL<strong>12</strong>25-332- ARION WL<strong>12</strong>25-432- -<br />

3200 ARION WL<strong>12</strong>32-332- ARION WL<strong>12</strong>32-432- -<br />

4000 - - ARION WL1340-432-<br />

5000 - - ARION WL1350-432-<br />

6300 - - -<br />

Rear vertical connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-331- ARION WL<strong>12</strong>08-431- -<br />

1000 ARION WL<strong>12</strong>10-331- ARION WL<strong>12</strong>10-431- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-331- ARION WL<strong>12</strong><strong>12</strong>-431- -<br />

1600 ARION WL<strong>12</strong>16-331- ARION WL<strong>12</strong>16-431- -<br />

2000 ARION WL<strong>12</strong>20-331- ARION WL<strong>12</strong>20-431- -<br />

2500 ARION WL<strong>12</strong>25-331- ARION WL<strong>12</strong>25-431- -<br />

3200 ARION WL<strong>12</strong>32-331- ARION WL<strong>12</strong>32-431- -<br />

4000 - - ARION WL1340-431-<br />

5000 - - ARION WL1350-431-<br />

6300 - - ARION WL1363-431-<br />

Front connection one series of holes<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-333- ARION WL<strong>12</strong>08-433- -<br />

1000 ARION WL<strong>12</strong>10-333- ARION WL<strong>12</strong>10-433- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-333- ARION WL<strong>12</strong><strong>12</strong>-433- -<br />

1600 ARION WL<strong>12</strong>16-333- ARION WL<strong>12</strong>16-433- -<br />

2000 ARION WL<strong>12</strong>20-333- ARION WL<strong>12</strong>20-433- -<br />

2500 ARION WL<strong>12</strong>25-333- ARION WL<strong>12</strong>25-433- -<br />

3200 ARION WL<strong>12</strong>32-333- ARION WL<strong>12</strong>32-433- -<br />

4000 - - ARION WL1340-433-<br />

5000 - - -<br />

6300 - - -<br />

Front connection two series of holes<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-334- ARION WL<strong>12</strong>08-434- -<br />

1000 ARION WL<strong>12</strong>10-334- ARION WL<strong>12</strong>10-434- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-334- ARION WL<strong>12</strong><strong>12</strong>-434- -<br />

1600 ARION WL<strong>12</strong>16-334- ARION WL<strong>12</strong>16-434- -<br />

2000 ARION WL<strong>12</strong>20-334- ARION WL<strong>12</strong>20-434- -<br />

2500 ARION WL<strong>12</strong>25-334- ARION WL<strong>12</strong>25-434- -<br />

3200 ARION WL<strong>12</strong>32-334- ARION WL<strong>12</strong>32-434- -<br />

4000 - - ARION WL1340-434-<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

3)<br />

Current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

19


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Withdrawable design, 3-pole, AC<br />

Rear horizontal connection<br />

<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

[A]<br />

50 kA – size I 55 kA – size II 65 kA – size I<br />

N N S<br />

630 ARION WL1106-236- - ARION WL1106-336-<br />

800 ARION WL1108-236- - ARION WL1108-336-<br />

1000 ARION WL1110-236- - ARION WL1110-336-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-236- - ARION WL11<strong>12</strong>-336-<br />

1600 ARION WL1116-236- - ARION WL1116-336-<br />

2000 - ARION WL<strong>12</strong>20-236- -<br />

2500 - ARION WL<strong>12</strong>25-236- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Without withdrawable device<br />

Rear vertical connection<br />

<br />

Rear flanged connection<br />

<br />

630 ARION WL1106-235- - ARION WL1106-335-<br />

800 ARION WL1108-235- - ARION WL1108-335-<br />

1000 ARION WL1110-235- - ARION WL1110-335-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-235- - ARION WL11<strong>12</strong>-335-<br />

1600 ARION WL1116-235- - ARION WL1116-335-<br />

2000 - ARION WL<strong>12</strong>20-235- -<br />

2500 - ARION WL<strong>12</strong>25-235- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-237- - ARION WL1106-337-<br />

800 ARION WL1108-237- - ARION WL1108-337-<br />

1000 ARION WL1110-237- - ARION WL1110-337-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-237- - ARION WL11<strong>12</strong>-337-<br />

1600 ARION WL1116-237- - ARION WL1116-337-<br />

2000 - ARION WL<strong>12</strong>20-237- -<br />

2500 - ARION WL<strong>12</strong>25-237- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-238- - ARION WL1106-338-<br />

800 ARION WL1108-238- - ARION WL1108-338-<br />

1000 ARION WL1110-238- - ARION WL1110-338-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-238- - ARION WL11<strong>12</strong>-338-<br />

1600 ARION WL1116-238- - ARION WL1116-338-<br />

2000 - ARION WL<strong>12</strong>20-238- -<br />

2500 - ARION WL<strong>12</strong>25-238- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

3)<br />

Current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

20


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Withdrawable design, 3-pole, AC<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

80 kA – size II 100 kA – size II 100 kA – size III<br />

Rear horizontal connection<br />

630<br />

S<br />

-<br />

H<br />

-<br />

H<br />

-<br />

800 ARION WL<strong>12</strong>08-336- ARION WL<strong>12</strong>08-436- -<br />

1000 ARION WL<strong>12</strong>10-336- ARION WL<strong>12</strong>10-436- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-336- ARION WL<strong>12</strong><strong>12</strong>-436- -<br />

1600 ARION WL<strong>12</strong>16-336- ARION WL<strong>12</strong>16-436- -<br />

2000 ARION WL<strong>12</strong>20-336- ARION WL<strong>12</strong>20-436- -<br />

2500 ARION WL<strong>12</strong>25-336- ARION WL<strong>12</strong>25-436- -<br />

3200 ARION WL<strong>12</strong>32-336- ARION WL<strong>12</strong>32-436- -<br />

4000 - - ARION WL1340-436-<br />

5000 - - ARION WL1350-436-<br />

6300 - - -<br />

Without withdrawable device<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-335- ARION WL<strong>12</strong>08-435- -<br />

1000 ARION WL<strong>12</strong>10-335- ARION WL<strong>12</strong>10-435- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-335- ARION WL<strong>12</strong><strong>12</strong>-435- -<br />

1600 ARION WL<strong>12</strong>16-335- ARION WL<strong>12</strong>16-435- -<br />

2000 ARION WL<strong>12</strong>20-335- ARION WL<strong>12</strong>20-435- -<br />

2500 ARION WL<strong>12</strong>25-335- ARION WL<strong>12</strong>25-435- -<br />

3200 ARION WL<strong>12</strong>32-335- ARION WL<strong>12</strong>32-435- -<br />

4000 - - ARION WL1340-435-<br />

5000 - - ARION WL1350-435-<br />

6300 - - ARION WL1363-435-<br />

Rear vertical connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-337- ARION WL<strong>12</strong>08-437- -<br />

1000 ARION WL<strong>12</strong>10-337- ARION WL<strong>12</strong>10-437- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-337- ARION WL<strong>12</strong><strong>12</strong>-437- -<br />

1600 ARION WL<strong>12</strong>16-337- ARION WL<strong>12</strong>16-437- -<br />

2000 ARION WL<strong>12</strong>20-337- ARION WL<strong>12</strong>20-437- -<br />

2500 ARION WL<strong>12</strong>25-337- ARION WL<strong>12</strong>25-437- -<br />

3200 ARION WL<strong>12</strong>32-337- ARION WL<strong>12</strong>32-437- -<br />

4000 - - ARION WL1340-437-<br />

5000 - - ARION WL1350-437-<br />

6300 - - ARION WL1363-437-<br />

Rear flanged connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-338- ARION WL<strong>12</strong>08-438- -<br />

1000 ARION WL<strong>12</strong>10-338- ARION WL<strong>12</strong>10-438- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-338- ARION WL<strong>12</strong><strong>12</strong>-438- -<br />

1600 ARION WL<strong>12</strong>16-338- ARION WL<strong>12</strong>16-438- -<br />

2000 ARION WL<strong>12</strong>20-338- ARION WL<strong>12</strong>20-438- -<br />

2500 ARION WL<strong>12</strong>25-338- ARION WL<strong>12</strong>25-438- -<br />

3200 ARION WL<strong>12</strong>32-338- ARION WL<strong>12</strong>32-438- -<br />

4000 - - ARION WL1340-438-<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

3)<br />

Current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

21


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Fixed design, 4-pole, AC<br />

Rear horizontal connection<br />

<br />

Rear vertical connection<br />

<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

[A]<br />

50 kA – size I 55 kA – size II 65 kA – size I<br />

N N S<br />

630 ARION WL1106-242- - ARION WL1106-342-<br />

800 ARION WL1108-242- - ARION WL1108-342-<br />

1000 ARION WL1110-242- - ARION WL1110-342-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-242- - ARION WL11<strong>12</strong>-342-<br />

1600 ARION WL1116-242- - ARION WL1116-342-<br />

2000 - ARION WL<strong>12</strong>20-242- -<br />

2500 - ARION WL<strong>12</strong>25-242- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-241- - ARION WL1106-341-<br />

800 ARION WL1108-241- - ARION WL1108-341-<br />

1000 ARION WL1110-241- - ARION WL1110-341-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-241- - ARION WL11<strong>12</strong>-341-<br />

1600 ARION WL1116-241- - ARION WL1116-341-<br />

2000 - ARION WL<strong>12</strong>20-241- -<br />

2500 - ARION WL<strong>12</strong>25-241- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Front connection one series of holes<br />

Front connection two series of holes<br />

<br />

<br />

630 ARION WL1106-243- - ARION WL1106-343-<br />

800 ARION WL1108-243- - ARION WL1108-343-<br />

1000 ARION WL1110-243- - ARION WL1110-343-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-243- - ARION WL11<strong>12</strong>-343-<br />

1600 ARION WL1116-243- - ARION WL1116-343-<br />

2000 - ARION WL<strong>12</strong>20-243- -<br />

2500 - ARION WL<strong>12</strong>25-243- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-244- - ARION WL1106-344-<br />

800 ARION WL1108-244- - ARION WL1108-344-<br />

1000 ARION WL1110-244- - ARION WL1110-344-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-244- - ARION WL11<strong>12</strong>-344-<br />

1600 ARION WL1116-244- - ARION WL1116-344-<br />

2000 - ARION WL<strong>12</strong>20-244- -<br />

2500 - ARION WL<strong>12</strong>25-244- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

Internal current transformer for protection of N conductor can be ordered with „F23“ code, see page 32.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

22


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Fixed design, 4-pole, AC<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

80 kA – size II 100 kA – size II 100 kA – size III<br />

Rear horizontal connection<br />

630<br />

S<br />

-<br />

H<br />

-<br />

H<br />

-<br />

800 ARION WL<strong>12</strong>08-342- ARION WL<strong>12</strong>08-442- -<br />

1000 ARION WL<strong>12</strong>10-342- ARION WL<strong>12</strong>10-442- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-342- ARION WL<strong>12</strong><strong>12</strong>-442- -<br />

1600 ARION WL<strong>12</strong>16-342- ARION WL<strong>12</strong>16-442- -<br />

2000 ARION WL<strong>12</strong>20-342- ARION WL<strong>12</strong>20-442- -<br />

2500 ARION WL<strong>12</strong>25-342- ARION WL<strong>12</strong>25-442- -<br />

3200 ARION WL<strong>12</strong>32-342- ARION WL<strong>12</strong>32-442- -<br />

4000 - - ARION WL1340-442-<br />

5000 - - ARION WL1350-442-<br />

6300 - - -<br />

Rear vertical connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-341- ARION WL<strong>12</strong>08-441- -<br />

1000 ARION WL<strong>12</strong>10-341- ARION WL<strong>12</strong>10-441- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-341- ARION WL<strong>12</strong><strong>12</strong>-441- -<br />

1600 ARION WL<strong>12</strong>16-341- ARION WL<strong>12</strong>16-441- -<br />

2000 ARION WL<strong>12</strong>20-341- ARION WL<strong>12</strong>20-441- -<br />

2500 ARION WL<strong>12</strong>25-341- ARION WL<strong>12</strong>25-441- -<br />

3200 ARION WL<strong>12</strong>32-341- ARION WL<strong>12</strong>32-441- -<br />

4000 - - ARION WL1340-441-<br />

5000 - - ARION WL1350-441-<br />

6300 - - ARION WL1363-441-<br />

Front connection one series of holes<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-343- ARION WL<strong>12</strong>08-443- -<br />

1000 ARION WL<strong>12</strong>10-343- ARION WL<strong>12</strong>10-443- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-343- ARION WL<strong>12</strong><strong>12</strong>-443- -<br />

1600 ARION WL<strong>12</strong>16-343- ARION WL<strong>12</strong>16-443- -<br />

2000 ARION WL<strong>12</strong>20-343- ARION WL<strong>12</strong>20-443- -<br />

2500 ARION WL<strong>12</strong>25-343- ARION WL<strong>12</strong>25-443- -<br />

3200 ARION WL<strong>12</strong>32-343- ARION WL<strong>12</strong>32-443- -<br />

4000 - - ARION WL1340-443-<br />

5000 - - -<br />

6300 - - -<br />

Front connection two series of holes<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-344- ARION WL<strong>12</strong>08-444- -<br />

1000 ARION WL<strong>12</strong>10-344- ARION WL<strong>12</strong>10-444- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-344- ARION WL<strong>12</strong><strong>12</strong>-444- -<br />

1600 ARION WL<strong>12</strong>16-344- ARION WL<strong>12</strong>16-444- -<br />

2000 ARION WL<strong>12</strong>20-344- ARION WL<strong>12</strong>20-444- -<br />

2500 ARION WL<strong>12</strong>25-344- ARION WL<strong>12</strong>25-444- -<br />

3200 ARION WL<strong>12</strong>32-344- ARION WL<strong>12</strong>32-444- -<br />

4000 - - ARION WL1340-444-<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

Internal current transformer for protection of N conductor can be ordered with „F23“ code, see page 32.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

23


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Withdrawable design, 4-pole, AC<br />

Rear horizontal connection<br />

<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

[A]<br />

50 kA –size I 55 kA – size II 65 kA – size I<br />

N N S<br />

630 ARION WL1106-246- - ARION WL1106-346-<br />

800 ARION WL1108-246- - ARION WL1108-346-<br />

1000 ARION WL1110-246- - ARION WL1110-346-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-246- - ARION WL11<strong>12</strong>-346-<br />

1600 ARION WL1116-246- - ARION WL1116-346-<br />

2000 - ARION WL<strong>12</strong>20-246- -<br />

2500 - ARION WL<strong>12</strong>25-246- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Without withdrawable device<br />

Rear vertical connection<br />

<br />

Rear flanged connection<br />

<br />

630 ARION WL1106-245- - ARION WL1106-345-<br />

800 ARION WL1108-245- - ARION WL1108-345-<br />

1000 ARION WL1110-245- - ARION WL1110-345-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-245- - ARION WL11<strong>12</strong>-345-<br />

1600 ARION WL1116-245- - ARION WL1116-345-<br />

2000 - ARION WL<strong>12</strong>20-245- -<br />

2500 - ARION WL<strong>12</strong>25-245- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-247- - ARION WL1106-347-<br />

800 ARION WL1108-247- - ARION WL1108-347-<br />

1000 ARION WL1110-247- - ARION WL1110-347-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-247- - ARION WL11<strong>12</strong>-347-<br />

1600 ARION WL1116-247- - ARION WL1116-347-<br />

2000 - ARION WL<strong>12</strong>20-247- -<br />

2500 - ARION WL<strong>12</strong>25-247- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

630 ARION WL1106-248- - ARION WL1106-348-<br />

800 ARION WL1108-248- - ARION WL1108-348-<br />

1000 ARION WL1110-248- - ARION WL1110-348-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-248- - ARION WL11<strong>12</strong>-348-<br />

1600 ARION WL1116-248- - ARION WL1116-348-<br />

2000 - ARION WL<strong>12</strong>20-248- -<br />

2500 - ARION WL<strong>12</strong>25-248- -<br />

3200 - - -<br />

4000 - - -<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

Internal current transformer for protection of N conductor can be ordered with „F23“ code, see page 32.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

24


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Withdrawable design, 4-pole, AC<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/440 V<br />

80 kA – size II 100 kA – size II 100 kA – size III<br />

Rear horizontal connection<br />

630<br />

S<br />

-<br />

H<br />

-<br />

H<br />

-<br />

800 ARION WL<strong>12</strong>08-346- ARION WL<strong>12</strong>08-446- -<br />

1000 ARION WL<strong>12</strong>10-346- ARION WL<strong>12</strong>10-446- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-346- ARION WL<strong>12</strong><strong>12</strong>-446- -<br />

1600 ARION WL<strong>12</strong>16-346- ARION WL<strong>12</strong>16-446- -<br />

2000 ARION WL<strong>12</strong>20-346- ARION WL<strong>12</strong>20-446- -<br />

2500 ARION WL<strong>12</strong>25-346- ARION WL<strong>12</strong>25-446- -<br />

3200 ARION WL<strong>12</strong>32-346- ARION WL<strong>12</strong>32-446- -<br />

4000 - - ARION WL1340-446-<br />

5000 - - ARION WL1350-446-<br />

6300 - - -<br />

Without withdrawable device<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-345- ARION WL<strong>12</strong>08-445- -<br />

1000 ARION WL<strong>12</strong>10-345- ARION WL<strong>12</strong>10-445- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-345- ARION WL<strong>12</strong><strong>12</strong>-445- -<br />

1600 ARION WL<strong>12</strong>16-345- ARION WL<strong>12</strong>16-445- -<br />

2000 ARION WL<strong>12</strong>20-345- ARION WL<strong>12</strong>20-445- -<br />

2500 ARION WL<strong>12</strong>25-345- ARION WL<strong>12</strong>25-445- -<br />

3200 ARION WL<strong>12</strong>32-345- ARION WL<strong>12</strong>32-445- -<br />

4000 - - ARION WL1340-445-<br />

5000 - - ARION WL1350-445-<br />

6300 - - ARION WL1363-445-<br />

Rear vertical connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-347- ARION WL<strong>12</strong>08-447- -<br />

1000 ARION WL<strong>12</strong>10-347- ARION WL<strong>12</strong>10-447- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-347- ARION WL<strong>12</strong><strong>12</strong>-447- -<br />

1600 ARION WL<strong>12</strong>16-347- ARION WL<strong>12</strong>16-447- -<br />

2000 ARION WL<strong>12</strong>20-347- ARION WL<strong>12</strong>20-447- -<br />

2500 ARION WL<strong>12</strong>25-347- ARION WL<strong>12</strong>25-447- -<br />

3200 ARION WL<strong>12</strong>32-347- ARION WL<strong>12</strong>32-447- -<br />

4000 - - ARION WL1340-447-<br />

5000 - - ARION WL1350-447-<br />

6300 - - ARION WL1363-447-<br />

Rear flanged connection<br />

630 - - -<br />

800 ARION WL<strong>12</strong>08-348- ARION WL<strong>12</strong>08-448- -<br />

1000 ARION WL<strong>12</strong>10-348- ARION WL<strong>12</strong>10-448- -<br />

<strong>12</strong>50 ARION WL<strong>12</strong><strong>12</strong>-348- ARION WL<strong>12</strong><strong>12</strong>-448- -<br />

1600 ARION WL<strong>12</strong>16-348- ARION WL<strong>12</strong>16-448- -<br />

2000 ARION WL<strong>12</strong>20-348- ARION WL<strong>12</strong>20-448- -<br />

2500 ARION WL<strong>12</strong>25-348- ARION WL<strong>12</strong>25-448- -<br />

3200 ARION WL<strong>12</strong>32-348- ARION WL<strong>12</strong>32-448- -<br />

4000 - - ARION WL1340-448-<br />

5000 - - -<br />

6300 - - -<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth-fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI 4)<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSIN 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth-fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, 4-line display 3)<br />

Overcurrent release ETU55B – protective function LSING 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

JB<br />

NB<br />

DG<br />

EG<br />

FG<br />

JG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required,<br />

its change is possible, see page 31.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page 51 (only for AC applications).<br />

Internal current transformer for protection of N conductor can be ordered with „F23“ code, see page 32.<br />

4)<br />

Power circuit breaker of size III cannot be equipped with an electronic overcurrent release ETU15B.<br />

For weight see page 51<br />

25


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION 3P 4P<br />

Fixed design, 3-pole, 4-pole, DC switch-disconnector<br />

Rear horizontal connection<br />

Rated current I n<br />

Size 3-pole design 4-pole design<br />

1000 II ARION WL<strong>12</strong>10-8AA32- ARION WL<strong>12</strong>10-8AA42-<br />

2000 II ARION WL<strong>12</strong>20-8AA32- ARION WL<strong>12</strong>20-8AA42-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA32- ARION WL<strong>12</strong>40-8AA42-<br />

<br />

Rear vertical connection<br />

1000 II ARION WL<strong>12</strong>10-8AA31- ARION WL<strong>12</strong>10-8AA41-<br />

2000 II ARION WL<strong>12</strong>20-8AA31- ARION WL<strong>12</strong>20-8AA41-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA31- ARION WL<strong>12</strong>40-8AA41-<br />

<br />

Front connection one series of holes<br />

1000 II ARION WL<strong>12</strong>10-8AA33- ARION WL<strong>12</strong>10-8AA43-<br />

2000 II ARION WL<strong>12</strong>20-8AA33- ARION WL<strong>12</strong>20-8AA43-<br />

<br />

Front connection two series of holes<br />

1000 II ARION WL<strong>12</strong>10-8AA34- ARION WL<strong>12</strong>10-8AA44-<br />

2000 II ARION WL<strong>12</strong>20-8AA34- ARION WL<strong>12</strong>20-8AA44-<br />

<br />

1 A A 2 Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200<br />

(2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Cubicle manufacturer must provide precautions for heat dissipation.<br />

Permissible rated short-time current I CW<br />

and short-circuit capacity I CC<br />

for non-automatic circuit-breakers see page 53.<br />

For weight see page 53<br />

26


ARION WL - Commercial information<br />

COMPOSITION OF TYPE DESIGNATION 3P 4P<br />

Withdrawable design, 3-pole, 4-pole, DC switch-disconnector<br />

Without withdrawable device<br />

Rated current I n<br />

Size 3-pole design 4-pole design<br />

1000 II ARION WL<strong>12</strong>10-8AA35- ARION WL<strong>12</strong>10-8AA45-<br />

2000 II ARION WL<strong>12</strong>20-8AA35- ARION WL<strong>12</strong>20-8AA45-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA35- ARION WL<strong>12</strong>40-8AA45-<br />

Rear horizontal connection<br />

1000 II ARION WL<strong>12</strong>10-8AA36- ARION WL<strong>12</strong>10-8AA46-<br />

2000 II ARION WL<strong>12</strong>20-8AA36- ARION WL<strong>12</strong>20-8AA46-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA36- ARION WL<strong>12</strong>40-8AA46-<br />

<br />

Rear vertical connection<br />

1000 II ARION WL<strong>12</strong>10-8AA37- ARION WL<strong>12</strong>10-8AA47-<br />

2000 II ARION WL<strong>12</strong>20-8AA37- ARION WL<strong>12</strong>20-8AA47-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA37- ARION WL<strong>12</strong>40-8AA47-<br />

<br />

Rear flanged connection<br />

1000 II ARION WL<strong>12</strong>10-8AA38- ARION WL<strong>12</strong>10-8AA48-<br />

2000 II ARION WL<strong>12</strong>20-8AA38- ARION WL<strong>12</strong>20-8AA48-<br />

4000 1) II ARION WL<strong>12</strong>40-8AA38- ARION WL<strong>12</strong>40-8AA48-<br />

<br />

1 A A 2 Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200<br />

(2 closing + 2 opening)<br />

(you will find other accessories on page 28)<br />

1)<br />

Cubicle manufacturer must provide precautions for heat dissipation.<br />

Permissible rated short-time current I CW<br />

and short-circuit capacity I CC<br />

for non-automatic circuit-breakers see page 53.<br />

For weight see page 53<br />

27


ARION WL - Commercial information<br />

BASIC ACCESSORIES 3P 4P<br />

Selected type designation of ARION WL1--<br />

Hand drive with mechanical closing 1<br />

Hand drive with electrical closing – closing release: load factor 100%<br />

110 V a.c./110 V d.c. 2<br />

230 V a.c./220 V d.c. 3<br />

Motor and hand drive with electrical closing – closing release: load factor 100%<br />

230 V a.c./220 V d.c. 4<br />

110 V a.c./d.c. 5<br />

24 V d.c. 6<br />

- different operating voltages for motor drive and closing release see page 30<br />

1st auxiliary release<br />

Without 1st auxiliary release<br />

A<br />

Voltage – load factor 100%<br />

24 V d.c. B<br />

30 V d.c. C<br />

48 V d.c. D<br />

60 V d.c. E<br />

110 V a.c./d.c. F<br />

230 V a.c./220 V d.c. G<br />

2nd auxiliary release<br />

Without 2nd auxiliary release<br />

A<br />

Voltage – load factor 100%<br />

24 V d.c. B<br />

30 V d.c. C<br />

48 V d.c. D<br />

60 V d.c. E<br />

110 V a.c./d.c. F<br />

230 V a.c./220 V d.c. G<br />

Undervoltage – short-time delayed 80 or 200 ms<br />

24 V d.c. J<br />

30 V d.c. K<br />

48 V d.c. L<br />

60 V d.c. U<br />

110 V a.c./d.c. M<br />

230 V a.c./220 V d.c. N<br />

400 V a.c. P<br />

Undervoltage – delayed 0.2 to 3.2 s<br />

48 V d.c. Q<br />

110 V a.c./d.c. R<br />

230 V a.c./220 V d.c. S<br />

400 V a.c. T<br />

Auxiliary switches<br />

2s + 2r 2<br />

4s + 4r 4<br />

6s + 2r 7<br />

5s + 3r 8<br />

28


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Method of connection<br />

Selected type designation ARION WL1--- Z <br />

Method of connection of a fixed design circuit breaker<br />

- If this method of connection is selected, on the <strong>12</strong>th place of the type designation there must be „2“ (ARION WL1-2-)<br />

Upper terminals Lower terminals For circuit breaker size – rated current Code<br />

rear horizontal connection front connection – one series of holes I-10; I-16; II-20; II25; II-32; III-40 N11<br />

rear vertical connection rear horizontal connection I-10; I-16; II-20; II25; II-32; III-40; III-50 N20<br />

rear horizontal connection rear vertical connection I-10; I-16; II-20; II25; II-32; III-40; III-50 N24<br />

<br />

Method of connection of a circuit breaker of withdrawable design and of withdrawable device<br />

- If this method of connection is selected, on the <strong>12</strong>th place of the type designation there must be „6“ (ARION WL1-6-)<br />

Upper terminals Lower terminals For circuit breaker size – rated current Code<br />

front connection – one series of holes front connection – one series of holes I-10; I-16; II-20; II25; II-32; III-40 P00<br />

front connection – two series of holes front connection – two series of holes I-10; I-16; II-20; II25; II-32; III-40 P01<br />

rear horizontal connection front connection – one series of holes I-10; I-16; II-20; II25; II-32; III-40 P07<br />

rear vertical connection rear horizontal connection I-10; I-16; II-20; II25; II-32; III-40; III-50 P18<br />

flanged connection rear vertical connection I-10; I-16; II-20; II25; II-32; III-40 P19<br />

rear horizontal connection rear vertical connection I-10; I-16; II-20; II25; II-32; III-40; III-50 P23<br />

<br />

Rear horizontal connection<br />

Rear vertical connection<br />

fixed design<br />

Rear vertical connection<br />

withdrawable design<br />

Rear flanged connection<br />

withdrawable design<br />

Front connection<br />

one series of holes<br />

Front connection<br />

two series of holes<br />

<br />

<br />

<br />

<br />

<br />

<br />

Terminal boards of auxiliary circuits<br />

Selected type designation<br />

ARION WL1--- Z <br />

Method of connection of auxiliary circuits of circuit breaker by means of screwless terminals<br />

- tension spring principle (normally the circuit breaker is equipped with screw terminals)<br />

Fixed design of circuit breaker<br />

Withdrawable design of circuit breaker<br />

N61<br />

P61<br />

<br />

29


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Closing release and motor drives with different operating voltage<br />

Selected type designation ARION WL1- - -Z <br />

Closing release<br />

- load factor 100%; if this method of control is selected, there must be „1” set on the 13th place of the type designation<br />

Code<br />

(ARION WL1--1)<br />

24 V d.c. M21<br />

30 V d.c. M22<br />

48 V d.c. M23<br />

60 V d.c. M24<br />

110 V a.c./d.c. M25<br />

230 V a.c./220 V d.c. M26<br />

<br />

Closing releases<br />

- load factor 5% - overexcitation (pull-in time) 25 ÷ 60 ms, max. load time 3 s; if this method of control is selected, there must be „1” set on the 13th place of the type designation<br />

Kód<br />

(ARION WL1--1)<br />

24 ÷ 30 V d.c. M31<br />

48 ÷ 60 V d.c. M33<br />

110 V a.c./d.c. M35<br />

230 V a.c./220 V d.c. M36<br />

<br />

Motor drives<br />

- If this method of control is selected, there must be „1” set on the 13th place of the type designation<br />

Code<br />

(ARION WL1--1)<br />

24 ÷ 30 V d.c. M01<br />

48 ÷ 60 V d.c. M03<br />

110 V a.c./d.c. M05<br />

230 V a.c./220 V d.c. M06<br />

<br />

Opening release<br />

Selected type designation ARION WL1- - -Z <br />

Opening release<br />

- load factor 5% - overexcitation (pull-in time) 25 ÷ 60 ms, max. load time 3 s; if this method of control is selected, there must be „A” on the 14th or 15th position of the type designation<br />

Code<br />

(ARION WL1--A, ARION WL1--A)<br />

24 ÷ 30 V d.c. M41<br />

48 ÷ 60 V d.c. M43<br />

110 V a.c./d.c. M45<br />

230 V a.c./220 V d.c. M46<br />

<br />

30


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Rated voltage 1000 V<br />

Selected type designation ARION WL1--- Z <br />

Rated voltage 1000 V for both AC and DC versions<br />

- If withdrawable circuit breaker and plug-in frame are ordered separately, the complement code „A05” must be stated for both the withdrawable circuit breaker and plug-in frame<br />

- only for circuit breakers with I cu<br />

= 100 kA<br />

- possible also for DC switch-disconnector<br />

Code<br />

Only for circuit breakers and switch-disconnectors of size II and III with I cu<br />

= 100 kA A05 <br />

Rated current modules<br />

Selected type designation ARION WL1--- Z <br />

Rated current modules<br />

- It is possible to order only one module per circuit breaker (not possible for overcurrent release ETU15B)<br />

- standardly delivered rated current module corresponds to the max. rated current of the circuit breaker<br />

Rated current I n<br />

Size I Size II Size III Code<br />

250 A + + – B02<br />

315 A + + – B03<br />

400 A + + – B04<br />

500 A + + – B05<br />

630 A + + – B06<br />

800 A + + – B08<br />

1000 A + + – B10<br />

<strong>12</strong>50 A + + + B<strong>12</strong><br />

1600 A + + + B16<br />

2000 A – + + B20<br />

2500 A – + + B25<br />

3200 A – + + B32<br />

4000 A – – + B40<br />

5000 A – – + B50<br />

6300 A – – + B63<br />

+ can be used, – cannot be used<br />

<br />

Signal switches<br />

Selected type designation ARION WL1--- Z <br />

Signal switches<br />

Code<br />

Signal switch of energy-storing mechanism state – cannot be combined with codes „F01“, „F02“ and „F<strong>12</strong>“ (S21 - 1 make contact) C20 <br />

Signal switch “ready to closing” – cannot be combined with codes „F01“, „F02“ and „F<strong>12</strong>“ (S20 - 1 make contact) C22 <br />

Signal switch for the 1st auxiliary release – cannot be combined with codes „F01“, „02“ and „F<strong>12</strong>“ (S22 - 1 make-and-break contact) C26 <br />

Signal switch for the 2nd auxiliary release – cannot be combined with codes „F01“, „F02“ and „F<strong>12</strong>“ (S23 - 1 make-and-break contact) C27 <br />

Signal switch “switched off by overcurrent release – cannot be combined with codes „F01“, „F02“ and „F<strong>12</strong>“ (S24 - 1 make-and-break contact) K07 <br />

Operating position Test position Disconnected position<br />

Signal switch of position in the plug-in frame 1p 1p 1p R15<br />

Signal switch of position in the plug-in frame 3p 2p 1p R16<br />

<br />

31


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Control presentation<br />

Selected type designation ARION WL1--- Z <br />

Control presentation<br />

Code<br />

Operating cycle counter - mechanical, 5-place - possible only in combination with motor drive C01 <br />

Emergency OFF push-button – mushroom push-button in the place of mechanical button OFF S24 <br />

Switch of the drive of the energy-storing mechanism on the front control panel of the circuit breaker (S<strong>12</strong>)<br />

- only for circuit breaker with motor drive, cannot be combined with codes „C11“, „C<strong>12</strong>“, „C14“ and „C15“ S25<br />

S25<br />

<br />

Electrically ON push-button on the front control panel of the circuit breaker – possible only for circuit breakers with closing release – cannot be combined with codes „F01“, „F02“, „F<strong>12</strong>“ and „S25“<br />

Push-button with sealable cap<br />

Push-button with safety lock CES<br />

Push-button with safety lock IKON<br />

Push-button with cover for a padlock of diameter 6.3 mm – the lock is not included in the scope of delivery<br />

Automatic reset<br />

- automatic reset of the circuit breaker reclosing blocking after its switching off by overcurrent release<br />

C11<br />

C<strong>12</strong><br />

C14<br />

C15<br />

K01<br />

<br />

<br />

Remote reset<br />

- remote reset of the indicating push-button „switched off by overcurrent release“ and remote reset of circuit breaker<br />

reclosing blocking after its switching off by overcurrent release<br />

24 d.c. K10<br />

48 d.c. K11<br />

110 V a.c./d.c. K<strong>12</strong><br />

230 V a.c./220 V d.c. K13<br />

<br />

Data communication and measurement<br />

Selected type designation ARION WL1--- Z <br />

Data communication – circuit breaker must be equipped at least with ETU45B<br />

BSS (Breaker State Sensor) module<br />

Data communication PROFIBUS<br />

- contains COM15 and BSS modules<br />

- If withdrawable circuit breaker and plug-in frame are ordered separately, the complement code „F02” must be stated for both the withdrawable circuit breaker and plug-in frame<br />

- The overcurrent release ETU45B must be set via BDA adapter or via PC equipped with profi bus card and SW ES Switch Power<br />

Data communication MODBUS<br />

- contains COM16 and BSS modules<br />

- If withdrawable circuit breaker and plug-in frame are ordered separately, the complement code „F<strong>12</strong>” must be stated for both the withdrawable circuit breaker and plug-in frame<br />

- The overcurrent release ETU45B must be set via BDA adapter<br />

Code<br />

F01<br />

F02<br />

F<strong>12</strong><br />

<br />

Measuring function<br />

Code<br />

Measuring function Plus (without connection of communication) – for the measuring function, voltage transformers are necessary, see page 40 F05 <br />

Internal current transformer for N conductor<br />

Size I, II, III<br />

- It is only possible for 4-pole circuit breakers with releases ETU27B, ETU55B or ETU76B<br />

Code<br />

F23<br />

<br />

Electronic protection of N conductor<br />

To ensure protection of N conductor at loading of only 1 pole<br />

- It is only possible for 4-pole circuit breakers with releases ETU27B, ETU45B, ETU55B or ETU76B with internal current transformer for N conductor<br />

Code<br />

F30<br />

<br />

32


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Blocking and locking<br />

Selected type designation ARION WL1--- Z <br />

Mechanical interlocking - blocking module with Bowden cable 2 m<br />

- It is possible to block two or three circuit breakers - each must contain mechanical interlocking<br />

- For blocking of three circuit breakers it is necessary to buy one additional Bowden cable to each circuit breaker – see page 41 Code<br />

For fixed design<br />

S55<br />

For withdrawable circuit breaker with withdrawable device<br />

R55<br />

For withdrawable device<br />

For withdrawable circuit breaker<br />

R56<br />

R57<br />

<br />

Locking device against unauthorized closing – for both fixed and withdrawable circuit breaker<br />

- After locking, it is not possible to switch on the circuit breaker mechanically or electrically<br />

- The locking acts only on the given circuit breaker<br />

- Meets the requirements of EN 60 204 for the main switch and EN 60 947-2 for safe disconnection Code<br />

Safety lock CES<br />

S01<br />

Safety lock IKON<br />

S03<br />

Set for locks FORTRESS or CASTELL – preparation for locks; the locks are not included in the delivery; they are ordered directly at the manufacturer<br />

S05<br />

Set for padlocks – the padlock is not included in the delivery<br />

S07<br />

Safety lock RONIS<br />

Safety lock PROFALUX<br />

S08<br />

S09<br />

<br />

Locking device against unauthorized closing for withdrawable circuit breaker<br />

- After locking, it is not possible to switch on the circuit breaker mechanically or electrically<br />

- The locking acts on each circuit breaker inserted into the withdrawable device<br />

- Meets the requirements of EN 60 204 for the main switch and EN 60 947-2 for safe disconnection Code<br />

Safety lock PROFALUX<br />

Safety lock CES<br />

Safety lock RONIS<br />

R60<br />

R61<br />

R68<br />

<br />

Locking device of the hand drive energy-storing mechanism lever<br />

- It is not possible to wind up the circuit breaker manually Code<br />

Set for padlocks – the padlock is not included in the delivery S33 <br />

Locking device against movement of the withdrawable circuit breaker<br />

- prevents from crank withdrawal for shifting Code<br />

Safety lock PROFALUX<br />

S75<br />

Safety lock CES<br />

S71<br />

Safety lock RONIS<br />

S76<br />

<br />

Locking device against shifting of the withdrawable circuit breaker in disconnected position<br />

- Consists of the Bowden cable and the lock in the cubicle door Code<br />

Safety lock PROFALUX<br />

R85<br />

Safety lock CES<br />

R81<br />

Safety lock RONIS<br />

R86<br />

<br />

Blocking device<br />

Code<br />

Blocking device against cubicle door opening: for fixed circuit breaker in ON state S30<br />

for withdrawable circuit breaker in operating position<br />

R30<br />

Blocking device against shifting of the circuit breaker at opened cubicle door<br />

R50<br />

<br />

33


ARION WL - Commercial information<br />

ADDITIONAL ACCESSORIES 3P 4P<br />

Covers, door sealing frame<br />

Selected type designation ARION WL1--- Z <br />

Arc chute cover<br />

Arc chute cover - for withdrawable design; it is installed on the withdrawable device<br />

- not possible for 1000 V design<br />

- not possible for DC design<br />

Code<br />

R10<br />

<br />

Insulation cover<br />

Insulation cover - for withdrawable design; it is installed on the withdrawable device (covers power contacts in the withdrawable device)<br />

- lockable by a padlock (the padlock is not included in the delivery)<br />

Code<br />

R21<br />

<br />

Door sealing frame<br />

Code<br />

Door sealing frame - it is installed on the cubicle door, protection IP41 T40 <br />

34


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Connecting sets – fixed design<br />

- The set contains one terminal with connecting material for terminal mounting on the circuit breaker<br />

- The data are valid for one terminal, if not stated otherwise<br />

- For 3-pole design, 3 terminals are necessary on both upper and lower side; for 4-pole design, 4 terminals on both<br />

upper and lower side<br />

Front connection one series of holes<br />

NSE-01010<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AL01-0AA0 Upper terminal 1.000 1<br />

I Up to 1600 A 3WL9111-0AL02-0AA0 Upper terminal 2.000 1<br />

II Up to 2000 A 3WL9111-0AL03-0AA0 20371 Upper terminal 2.300 1<br />

II Up to 2500 A 3WL9111-0AL04-0AA0 Upper terminal 4.500 1<br />

II Up to 3200 A 3WL9111-0AL05-0AA0 Upper terminal 4.400 1<br />

III Up to 4000 A 3WL9111-0AL06-0AA0 Upper terminal 6.000 1<br />

NSE-01010<br />

I Up to 1000 A 3WL9111-0AL51-0AA0 Lower terminal 1.200 1<br />

I Up to 1600 A 3WL9111-0AL52-0AA0 Lower terminal 1.700 1<br />

II Up to 2000 A 3WL9111-0AL53-0AA0 Lower terminal 2.000 1<br />

II Up to 2500 A 3WL9111-0AL54-0AA0 Lower terminal 3.700 1<br />

II Up to 3200 A 3WL9111-0AL55-0AA0 Lower terminal 3.600 1<br />

III Up to 4000 A 3WL9111-0AL56-0AA0 Lower terminal 6.400 1<br />

Front connection two series of holes<br />

NSE-01011<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AL07-0AA0 19341 Upper terminal 1.000 1<br />

I Up to 1600 A 3WL9111-0AL08-0AA0 19342 Upper terminal 2.000 1<br />

II Up to 2000 A 3WL9111-0AL11-0AA0 19343 Upper terminal 2.300 1<br />

II Up to 2500 A 3WL9111-0AL<strong>12</strong>-0AA0 19344 Upper terminal 4.500 1<br />

II Up to 3200 A 3WL9111-0AL13-0AA0 19345 Upper terminal 4.400 1<br />

III Up to 4000 A 3WL9111-0AL14-0AA0 19532 Upper terminal 6.000 1<br />

NSE-01011<br />

I Up to 1000 A 3WL9111-0AL57-0AA0 19346 Lower terminal 1.200 1<br />

I Up to 1600 A 3WL9111-0AL58-0AA0 19347 Lower terminal 1.700 1<br />

II Up to 2000 A 3WL9111-0AL61-0AA0 19348 Lower terminal 2.000 1<br />

II Up to 2500 A 3WL9111-0AL62-0AA0 19349 Lower terminal 3.700 1<br />

II Up to 3200 A 3WL9111-0AL63-0AA0 19350 Lower terminal 3.600 1<br />

III Up to 4000 A 3WL9111-0AL64-0AA0 19354 Lower terminal 6.400 1<br />

Rear vertical connection<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1600 A 3WL9111-0AM01-0AA0 1) 19351 Upper terminal or lower terminal 0.500 1<br />

II Up to 3200 A 3WL9111-0AM02-0AA0 2) 19352 Upper terminal or lower terminal 1.600 1<br />

III Up to 6300 A 3WL9111-0AM03-0AA0 19355 Upper terminal or lower terminal 5.000 1<br />

1)<br />

– up to (inclusive) 1000 A one terminal is needed per pole, up to (inclusive) 1600 A two terminals are needed per pole<br />

2)<br />

– up to (inclusive) 2500 A one terminal is needed per pole, up to (inclusive) 3200 A two terminals are needed per pole<br />

NSE-010<strong>12</strong><br />

state both type designation and product code, if any<br />

35


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Connecting sets – withdrawable design<br />

- The set contains one terminal with connecting material for terminal mounting on the circuit breaker<br />

- The data are valid for one terminal, if not stated otherwise<br />

- For 3-pole design, 3 terminals are necessary on both upper and lower side; for 4-pole design, 4 terminals on both<br />

upper and lower side<br />

Front connection one series of holes<br />

NSE-01013<br />

Front connection two series of holes<br />

NSE-01014<br />

Supports for front connection with one or two rows of holes<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AN01-0AA0 Upper terminal or lower terminal 1.100 1<br />

I Up to 1600 A 3WL9111-0AN02-0AA0 14462 Upper terminal or lower terminal 1.00 1<br />

II Up to 2000 A 3WL9111-0AN03-0AA0 Upper terminal or lower terminal 1.900 1<br />

II Up to 2500 A 3WL9111-0AN04-0AA0 Upper terminal or lower terminal 3.700 1<br />

II Up to 3200 A 3WL9111-0AN05-0AA0 Upper terminal or lower terminal 3.600 1<br />

III Up to 4000 A 3WL9111-0AN06-0AA0 Upper terminal or lower terminal 6.400 1<br />

- On both upper and lower side it is necessary to use supports „Supports for front connection with one or two rows of holes“<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AN07-0AA0 19353 Upper terminal or lower terminal 1.100 1<br />

I Up to 1600 A 3WL9111-0AN08-0AA0 19354 Upper terminal or lower terminal 1.700 1<br />

II Up to 2000 A 3WL9111-0AN11-0AA0 19355 Upper terminal or lower terminal 1.900 1<br />

II Up to 2500 A 3WL9111-0AN<strong>12</strong>-0AA0 19356 Upper terminal or lower terminal 3.700 1<br />

II Up to 3200 A 3WL9111-0AN13-0AA0 19357 Upper terminal or lower terminal 3.600 1<br />

III Up to 4000 A 3WL9111-0AN14-0AA0 19358 Upper terminal or lower terminal 6.400 1<br />

- On both upper and lower side it is necessary to use supports see „Supports for front connection with one or two rows of holes“<br />

Size Number of poles Type Product code Weight [kg] Packing [pc]<br />

I 3-pole design 3WL9111-0AN41-0AA0 19368 0.800 1<br />

II 3-pole design 3WL9111-0AN42-0AA0 19369 1.200 1<br />

III 3-pole design 3WL9111-0AN43-0AA0 19370 1.200 1<br />

I 4-pole design 3WL9111-0AN44-0AA0 19371 1.200 1<br />

II 4-pole design 3WL9111-0AN45-0AA0 19372 1.200 1<br />

III 4-pole design 3WL9111-0AN46-0AA0 19373 1.200 1<br />

NSE-01017<br />

state both type designation and product code, if any<br />

36


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Withdrawable device, 3-pole, 4-pole, AC<br />

Size Max. rated current 3-pole 3-pole<br />

Front connection one series of holes<br />

I 1000 3WL9211-1AA-A1 3WL9211-1BA-A1<br />

I 1600 3WL9211-2AA-A1 3WL9211-2BA-A1<br />

II 2000 3WL92<strong>12</strong>-3AA-A1 3WL92<strong>12</strong>-3BA-A1<br />

II 2500 3WL92<strong>12</strong>-4AA-A1 3WL92<strong>12</strong>-4BA-A1<br />

II 3200 3WL92<strong>12</strong>-5AA-A1 3WL92<strong>12</strong>-5BA-A1<br />

III 4000 3WL9213-6AA-A1 3WL9213-6BA-A1<br />

Front connection two series of holes<br />

I 1000 3WL9211-1AB-A1 3WL9211-1BB-A1<br />

I 1600 3WL9211-2AB-A1 3WL9211-2BB-A1<br />

II 2000 3WL92<strong>12</strong>-3AB-A1 3WL92<strong>12</strong>-3BB-A1<br />

II 2500 3WL92<strong>12</strong>-4AB-A1 3WL92<strong>12</strong>-4BB-A1<br />

II 3200 3WL92<strong>12</strong>-5AB-A1 3WL92<strong>12</strong>-5BB-A1<br />

III 4000 3WL9213-6AB-A1 3WL9213-6BB-A1<br />

<br />

<br />

Rear horizontal connection<br />

Rear vertical connection<br />

Rear flanged connection<br />

<br />

<br />

<br />

I 1000 3WL9211-1AC-A1 3WL9211-1BC-A1<br />

I 1600 3WL9211-2AC-A1 3WL9211-2BC-A1<br />

II 2000 3WL92<strong>12</strong>-3AC-A1 3WL92<strong>12</strong>-3BC-A1<br />

II 2500 3WL92<strong>12</strong>-4AC-A1 3WL92<strong>12</strong>-4BC-A1<br />

II 3200 3WL92<strong>12</strong>-5AC-A1 3WL92<strong>12</strong>-5BC-A1<br />

III 4000 3WL9213-6AC-A1 3WL9213-6BC-A1<br />

III 5000 3WL9213-7AC-A1 3WL9213-7BC-A1<br />

I 1000 3WL9211-1AD-A1 3WL9211-1BD-A1<br />

I 1600 3WL9211-2AD-A1 3WL9211-2BD-A1<br />

II 2000 3WL92<strong>12</strong>-3AD-A1 3WL92<strong>12</strong>-3BD-A1<br />

II 2500 3WL92<strong>12</strong>-4AD-A1 3WL92<strong>12</strong>-4BD-A1<br />

II 3200 3WL92<strong>12</strong>-5AD-A1 3WL92<strong>12</strong>-5BD-A1<br />

III 4000 3WL9213-6AD-A1 3WL9213-6BD-A1<br />

III 5000 3WL9213-7AD-A1 3WL9213-7BD-A1<br />

III 6300 3WL9213-8AD-A1 3WL9213-8BD-A1<br />

I 1000 3WL9211-1AE-A1 3WL9211-1BE-A1<br />

I 1600 3WL9211-2AE-A1 3WL9211-2BE-A1<br />

II 2000 3WL92<strong>12</strong>-3AE-A1 3WL92<strong>12</strong>-3BE-A1<br />

II 2500 3WL92<strong>12</strong>-4AE-A1 3WL92<strong>12</strong>-4BE-A1<br />

II 3200 3WL92<strong>12</strong>-5AE-A1 3WL92<strong>12</strong>-5BE-A1<br />

III 4000 3WL9213-6AE-A1 3WL9213-6BE-A1<br />

-<br />

Number of connectors of auxiliary circuits<br />

Without connector 0<br />

1 connector 1<br />

2 connector 2<br />

3 connector 3<br />

4 connector 4<br />

Method of connection of conductors of auxiliary circuits<br />

Without connector 0<br />

Screw terminals – standard 1<br />

Spring terminals 2<br />

Position signal switches<br />

Without switches 0<br />

Variant 1 – 3 microswitches 1<br />

Variant 2 – 6 microswitches 2<br />

Insulation cover<br />

No<br />

A<br />

Yes<br />

B<br />

Other accessories of withdrawable device must be ordered by means of complement codes<br />

For weight see page 51<br />

37


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Withdrawable device, 3-pole, 4-pole, DC<br />

Size Max. rated current 3-pole 4-pole<br />

Front connection one series of holes<br />

II 2000 3WL92<strong>12</strong>-3DA-A1 3WL92<strong>12</strong>-3EA-A1<br />

<br />

Front connection two series of holes<br />

II 2000 3WL92<strong>12</strong>-3DB-A1 3WL92<strong>12</strong>-3EB-A1<br />

<br />

Rear horizontal connection<br />

II 2000 3WL92<strong>12</strong>-3DC-A1 3WL92<strong>12</strong>-3EC-A1<br />

II 4000 3WL92<strong>12</strong>-6DC-A1 3WL92<strong>12</strong>-6EC-A1<br />

<br />

Rear vertical connection<br />

II 2000 3WL92<strong>12</strong>-3DD-A1 3WL92<strong>12</strong>-3ED-A1<br />

II 4000 3WL92<strong>12</strong>-6DD-A1 3WL92<strong>12</strong>-6ED-A1<br />

<br />

Rear flanged connection<br />

II 2000 3WL92<strong>12</strong>-3DE-A1 3WL92<strong>12</strong>-3ED-A1<br />

II 4000 3WL92<strong>12</strong>-6DE-A1 3WL92<strong>12</strong>-6EE-A1<br />

<br />

38<br />

-<br />

Number of connectors of auxiliary circuits<br />

Without connector 0<br />

1 connector 1<br />

2 connector 2<br />

3 connector 3<br />

4 connector 4<br />

Method of connection of conductors of auxiliary circuits<br />

Without connector 0<br />

Screw terminals – standard 1<br />

Spring terminals 2<br />

Position signal switches<br />

Without switches 0<br />

Variant 1 – 3 microswitches 1<br />

Variant 2 – 6 microswitches 2<br />

Insulation cover<br />

No<br />

A<br />

Yes<br />

B<br />

Other accessories of withdrawable device must be ordered by means of complement codes<br />

For weight see page 53


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Rated current modules<br />

I n<br />

= 3200 A<br />

<br />

Rated current Type Product code Description Weight [kg] Packing [pc]<br />

250 3WL9111-0AA51-0AA0 for size I, II 1<br />

315 3WL9111-0AA52-0AA0 for size I, II 1<br />

400 3WL9111-0AA53-0AA0 for size I, II 1<br />

500 3WL9111-0AA54-0AA0 for size I, II 1<br />

630 3WL9111-0AA55-0AA0 for size I, II 1<br />

800 3WL9111-0AA56-0AA0 for size I, II 1<br />

1000 3WL9111-0AA57-0AA0 for size I, II 1<br />

<strong>12</strong>50 3WL9111-0AA58-0AA0 for size I, II, III 1<br />

1600 3WL9111-0AA61-0AA0 for size I, II, III 1<br />

2000 3WL9111-0AA62-0AA0 for size II, III 1<br />

2500 3WL9111-0AA63-0AA0 for size II, III 1<br />

3200 3WL9111-0AA64-0AA0 for size II, III 1<br />

4000 3WL9111-0AA65-0AA0 for size III 1<br />

5000 3WL9111-0AA66-0AA0 for size III 1<br />

6300 3WL9111-0AA67-0AA0 for size III 1<br />

- At insertion of the rated current module (rating plug) into the overcurrent release UTU25B, ETU45B, ETU55B or ETU76B, the rated current of the circuit<br />

breaker is changed to the value of the rated current module - rated current can only be decreased<br />

- The rated current module with the rated current of the selected circuit breaker is part of every circuit breaker or overcurrent release<br />

- Not possible for overcurrent release ETU15B<br />

Test device<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AT31-0AA0 19423 Hand test device for function tests of overcurrent releases<br />

1.000<br />

- for overcurrent releases ETU15B to ETU76B<br />

1<br />

3WL9111-0AT44-0AA0<br />

Test device for testing of tripping characteristics<br />

- for overcurrent releases ETU15B to ETU76B<br />

1<br />

CubicleBUS modules and cables<br />

<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AT26-0AA0 17878 Digital output module with rotary switch - relay outputs 0.400 1<br />

3WL9111-0AT25-0AA0 Digital output module with rotary switch - output with optocouplers 0.400 1<br />

3WL9111-0AT20-0AA0<br />

Digital output module, programmable - relay outputs<br />

0.400 1<br />

- it must be programmed<br />

3WL9111-0AT30-0AA0<br />

Digital output module, programmable - output with optocouplers<br />

0.400 1<br />

- it must be programmed<br />

3WL9111-0AT27-0AA0 Digital input module 0.400 1<br />

3WL9111-0AT23-0AA0 Analog output module 0.400 1<br />

3WL9111-0AT21-0AA0 ZSS module - short selectivity control 0.400 1<br />

3WL9111-0BC04-0AA0<br />

Connecting cable for CubicleBUS modules and circuit breakers<br />

1<br />

- for circuit breakers with data communication PROFIBUS - length 20 cm<br />

3WL9111-0BC02-0AA0<br />

Connecting cable for CubicleBUS modules and circuit breakers<br />

1<br />

- for circuit breakers with data communication PROFIBUS - length 1 m<br />

3WL9111-0BC03-0AA0<br />

Connecting cable for CubicleBUS modules and circuit breakers<br />

1<br />

- for circuit breakers with data communication PROFIBUS - length 2 m<br />

3WL9111-0BC05-0AA0<br />

Connecting cable for CubicleBUS modules and circuit breakers<br />

1<br />

- for circuit breakers without data communication PROFIBUS - length 2 m<br />

- Each module is delivered with a 20 cm cable for interconnection of individual modules<br />

- For connection of CubicleBUS modules to the circuit breaker, one connecting cable is necessary (it is not delivered with the modules)<br />

- The circuit breaker must be equipped with at least ETU45B<br />

Voltage sources<br />

Type Product code Voltage Current Weight [kg] Packing [pc]<br />

6EP1332-2BA10 33325 24 V d.c. 2.5 A 0.400 1<br />

6EP1333-2AA01 33505 24 V d.c. 5 A 0.500 1<br />

- The source is necessary for the circuit breakers equipped with data communication or Plus measuring function<br />

state both type designation and product code, if any<br />

39


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Data communication - BDA adapters<br />

Type Product code Name Description Weight [kg] Packing [pc]<br />

3WL9111-0AT28-0AA0 BDA adapter Parameterization, control, diagnostics and testing<br />

of circuit breakers ARION WL by means of PC<br />

- interface RS232<br />

- programmed by means of PC<br />

Internet Explorer + JAVA2 VM 1.4.0-01<br />

- includes cable for interconnection of BDA adapter and<br />

overcurrent release of the circuit breaker (the cable is not<br />

suitable for long-time connection of BDA adapter)<br />

- no other software is needed<br />

- the circuit breaker must be equipped with at least ETU45B<br />

1<br />

<br />

3WL9111-0AT33-0AA0 15968 BDA plus<br />

adapter<br />

Parameterization, control, diagnostics and testing<br />

of circuit breakers ARION WL by means of PC<br />

- interface ETHERNET and RS232<br />

- programmed by means of PC<br />

Internet Explorer + JAVA2 VM 1.4.0-01<br />

- includes cable for interconnection of BDA adapter and<br />

overcurrent release of the circuit breaker (the cable is not<br />

suitable for long-time connection of BDA adapter)<br />

- no other software is needed<br />

- the circuit breaker must be equipped with at least ETU45B<br />

1<br />

3WL9111-0BC20-0AA0<br />

Connecting<br />

cable<br />

Connecting<br />

cable<br />

Connecting cable for BDA adapter and overcurrent release<br />

- length 1 m<br />

1<br />

3WL9111-0BC21-0AA0<br />

For connection of BDA adapter to the circuit breaker<br />

- suitable for long-time connection<br />

- the cable is not necessary, if the circuit breaker is equipped<br />

with data communication PROFIBUS or CubicleBUS modules<br />

1<br />

3ZS2311-0CC10-0YA0<br />

Switch ES<br />

Power<br />

Parameterization software<br />

- parameterization, control, diagnostics and testing of circuit<br />

breakers ARION WL via PROFIBUS<br />

- compatible with WIN 95, WIN 98, WIN NT, WIN 2000, WIN XP<br />

- the circuit breaker must be equipped with data communication<br />

PROFIBUS<br />

- in addition, for PC there must be a PROFIBUS card<br />

1<br />

Voltage transformers<br />

Operating voltage Type Product code Description Weight [kg] Packing [pc]<br />

230 V a.c. 3WL9111-0BB70-0AA0 Accuracy class 0.5 1<br />

380 ÷ 440 V a.c. 3WL9111-0BB68-0AA0 34154 Accuracy class 0.5 1<br />

500 ÷ 690 V a.c. 3WL9111-0BB64-0AA0 Accuracy class 0.5 1<br />

External current transformers for N conductor<br />

<br />

<br />

Circuit breaker size Type Product code Description Weight [kg] Packing [pc]<br />

I 3WL9111-0AA21-0AA0 Without copper clamps 1<br />

II 3WL9111-0AA22-0AA0 20513 Without copper clamps 1<br />

III 3WL9111-0AA23-0AA0 Without copper clamps 1<br />

I 3WL9111-0AA31-0AA0 201<strong>12</strong> Without copper clamps 1<br />

II 3WL9111-0AA32-0AA0 20111 Without copper clamps 1<br />

III 3WL9111-0AA33-0AA0 Without copper clamps 1<br />

In your order always state both type designation and product code, if any<br />

40


ARION WL - Commercial information<br />

SEPARATELY DELIVERED ACCESSORIES 3P 4P<br />

Auxiliary power sources for shunt releases<br />

Bowden cables for mechanical interlocking<br />

Operating voltage Type Product code Description Weight [kg] Packing [pc]<br />

110 V a.c./d.c. 3WL9111-0BA13-0AA0 Enables circuit breaker switching off by shunt 0.500 1<br />

release also at interruption of power supply of<br />

control circuits (max. 5 min)<br />

230 V a.c./220 d.c. 3WL9111-0BA14-0AA0 Enables circuit breaker switching off by shunt 0.500 1<br />

release also at interruption of power supply of<br />

control circuits (max. 5 min)<br />

- operating voltage of the source must be identical to the operating voltage of the shunt release<br />

Length Type Product code Weight [kg] Packing [pc]<br />

2 m 3WL9111-0BB25-0AA0 14620 0.160 1<br />

3 m 3WL9111-0BB26-0AA0 17366 0.250 1<br />

4.5 m 3WL9111-0BB27-0AA0 14733 0.350 1<br />

Sealable covers of overcurrent release<br />

<br />

<br />

Overcurrent release Type Product code Weight [kg] Packing [pc]<br />

ETU15B, ETU25B, ETU27B,<br />

3WL9111-0AT45-0AA0 19421 0.050 1<br />

ETU45B, ETU55B<br />

ETU76B 3WL9111-0AT46-0AA0 19422 0.050 1<br />

<br />

<br />

Door sealing frame<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AP01-0AA0 13459 Protection IP41 0.630 1<br />

<br />

Transparent cover<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AP02-0AA0 20516 Protection IP55<br />

- the cover cannot be used simultaneously with the sealing frame<br />

- the cover can be removed<br />

- the cover can be opened to both sides<br />

1<br />

Arch chute covers for withdrawable device<br />

<br />

Bearing angle<br />

Design, size Type Product code Weight [kg] Packing [pc]<br />

3-pole, size I 3WL9111-0AS32-0AA0 19335 1.830 1<br />

3-pole, size II 3WL9111-0AS36-0AA0 19336 2.600 1<br />

3-pole, size III 3WL9111-0AS38-0AA0 19337 4.050 1<br />

4-pole, size I 3WL9111-0AS42-0AA0 19338 2.340 1<br />

4-pole, size II 3WL9111-0AS44-0AA0 19339 3.300 1<br />

4-pole, size III 3WL9111-0AS46-0AA0 19340 5.210 1<br />

- installation is not possible for 1000 V (code„A05“) and DC switch-disconnectors<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0BB50-0AA0<br />

For installation of fixed circuit breaker on vertical plane,<br />

4.800 1<br />

only for size I and II - contains 2 pieces<br />

<br />

<br />

NSE01028<br />

state both type designation and product code, if any<br />

41


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Connections for withdrawable device - rear vertical connection<br />

<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AN15-0AA0 Upper terminal or lower terminal 0.570 1<br />

I Up to 1600 A 3WL9111-0AN16-0AA0 Upper terminal or lower terminal 0.800 1<br />

II Up to 2000 A 3WL9111-0AN17-0AA0 Upper terminal or lower terminal 1.100 1<br />

II Up to 2500 A 3WL9111-0AN18-0AA0 Upper terminal or lower terminal 1.400 1<br />

II Up to 3200 A 3WL9111-0AN21-0AA0 Upper terminal or lower terminal 2.500 1<br />

III Up to 5000 A 3WL9111-0AN22-0AA0 Upper terminal or lower terminal 6.000 1<br />

III Up to 6300 A 3WL9111-0AN23-0AA0 3 upper terminal or lower terminal 20.000 1<br />

(for 3-pole design)<br />

3WL9111-0AN20-0AA0<br />

4 upper terminals<br />

20.000 1<br />

(for 4-pole design)<br />

3WL9111-0AN10-0AA0<br />

4 lower terminals<br />

(pro 4-pole design)<br />

20.000 1<br />

Connections for withdrawable device - rear horizontal connection<br />

<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AN32-0AA0 Upper terminal or lower terminal 1<br />

I Up to 1600 A 3WL9111-0AN33-0AA0 Upper terminal or lower terminal 1<br />

II Up to 2000 A 3WL9111-0AN34-0AA0 Upper terminal or lower terminal 1<br />

II Up to 2500 A 3WL9111-0AN35-0AA0 Upper terminal or lower terminal 1<br />

II Up to 3200 A 3WL9111-0AN36-0AA0 Upper terminal or lower terminal 1<br />

III Up to 5000 A 3WL9111-0AN37-0AA0 Upper terminal or lower terminal 1<br />

Connections for withdrawable device - flanged connection<br />

<br />

Size Rated current Type Product code Description Weight [kg] Packing [pc]<br />

I Up to 1000 A 3WL9111-0AN24-0AA0 Upper terminal or lower terminal 1<br />

I Up to 1600 A 3WL9111-0AN25-0AA0 Upper terminal or lower terminal 1<br />

II Up to 2000 A 3WL9111-0AN26-0AA0 Upper terminal or lower terminal 1<br />

II Up to 2500 A 3WL9111-0AN27-0AA0 Upper terminal or lower terminal 1<br />

II Up to 3200 A 3WL9111-0AN28-0AA0 Upper terminal or lower terminal 1<br />

III Up to 4000 A 3WL9111-0AN31-0AA0 Upper terminal or lower terminal 1<br />

42


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Overcurrent release<br />

Display<br />

Earth-fault modules<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Name Protective function Type Product code Description Weight [kg] Packing [pc]<br />

ETU15B LI 3WL9311-5AA00-0AA1 1<br />

ETU25B LSI 3WL93<strong>12</strong>-5AA00-0AA1 1<br />

ETU27B LSING 3WL93<strong>12</strong>-7AA00-0AA1 1<br />

ETU45B LSIN(G) 3WL9314-5AA00-0AA1 1<br />

3WL9314-5AA20-0AA1<br />

ETU55B LSIN(G) 3WL9315-5AA00-0AA1 - without measuring function Plus 1<br />

3WL9315-5AA20-0AA1<br />

- with measuring function Plus<br />

ETU76B LSIN(G) 3WL9317-6AA00-0AA1 - without measuring function Plus 1<br />

3WL9317-6AA20-0AA1<br />

- with measuring function Plus<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AT81-0AA0 Display for ETU45B, 4-line LCD 1<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

GFM AT 45B 3WL9111-0AT53-0AA0 Only for ETU45B, signalling and breaking function 1<br />

GFM AT 55B-76B 3WL9111-0AT56-0AA0 Only pro ETU55B and ETU76B, signalling and<br />

breaking function<br />

1<br />

Terminal boards and connectors for connection of auxiliary circuits<br />

3WL9111-0BA01-0AA0<br />

3WL9111-0BA04<br />

<br />

<br />

3WL9111-0BA03-0AA0<br />

<br />

3WL9111-0BA08<br />

<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

Blade contact block 3WL9111-0AB01-0AA0 For circuit breaker with U e<br />

= 690 V 0.100 1<br />

Blade contact block 3WL9111-0AB10-0AA0 For circuit breaker with U e<br />

= 1000 V – including<br />

blade contact block for the circuit breaker<br />

(need not be ordered separately)<br />

– use at configuring of a new circuit breaker<br />

1<br />

Additional (extension)<br />

blade contact block<br />

Terminal boards pro connection<br />

of conductors of aux. circuits<br />

3WL9111-0BA02-0AA0<br />

3WL9111-0AB03-0AA0<br />

3WL9111-0AB04-0AA0<br />

For circuit breaker with U e<br />

= 1000 V (blade<br />

contact block for the circuit breaker must be<br />

ordered separately, unless it is not on the circuit<br />

breaker) – use at circuit breaker reconstruction<br />

from U e<br />

= 690 V to 1000 V<br />

For circuit b. or withdrawable device – screw term.<br />

For circuit b. or withdrawable device – spring term.<br />

1<br />

0.070 1<br />

Sliding contact module 3WL9111-0AB08-0AA0 Only for withdrawable device 0.100 1<br />

Sliding contact module 3WL9111-0AB18-0AA0 Including terminal boards - screw terminals 1<br />

Blanking block 3WL9111-0AB<strong>12</strong>-0AA0 Only for circuit breaker 1<br />

Coding set 3WL9111-0AB07-0AA0 Only for fixed circuit breaker 1<br />

Motor drives<br />

Description Type Product code Weight [kg] Packing [pc]<br />

24 ÷ 30 V d.c. 3WL9111-0AF01-0AA0 1.510 1<br />

48 ÷ 60 V d.c. 3WL9111-0AF02-0AA0 1.510 1<br />

110 V a.c./d.c. 3WL9111-0AF03-0AA0 1.510 1<br />

230 V a.c./220 V d.c. 3WL9111-0AF04-0AA0 1.510 1<br />

<br />

Closing releases/shunt releases<br />

Operating voltage Type Product code Description Weight [kg] Packing [pc]<br />

24 V d.c. 3WL9111-0AD01-0AA0 Load factor 100 % 0.700 1<br />

30 V d.c. 3WL9111-0AD02-0AA0 Load factor 100 % 0.700 1<br />

48 V d.c. 3WL9111-0AD03-0AA0 Load factor 100 % 0.700 1<br />

60 V d.c. 3WL9111-0AD04-0AA0 Load factor 100 % 0.700 1<br />

110 V a.c./d.c. 3WL9111-0AD05-0AA0 Load factor 100 % 0.700 1<br />

230 V a.c./220 V d.c. 3WL9111-0AD06-0AA0 Load factor 100 % 0.700 1<br />

24 V d.c. 3WL9111-0AD11-0AA0 Load factor 5 % 0.700 1<br />

48 V d.c. 3WL9111-0AD<strong>12</strong>-0AA0 Load factor 5 % 0.700 1<br />

110 V a.c./d.c. 3WL9111-0AD13-0AA0 Load factor 5 % 0.700 1<br />

230 V a.c./220 V d.c. 3WL9111-0AD14-0AA0 Load factor 5 % 0.700 1<br />

43


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Undervoltage releases<br />

Auxiliary switches<br />

Operating voltage Type Product code Description Weight [kg] Packing [pc]<br />

24 V d.c. 3WL9111-0AE01-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

30 V d.c. 3WL9111-0AE02-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

48 V d.c. 3WL9111-0AE03-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

60 V d.c. 3WL9111-0AE07-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

110 V a.c./d.c. 3WL9111-0AE04-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

230 V a.c./220 V d.c. 3WL9111-0AE05-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

400 V d.c. 3WL9111-0AE06-0AA0 Short-time delayed 80 or 200 ms 0.730 1<br />

48 V d.c. 3WL9111-0AE11-0AA0 Delay 0.2 ÷ 3.2 s 0.740 1<br />

110 V a.c./d.c. 3WL9111-0AE<strong>12</strong>-0AA0 Delay 0.2 ÷ 3.2 s 0.730 1<br />

230 V a.c./220 V d.c. 3WL9111-0AE13-0AA0 Delay 0.2 ÷ 3.2 s 0.730 1<br />

400 V a.c. 3WL9111-0AE14-0AA0 Delay 0.2 ÷ 3.2 s 0.730 1<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AG01-0AA0 2 make + 2 break 0.180 1<br />

3WL9111-0AG02-0AA0 2 make 0.050 1<br />

3WL9111-0AG03-0AA0 1 make + 1 break 0.050 1<br />

Signal switches, display and control<br />

3WL9111-0AH11-0AA0<br />

<br />

3WL9111-0AH07-0AA0<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

Signal switch<br />

3WL9111-0AH01-0AA0 0.025 1<br />

“ready-to-close”<br />

Signal switch for<br />

1st or 2nd auxiliary release<br />

Signal switch disconnected<br />

by overcurrent release<br />

Signal switch of the state of<br />

energy-storing mechanism<br />

Position signal switches<br />

in withdrawable device<br />

3WL9111-0AH02-0AA0<br />

3WL9111-0AH14-0AA0<br />

3WL9111-0AH08-0AA0<br />

3WL9111-0AH11-0AA0<br />

3WL9111-0AH<strong>12</strong>-0AA0<br />

- cannot be combined with codes „F01“, „F02“<br />

and „F<strong>12</strong>“ - the circuit breaker must be equipped<br />

with connector X7<br />

- cannot be combined with codes „F01“, „F02“<br />

and „F<strong>12</strong>“ - the circuit breaker must be equipped<br />

with connector X7<br />

- cannot be combined with codes „F01“, „F02“<br />

and „F<strong>12</strong>“ - the circuit breaker must be equipped<br />

with connector X7<br />

Variant 1 - 3 microswitches<br />

Variant 2 - 6 microswitches<br />

1<br />

1<br />

0.030 1<br />

0.200 1<br />

Cycle counter 3WL9111-0AH07-0AA0 Possible only in combination with motor drive 0.100 1<br />

3WL9111-0BA72-0AA0<br />

<br />

Electrical ON push-button<br />

- cannot be combined with<br />

codes „F01“, „F02“, „F<strong>12</strong>“ and<br />

„S25“<br />

3WL9111-0AJ02-0AA0<br />

3WL9111-0AJ03-0AA0<br />

3WL9111-0AJ04-0AA0<br />

3WL9111-0AJ05-0AA0<br />

With sealable cap<br />

With safety lock CES<br />

With safety lock BKS<br />

With safety lock IKON<br />

Motor drive switch 3WL9111-0AJ06-0AA0 - cannot be combined with electrical ON<br />

push-button, possible only in combination<br />

with motor drive<br />

Emergency OFF push-button 3WL9111-0BA72-0AA0 Mushroom push-button instead of<br />

mechanical OFF push-button<br />

0.150 1<br />

1<br />

44


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Data communication, measurement<br />

<br />

<br />

<br />

<br />

<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

Data communication<br />

PROFIBUS<br />

3WL9111-0AT<strong>12</strong>-0AA0<br />

Circuit breaker completion with data communication<br />

PROFIBUS, contains COM15 module, BSS module<br />

(Breaker State Sensor), complete set of internal<br />

cables and CubicleBUS cable long 2 m<br />

1<br />

COM15 module 3WL9111-0AT15-0AA0 Data communication module PROFIBUS<br />

1<br />

including CubicleBUS cable long 2 m<br />

BSS module 3WL9111-0AT16-0AA0 BSS module - Breaker State Sensor 1<br />

Measuring function<br />

PLUS<br />

3WL9111-0AT03-0AA0<br />

- the circuit breaker must be equipped at least with ETU45B<br />

Measuring function PLUS module,<br />

without voltage transformers<br />

- the transformers shall be ordered see page 40<br />

1<br />

Internal current transformers for N conductor<br />

<br />

Size Type Product code Description Weight [kg] Packing [pc]<br />

I 3WL9111-0AA11-0AA0 Including set of connecting conductors 1<br />

I 3WL9111-0AA<strong>12</strong>-0AA0 Including set of connecting conductors 1<br />

II 3WL9111-0AA13-0AA0 Including set of connecting conductors 1<br />

EMC filter<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AK32-0AA0<br />

Filter for suppression of interference, contains attenuation (asymmetric) filter<br />

- attenuation in the range 40 kHz ÷ 10 MHz > 40 dB<br />

- application e.g. in IT networks or for frequency converters<br />

0.300 1<br />

Remote reset electromagnet of mechanical indicator of switching off by overcurrent release<br />

Operating voltage Type Product code Description Weight [kg] Packing [pc]<br />

24 V d.c. 3WL9111-0AK03-0AA0<br />

1<br />

48 V d.c. 3WL9111-0AK04-0AA0 Remote reset of the indication push-button<br />

1<br />

„switched off by overcurrent release“<br />

110 V a.c./d.c. 3WL9111-0AK05-0AA0 1<br />

230 V a.c./220 V d.c. 3WL9111-0AK06-0AA0 1<br />

- can be used only in combination with automatic reset<br />

Automatic reset<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0AK01-0AA0<br />

Automatic reset of circuit breaker reclosing blocking<br />

1<br />

after its switching off by overcurrent release<br />

45


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Mechanical interlocking<br />

NSE00989<br />

Locking device<br />

3WL9111-0BA2-0AA0<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9111-0BB21-0AA0 Complete module for fixed circuit breaker (Bowden cable 2 m) 2.320 1<br />

3WL9111-0BB22-0AA0 Module only for the withdrawable device 1<br />

3WL9111-0BB23-0AA0 Module only for the withdrawable circuit breaker 1<br />

3WL9111-0BB24-0AA0<br />

Complete module for withdrawable circuit breaker<br />

2.420 1<br />

and withdrawable device<br />

3WL9111-0BB30-0AA0 Adapter for withdrawable circuit breaker size III 1<br />

3WL9111-0BB25-0AA0 Bowden cable 2 m 0.160 1<br />

3WL9111-0BB26-0AA0 Bowden cable 3 m 0.250 1<br />

3WL9111-0BB27-0AA0 Bowden cable 4.5 m 0.350 1<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

Protective caps against 3WL9111-0BA21-0AA0<br />

Set for padlocks<br />

0.300 1<br />

mechanical On/Off<br />

- the padlock is not included in the delivery<br />

3WL9111-0BA22-0AA0 With safety lock CES 1<br />

3WL9111-0BA24-0AA0 With safety lock IKON 1<br />

<br />

3WL9111-0BA3-0AA0<br />

<br />

3WL9111-0BA5-0AA0<br />

Locking device against<br />

unauthorized closing<br />

3WL9111-0BA31-0AA0<br />

Set for locks FORTREES or CASTELL<br />

0.200 1<br />

- preparation for locks, the locks are not<br />

included in the delivery, they shall be<br />

ordered directly at the manufacturer<br />

3WL9111-0BA33-0AA0 With safety lock RONIS 1<br />

3WL9111-0BA34-0AA0 With safety lock KIRK-Key 1<br />

3WL9111-0BA35-0AA0 With safety lock PROFALUX 1<br />

3WL9111-0BA36-0AA0 With safety lock CES 1<br />

3WL9111-0BA38-0AA0 With safety lock IKON 1<br />

3WL9111-0BA41-0AA0<br />

Set for padlocks<br />

- the padlock is not included in the delivery<br />

1<br />

<br />

3WL9111-0BA71-0AA0<br />

Locking device against<br />

unauthorized closing for<br />

withdrawable circuit breaker<br />

3WL9111-0BA51-0AA0 With safety lock CES 1<br />

3WL9111-0BA53-0AA0 With safety lock IKON 1<br />

3WL9111-0BA57-0AA0 With safety lock KIRK-Key 1<br />

3WL9111-0BA58-0AA0 With safety lock RONIS 1<br />

3WL9111-0BA50-0AA0 With safety lock PROFALUX 1<br />

Locking device of the lever of<br />

energy-storing mechanism<br />

of the hand drive<br />

3WL9111-0BA71-0AA0<br />

Set for padlocks<br />

- the padlock is not included in the delivery<br />

0.080 1<br />

<br />

3WL9111-0BA7-0AA0<br />

<br />

3WL9111-0BA8-0AA0<br />

<br />

Locking device against<br />

shifting of withdrawable<br />

circuit breaker<br />

Locking device against<br />

shifting of circuit breaker<br />

in disconnected position<br />

3WL9111-0BA73-0AA0 With safety lock CES 1<br />

3WL9111-0BA75-0AA0<br />

With safety lock IKON<br />

1<br />

3WL9111-0BA76-0AA0 With safety lock PROFALUX 1<br />

3WL9111-0BA77-0AA0 With safety lock RONIS 1<br />

3WL9111-0BA80-0AA0 With safety lock KIRK-Key 1<br />

3WL9111-0BA81-0AA0 With safety lock CES 1<br />

3WL9111-0BA83-0AA0 With safety lock IKON 1<br />

3WL9111-0BA85-0AA0 With safety lock PROFALUX 1<br />

3WL9111-0BA86-0AA0 With safety lock RONIS 1<br />

3WL9111-0BA87-0AA0<br />

Set for padlocks<br />

- the padlock is not included in the delivery<br />

1<br />

46


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Blocking device<br />

Name Type Product code Description Weight [kg] Packing [pc]<br />

Blocking device against 3WL9111-0BB<strong>12</strong>-0AA0<br />

For fixed circuit breaker, blocking in the ON<br />

1<br />

opening of cubicle door (it can<br />

be bypassed using a tool)<br />

3WL9111-0BB13-0AA0<br />

state of the circuit breaker<br />

For withdrawable circuit breaker, blocking in<br />

operating position of the circuit breaker<br />

1<br />

Blocking device against<br />

circuit breaker shifting at<br />

open cubicle door<br />

3WL9111-0BB15-0AA0 For withdrawable circuit breaker 1<br />

47


ARION WL - Commercial information<br />

ACCESSORIES FOR ADDITIONAL INSTALLATION BY OEZ SERVICE 3P 4P<br />

Insulation cover<br />

Arc chutes<br />

<br />

Number of poles Size Type Product code Weight [kg] Packing [pc]<br />

3 - pole I 3WL9 111-0AP04-0AA0 0.500 1<br />

3 - pole II 3WL9 111-0AP06-0AA0 0.630 1<br />

3 - pole III 3WL9 111-0AP07-0AA0 0.860 1<br />

4 - pole I 3WL9 111-0AP08-0AA0 0.600 1<br />

4 - pole II 3WL9 111-0AP11-0AA0 0.770 1<br />

4 - pole III 3WL9 111-0AP<strong>12</strong>-0AA0 1.070 1<br />

Operating voltage Size Type Product code Weight [kg] Packing [pc]<br />

690 V I 3WL9 111-0AS01-0AA0 1<br />

690 V II 3WL9 111-0AS02-0AA0 1<br />

690 V III 3WL9 111-0AS03-0AA0 1<br />

1000 V II 3WL9 111-0AS05-0AA0 1<br />

1000 V III 3WL9 111-0AS06-0AA0 1<br />

Protection by earthing - contact module for withdrawable circuit breaker<br />

Number of poles Size Type Product code Weight [kg] Packing [pc]<br />

3 - pole I 3WL9 111-0BA05-0AA0 1<br />

3 - pole II 3WL9 111-0BA06-0AA0 1<br />

<br />

3 - pole III 3WL9 111-0BA07-0AA0 1<br />

4 - pole I 3WL9 111-0BA08-0AA0 1<br />

4 - pole II 3WL9 111-0BA04-0AA0 1<br />

4 - pole III 3WL9 111-0BA10-0AA0 1<br />

- contact module making capacity is 30 kA, at use of two modules 60 kA<br />

Protection by earthing - contact module for withdrawable device<br />

Size Type Product code Weight [kg] Packing [pc]<br />

I, II 3WL9 111-0BA01-0AA0 1<br />

III 3WL9 111-0BA02-0AA0 1<br />

<br />

- contact module making capacity is 30 kA, at use of two modules 60 kA<br />

Coding of withdrawable device<br />

Type Product code Description Weight [kg] Packing [pc]<br />

3WL9 111-0AR<strong>12</strong>-0AA0 Code can be set by the customer - 36 coding variants 1<br />

<br />

Set for retrofit from fixed to withdrawable design<br />

Number of poles Size Type Product code Weight [kg] Packing [pc]<br />

3 - pole I 3WL9111-0BC11-0AA0 1<br />

3 - pole II 3WL9111-0BC<strong>12</strong>-0AA0 1<br />

3 - pole III 3WL9111-0BC13-0AA0 1<br />

4 - pole I 3WL9111-0BC14-0AA0 1<br />

4 - pole II 3WL9111-0BC15-0AA0 1<br />

4 - pole III 3WL9111-0BC16-0AA0 1<br />

- Withdrawable device and sliding contacts shall be ordered separately<br />

Main contacts<br />

<br />

Size Rated current Type Product code Weight [kg] Packing [pc]<br />

I Up to 1600 A 3WL9 111-0AM90-0AA0 Y1 1<br />

II Up to 2500 A 3WL9 111-0AM91-0AA0 Y1 1<br />

II Up to 3200 A 3WL9 111-0AM92-0AA0 Y1 1<br />

III Up to 6300 A 3WL9 111-0AM93-0AA0 Y1 1<br />

- In the order it is necessary to specify the serial number of the circuit breaker, the type is changed automatically in the order depending on the serial number<br />

- 3 or 4 pcs are ordered according to the number of poles<br />

48


Air circuit breakers<br />

CONTENT – Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS<br />

- parameters ...............................................................................................................................................................50<br />

- diagram ....................................................................................................................................................................54<br />

- connection ................................................................................................................................................................56<br />

- description ...............................................................................................................................................................58<br />

- dimensions ...............................................................................................................................................................59<br />

WITHDRAWABLE DEVICE<br />

- description ...............................................................................................................................................................71<br />

OVERCURRENT RELEASES<br />

- description ...............................................................................................................................................................73<br />

- overview of parameters ...........................................................................................................................................74<br />

- ETU15B - description, tripping characteristic ............................................................................................................76<br />

- ETU25B - description, tripping characteristic ...........................................................................................................77<br />

- ETU27B - description, tripping characteristic ............................................................................................................78<br />

- ETU45B - description, tripping characteristic ............................................................................................................79<br />

- ETU55B - description, tripping characteristic ............................................................................................................80<br />

- ETU75B - description, tripping characteristic ...........................................................................................................81<br />

EARTH-FAULT PROTECTION MODULE<br />

- description ...............................................................................................................................................................84<br />

MEASUREMENT AND DATA COMMUNICATION<br />

- description ...............................................................................................................................................................85<br />

AUXILIARY SWITCHES, SIGNAL SWITCHES<br />

- description, parameters ...........................................................................................................................................88<br />

SHUNT RELEASES, AUXILIARY POWER SOURCE FOR SHUNT RELEASE<br />

- description, parameters ...........................................................................................................................................89<br />

UNDERVOLTAGE RELEASE<br />

- description, parameters ...........................................................................................................................................89<br />

LOCKING AND BLOCKING DEVICES<br />

- description ................................................................................................................................................................90<br />

DRIVES AND CLOSING RELEASES<br />

- description, parameters ...........................................................................................................................................91<br />

GLOSSARY ................................................................................................................................................................................92<br />

CONTENT – Commercial information<br />

see page 1<br />

49


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P<br />

Parameters<br />

Type ARION WL11... ARION WL<strong>12</strong>... ARION WL13...<br />

Size I II III<br />

Standards EN 60947-2<br />

IEC 60947-2<br />

DIN VDE 0660 Section 101<br />

Certification marks<br />

EN 60947-2<br />

IEC 60947-2<br />

DIN VDE 0660 Section 101<br />

EN 60947-2<br />

IEC 60947-2<br />

DIN VDE 0660 Section 101<br />

Size I<br />

Size II<br />

Size III<br />

Number of poles 3, 4 3, 4 3, 4<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

2500 A<br />

3200 A<br />

4000 A<br />

5000 A<br />

6300 A<br />

690 V a.c.<br />

Rated operating voltage U e<br />

690 V a.c. 690 V a.c.<br />

1000 V a.c. 3) 1000 V a.c. 3)<br />

Rated frequency f n<br />

50/60 Hz 50/60 Hz 50/60 Hz<br />

Rated pulse voltage - main current paths U imp<br />

<strong>12</strong> kV <strong>12</strong> kV <strong>12</strong> kV<br />

- auxiliary circuits 4 kV 4 kV 4 kV<br />

- control circuits 2.5 kV 2.5 kV 2.5 kV<br />

Rated insulation voltage U i<br />

1000 V 1000 V 1000 V<br />

Utilization category (selectivity) B B B<br />

Rated short-time withstand current I cw<br />

See the table on page 51 See the table on page 51 See the table on page 51<br />

Rated short-circuit ultimate breaking capacity I cu<br />

See the table on page 51 See the table on page 51 See the table on page 51<br />

Rated operating short-circuit breaking capacity I cs<br />

100% I cu<br />

100% I cu<br />

100% I cu<br />

Rated short-circuit making capacity I cm<br />

See the table on page 51 See the table on page 51 See the table on page 51<br />

Time to switching off at I cu<br />

50 ms 1) 50 ms 1) 50 ms 1)<br />

Mechanical On time 35 ms 35 ms 35 ms<br />

Mechanical Off time 38 ms 34 ms 34 ms<br />

Power loss at I n<br />

See the table on page 51 See the table on page 51 See the table on page 51<br />

Mechanical endurance - without maintenance 10 000 cycles 10 000 cycles 5 000 cycles<br />

- with maintenance 4) 20 000 cycles 15 000 cycles 10 000 cycles<br />

Electrical endurance - without maintenance (U e<br />

= 1000V) 10 000 cycles 7 500 cycles (1000) 2 000 cycles (1000)<br />

- with maintenance 4) 20 000 cycles 15 000 cycles 10 000 cycles<br />

Switching frequency U e<br />

= 690 V a.c. (1000 V a.c.) 60 cycles/h 60 cycles/h (20) 60 cycles/h (20)<br />

Minimum dwell between circuit breaker switching off by<br />

overcurrent release and subsequent reclosing<br />

80 ms 2) 80 ms 2) 80 ms 2)<br />

Degree of protection<br />

IP20, IP41 with sealing frame, IP55 with transparent cover<br />

Reference ambient temperature 40 °C 40 °C 40 °C<br />

Ambient temperature range<br />

operation - 25 °C ÷ + 70 °C - 25 °C ÷ + 70 °C - 25 °C ÷ + 70 °C<br />

(it is necessary to observe special conditions for LCD) storage - 40 °C ÷ + 70 °C - 40 °C ÷ + 70 °C - 40 °C ÷ + 70 °C<br />

Height above sea level 2000 m 2000 m 2000 m<br />

Climatic resistance IEC 68 section 30-20 IEC 68 section 30-20 IEC 68 section 30-20<br />

Weight m See the table on page 51 See the table on page 51 See the table on page 51<br />

1)<br />

- with ETU15B time to switching off is 85 ms<br />

2)<br />

- only with automatic reset of reclosing blocking<br />

3)<br />

- special design see page 31<br />

4)<br />

- at replacement of main contacts and arc chutes<br />

50


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P<br />

Parameters<br />

Rated short-time withstand current I cw<br />

2)<br />

Size - Type I – ARION WL11… II – ARION WL<strong>12</strong>… III – ARION WL13… 1)<br />

Designation of breaking capacity N S N S H - I n<br />


ARION WL - Technical information<br />

SWITCH-DISCONNECTORS - DC OPERATION 3P 4P<br />

Parameters<br />

Type ARION WL<strong>12</strong>10-8AA... ARION WL<strong>12</strong>20-8AA... ARION WL<strong>12</strong>40-8AA...<br />

Size II II II<br />

Standards EN 60947-3<br />

IEC 60947-3<br />

DIN VDE 0660 Section 101<br />

Certification marks<br />

EN 60947-3<br />

IEC 60947-3<br />

DIN VDE 0660 Section 101<br />

EN 60947-3<br />

IEC 60947-3<br />

DIN VDE 0660 Section 101<br />

Size II<br />

Number of poles 3, 4 3, 4 3, 4<br />

Rated current I n<br />

1000 A 2000 A 4000 A<br />

Rated operating voltage U e<br />

300 V d.c. 1)<br />

600 V d.c. 1)<br />

1000 V d.c. 1) 2) 300 V d.c. 1)<br />

600 V d.c. 1)<br />

1000 V d.c. 1) 2) 300 V d.c. 1)<br />

600 V d.c. 1)<br />

1) 2)<br />

1000 V d.c.<br />

Rated pulse voltage - main current paths <strong>12</strong> kV <strong>12</strong> kV <strong>12</strong> kV<br />

- auxiliary circuits 4 kV 4 kV 4 kV<br />

- control circuits 2.5 kV 2.5 kV 2.5 kV<br />

Rated insulation voltage U i<br />

1000 V 1000 V 1000 V<br />

Rated short-time withstand current I cw<br />

See the table on page 53 See the table on page 53 See the table on page 53<br />

Rated conditional short-circuit current I cc<br />

See the table on page 53 See the table on page 53 See the table on page 53<br />

Mechanical on time 35 ms 35 ms 35 ms<br />

Mechanical off time 34 ms 34 ms 34 ms<br />

Power loss at I n<br />

per 1 pole 280 W 770 W 1640 W<br />

Mechanical endurance - without maintenance 10 000 cycles 10 000 cycles 10 000 cycles<br />

- with maintenance 3) 15 000 cycles 15 000 cycles 15 000 cycles<br />

Electrical endurance - without maintenance (U e<br />

= 1000V) 6000 cycles (1000) 6000 cycles (1000) 4000 cycles (1000)<br />

- with maintenance 3) 15 000 cycles 15 000 cycles 15 000 cycles<br />

Switching frequency U e<br />

= 600 d.c. V (1000 V d.c) 60 cycles/h (20) 60 cycles/h (20) 60 cycles/h (20)<br />

Degree of protection<br />

IP20, IP41 with sealing frame, IP55 with transparent cover<br />

Reference ambient temperature 40 °C 40 °C 40 °C<br />

Ambient temperature range operation - 25 °C ÷ + 70 °C - 25 °C ÷ + 70 °C - 25 °C ÷ + 70 °C<br />

storage - 40 °C ÷ + 70 °C - 40 °C ÷ + 70 °C - 40 °C ÷ + 70 °C<br />

Height above sea level 2000 m 2000 m 2000 m<br />

Climatic resistance IEC 68 Section 30-20 IEC 68 Section 30-20 IEC 68 Section 30-20<br />

Weight See the table on page 53 See the table on page 53 See the table on page 53<br />

1)<br />

- rated operating voltage according to the connection see page 53<br />

2)<br />

- special design see page 31<br />

3)<br />

- at replacement of main contacts and arc chutes<br />

For possible protection of DC circuits, please call technical assistance. See the cover sheet for contact.<br />

52


ARION WL - Technical information<br />

SWITCH-DISCONNECTORS - DC OPERATION 3P 4P<br />

Parameters<br />

Rated short-time withstand current I cw<br />

1)<br />

Operating voltage U e<br />

Type ARION WL<strong>12</strong>10-8AA… ARION WL<strong>12</strong>20-8AA… ARION WL<strong>12</strong>40-8AA…<br />

300 V d.c. 30 kA/1 s 30 kA/1 s 30 kA/1 s<br />

600 V d.c. 25 kA/1 s 25 kA/1 s 25 kA/1 s<br />

1000 V d.c. 20 kA/1 s 20 kA/1 s 20 kA/1 s<br />

1)<br />

- at reverse connection of the switch-disconnector the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Rated conditional short-circuit current I cc<br />

1)<br />

Operating voltage U e<br />

Type ARION WL<strong>12</strong>10-8AA… ARION WL<strong>12</strong>20-8AA… ARION WL<strong>12</strong>40-8AA…<br />

300 V d.c. 30 kA/1 s 30 kA/1 s 30 kA/1 s<br />

600 V d.c. 25 kA/1 s 25 kA/1 s 25 kA/1 s<br />

1000 V d.c. 20 kA/1 s 20 kA/1 s 20 kA/1 s<br />

1)<br />

- at reverse connection of the switch-disconnector the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Weight<br />

Type 3-pole 4-pole<br />

Fixed design<br />

Withdrawable circuit breaker<br />

+ withdrawable device<br />

Fixed design<br />

Withdrawable circuit breaker<br />

+ withdrawable device<br />

ARION WL<strong>12</strong>10-8AA... 56 kg 60 + 31 = 91 kg 67 kg 72 + 37 = 109 kg<br />

ARION WL<strong>12</strong>20-8AA... 56 kg 60 + 31 = 91 kg 67 kg 72 + 37 = 109 kg<br />

ARION WL<strong>12</strong>40-8AA... 64 kg 68 + 45 = 113 kg 77 kg 82 + 54 = 136 kg<br />

Rated current versus ambient temperature<br />

Type 55°C 60°C 70°C<br />

ARION WL<strong>12</strong>10-8AA... 1000 A 1000 A 1000 A<br />

ARION WL<strong>12</strong>20-8AA... 2000 A 2000 A 1950 A<br />

ARION WL<strong>12</strong>40-8AA... 3640 A 3500 A 3250 A<br />

Connection of switch-disconnectors for DC operation according to operating voltage<br />

Rated operating voltage<br />

Recommended number of contacts in series<br />

3-pole switch-disconnectors<br />

Operating current up to 4000 A per current path<br />

4-pole switch-disconnectors<br />

Operating current up to 4000 A per current path<br />

up to 300 V + 10%<br />

1-pole switching,<br />

3 current paths<br />

parallel only with<br />

earthed network<br />

2-pole switching<br />

1-pole switching,<br />

4 current paths parallel only<br />

with earthed network<br />

2-pole switching<br />

2 current paths<br />

parallel<br />

over 300 V + 10%<br />

up to 600 V + 10%<br />

2-pole switching,<br />

only with earthed network<br />

1-pole switching,<br />

2 current paths parallel only<br />

with earthed network<br />

2-pole switching<br />

over 600 V + 10%<br />

up to1000 V + 10%<br />

1-pole switching,<br />

only with earthed network<br />

Connection of the switch-disconnector does not depend on polarity. Connection diagrams can<br />

be changed logically. If parallel or serial connections are made directly on the main leads of the<br />

circuit breaker, the for thermal reasons the circuit breakers can by permanently loaded only by<br />

80% of permissible rated current. if these connections are made at 1 m or more from the main<br />

leads, the circuit breaker can be loaded by full rated current.<br />

2-pole switching,<br />

only with earthed network<br />

Earthed network<br />

Load<br />

53


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTOR 3P 4P<br />

Diagram<br />

Internal<br />

Terminals<br />

External<br />

Remote reset electromagnet F7<br />

Current transformer G, S2<br />

Current transformer G, S1<br />

Current transformer N, S2<br />

Current transformer N, S1<br />

External voltage transformer, node<br />

External voltage transformer, L3<br />

External voltage transformer, L2<br />

External voltage transformer, L1<br />

CubicleBUS +<br />

CubicleBUS –<br />

ETU<br />

X8<br />

14<br />

13<br />

<strong>12</strong><br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

L / L+<br />

N / L−<br />

Jumper, if current transformer N is not connected<br />

L1<br />

L2<br />

L3<br />

- 24 V DC input<br />

+<br />

Terminating resistor, if no CubicleBUS module is connected<br />

(the resistor is included in the delivery)<br />

Signal switch „switched off by overcurrent release” S24<br />

Signalling of energy-storing mechanism state S21<br />

Electrical “ON” push-button on the circuit breaker S10<br />

Signal switch for the first auxiliary release,<br />

S22<br />

Signal switch for the second auxiliary release,<br />

S23<br />

X7<br />

14<br />

13<br />

<strong>12</strong><br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

COM 15<br />

or<br />

COM 16<br />

COM 15 - PROFIBUS data communication module<br />

COM 16 - MODBUS data communication module<br />

L / L+<br />

First auxiliary release F1 - voltage<br />

Auxiliary make contact S1<br />

Auxiliary break contact S1<br />

Closing release Y1<br />

Signal switch „ready-to-close” S20<br />

Auxiliary make contact S2<br />

Auxiliary break contact S2<br />

X6<br />

14<br />

13<br />

<strong>12</strong><br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

L / L+<br />

N / L−<br />

L / L+<br />

N / L−<br />

Electrical “OFF” push-button<br />

Electrical “ON” push-button<br />

Second auxiliary release:<br />

F2 - shunt<br />

or F3 - undervoltage<br />

or F4 - undervoltage with delay<br />

Auxiliary make contact S3 or make S7<br />

Auxiliary break contact S3 or make S7<br />

Auxiliary make contact S4 or make S8<br />

Auxiliary break contact S4 or make S8<br />

Motor drive energy-storing mechanism<br />

Energy-storing mechanism motor drive switch S<strong>12</strong><br />

M<br />

X5<br />

14<br />

13<br />

<strong>12</strong><br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

“Emergency OFF” push-button or jumper - only for undervoltage<br />

release delayed<br />

L / L+<br />

N / L−<br />

L / L+<br />

N / L−<br />

54


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTOR 3P 4P<br />

Diagram<br />

Example of control circuit connection<br />

L1<br />

(L+)<br />

B<br />

OFF<br />

L1<br />

(L+)<br />

ON<br />

-X5.2<br />

-X6.7<br />

-X7.9<br />

-X6.14<br />

-X5.<strong>12</strong><br />

-X6.6<br />

-X7.<strong>12</strong><br />

-X7.14<br />

N<br />

1<br />

3<br />

5<br />

-X6.<strong>12</strong><br />

-X6.10<br />

-X6.4<br />

-X6.2<br />

-X5.10<br />

-X5.8<br />

-X5.6<br />

-X5.4<br />

L<br />

ETU<br />

electrical elektr.<br />

ON ON<br />

-S10<br />

N<br />

S<br />

I<br />

N<br />

G<br />

R<br />

-S11<br />

-F5<br />

QS<br />

electrical mech.<br />

ON ON<br />

mechanical mech.<br />

OFF ON<br />

-S<strong>12</strong><br />

M<br />

P<br />

-Y1<br />

-F1<br />

-F3<br />

U<<br />

-S20<br />

-S24<br />

-T1<br />

-T2<br />

-T3<br />

-T4<br />

-Q1<br />

-S1<br />

-S2<br />

-S3<br />

-S4<br />

NSE0_01558a_oe<br />

N<br />

(L-)<br />

-X5.1<br />

-X6.8<br />

-X6.13<br />

-X5.11<br />

-X6.5<br />

-X7.13<br />

N<br />

(L-)<br />

-X8.9<br />

-X8.10<br />

*<br />

N<br />

2<br />

4<br />

6<br />

-X6.11<br />

-X6.9<br />

-X6.3<br />

-X6.1<br />

-X5.9<br />

-X5.7<br />

-X5.5<br />

-X5.3<br />

Diagram description<br />

* - jumper, if current transformer is not connected<br />

T1, T2, T3 - current transformers<br />

Q1<br />

- main contacts<br />

ETU<br />

- overcurrent release at the circuit breaker, switch-disconnector is without overcurrent release<br />

S1, S2, S3, S4 - auxiliary switches<br />

F1<br />

- 1st auxiliary release – shunt release<br />

F3<br />

- 2nd auxiliary release – undervoltage release<br />

F5<br />

- tripping coil – controlled by overcurrent release<br />

Y1<br />

- closing release<br />

S10<br />

- switch for electrical closing<br />

S<strong>12</strong><br />

- energy-storing mechanism motor drive switch<br />

S20<br />

- signal switch “ready-to-close”<br />

S24<br />

- signal switch „switched off by overcurrent release“ – it can only be at the circuit breaker<br />

P<br />

- energy-storing mechanism<br />

M<br />

- motor<br />

R<br />

- indication and reset push-button on the overcurrent release – signals switching off by overcurrent release<br />

QS<br />

- energy-storing mechanism lever<br />

electrical ON - push-button for electrical ON on the front panel of the circuit breaker<br />

mechanical ON - push-button for mechanical ON<br />

B<br />

- recommended connection of control circuits – not part of the circuit breaker/switch-disconnector<br />

- ON – push-button for electrical remote switching on<br />

- OFF – push-button for electrical remote switching off<br />

55


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Connection and installation<br />

Recommended dimensions of main connections and min. cross sections<br />

Type Dimensions Cu busbars [mm] Minimum cross section [mm 2 ]<br />

ARION WL1106... 1x 60 x 10 600<br />

ARION WL1108... 1x 60 x 10 600<br />

ARION WL1110... 1x 60 x 10 600<br />

ARION WL11<strong>12</strong>... 2x 50 x 8 800<br />

ARION WL1116... 2x 50 x 10 1000<br />

ARION WL<strong>12</strong>08... 1x 80 x 8 500<br />

ARION WL<strong>12</strong><strong>12</strong> ... 2x 80 x 5 800<br />

ARION WL<strong>12</strong>16... 2x 80 x 8 1000<br />

ARION WL<strong>12</strong>20... 4x 80 x 5 1500<br />

ARION WL<strong>12</strong>25... 3x 80 x 8 2000<br />

ARION WL<strong>12</strong>32... 4x 80 x 10 3000<br />

ARION WL1340... 4x 100 x 10 4000<br />

ARION WL1350... 5x <strong>12</strong>0 x 10 6000<br />

ARION WL1363... 6x <strong>12</strong>0 x 10 7200<br />

Main (power) circuit<br />

- is connected by Cu busbars<br />

- to extend connection options, use connecting sets see „Types of main connections“<br />

- reverse connection is possible (inversion of input and output terminals) without<br />

limitation of rated ultimate short-circuit breaking capacity Icu<br />

- we recommend to coat the busbars with paint<br />

- input and output conductors/busbars must be reinforced mechanically to eliminate<br />

transfer of electrodynamic forces into circuit breaker/switch-disconnector at short<br />

circuits see fig.<br />

Rear horizontal connection<br />

Rear vertical connection<br />

Rear flanged connection<br />

Front connection one series of holes<br />

Front connection two series of holes<br />

Types of main connections<br />

Fixed design<br />

<br />

<br />

<br />

<br />

Rear horizontal connection<br />

Front connection one series of<br />

holes - custom delivery<br />

Front connection two series<br />

of holes<br />

Rear vertical connection<br />

Withdrawable design<br />

<br />

<br />

<br />

<br />

<br />

Rear horizontal connection<br />

Front connection one series of<br />

holes - custom delivery<br />

Front connection two series<br />

of holes<br />

Rear vertical connection<br />

Rear flanged connection<br />

- custom delivery<br />

56


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Connection and installation<br />

Terminal boards and connectors for connection of auxiliary circuits<br />

The delivered circuit breaker/switch-disconnector is always equipped with all connectors<br />

and terminal boards for connection of selected auxiliary circuits.<br />

Fixed design<br />

Withdrawable design<br />

or<br />

or<br />

<br />

<br />

<br />

<br />

<br />

Terminal board with screw<br />

terminals for fixed circuit<br />

breaker/withdrawable<br />

device<br />

Blade contact block for fixed/<br />

withdrawable circuit breaker<br />

<br />

Terminal board with spring<br />

terminals for fixed circuit<br />

breaker/withdrawable<br />

device<br />

<br />

Terminal board with screw<br />

terminals for fixed circuit<br />

breaker/withdrawable<br />

device<br />

Terminal board with spring<br />

terminals for fixed circuit<br />

breaker/withdrawable<br />

device<br />

Sliding contact module<br />

for withdrawable device<br />

Blade contact block for fixed/<br />

withdrawable circuit breaker<br />

Connecting cross sections of conductors of auxiliary circuits<br />

Conductor type Terminal type Screw terminals Spring terminals<br />

Cu stranded wire without sleeve connector 2 x 0.5 mm 2 ÷ 2 x 1.5 mm 2 , 1 x 2.5 mm 2 2 x 0.5 mm 2 ÷ 2 x 2.5 mm 2<br />

Cu stranded wire with sleeve connector (DIN 46 228 T.2) 1 x 0.5 mm 2 ÷ 1 x 1.5 mm 2 2 x 0.5 mm 2 ÷ 2 x 1.5 mm 2<br />

Cu stranded wires with double sleeve connector (DIN 46 228 T.2) 2 x 0.5 mm 2 ÷ 2 x 1.5 mm 2 -<br />

57


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Description of circuit breaker, switch-disconnector<br />

Circuit breaker<br />

(28) <br />

(27) <br />

(26) <br />

(25) <br />

(24) <br />

(23) <br />

(22) <br />

(21) <br />

(20) <br />

(19) <br />

(18) <br />

(17) <br />

(16) <br />

Withdrawable device<br />

<br />

(1)<br />

<br />

(2)<br />

(3)<br />

(4)<br />

(5)<br />

(6) <br />

<br />

(7)<br />

(8) <br />

(9)<br />

<br />

(10)<br />

(11) <br />

(<strong>12</strong>)<br />

(13)<br />

<br />

(14)<br />

(15)<br />

1 Arch chutes<br />

2 Transport handle<br />

3 Label for description by the user<br />

4 Optional energy-storing mechanism motor drive switch or<br />

push-button „electrical ON“<br />

5 Label with circuit breaker parameters (rated values)<br />

6 Mechanical indicator of energy-storing mechanism state<br />

7 Push-button „mechanical ON“<br />

8 Circuit breaker rated current value<br />

9 Pictogram of instructions for withdrawable circuit breaker<br />

handling (for withdrawable design only)<br />

10 Operating cycle counter (optional)<br />

11 Energy-storing mechanism hand drive lever<br />

<strong>12</strong> Crank for withdrawing/inserting (for withdrawable design only)<br />

13 Shaft of withdrawable circuit breaker shifting<br />

(for withdrawable design only)<br />

14 Label with data of circuit breaker equipment<br />

15 Hole for protective earthing<br />

16 Indication of circuit breaker position in the withdrawable device<br />

17 Table with data of earth-fault protection<br />

18 Locking device against shifting of withdrawable circuit breaker<br />

(optional)<br />

19 Mechanical unlock of the crank for withdrawing/inserting<br />

(for withdrawable design only)<br />

20 Overcurrent release<br />

21 Rated current module (rating plug)<br />

22 „Mechanical ON“ push-button or mushroom „Emergency OFF“<br />

push-button (optional)<br />

23 Mechanical indicator „ready-to-close“<br />

24 Mechanical indicator of circuit breaker state<br />

25 Mechanical indicator of switching off by overcurrent release<br />

(reset push-button)<br />

26 Locking device against unauthorized closing (optional)<br />

27 Control panel<br />

28 Sliding contact module<br />

(18) <br />

(17) <br />

(16) <br />

(15) <br />

(14) <br />

(13) <br />

(1)<br />

(2)<br />

(3)<br />

(4)<br />

(5)<br />

(6)<br />

(7)<br />

(8)<br />

1 Arc chute cover (optional)<br />

2 Exhaust holes<br />

3 Holes for crane hooks<br />

4 Insulation cover (optional)<br />

5 Insulation cover locking<br />

6 Type label of withdrawable device<br />

7 Disconnecting (break) contacts of main leads<br />

8 Hole for protective earthing - diameter 14 mm<br />

9 Locking device for withdrawing rails<br />

10 Blocking of withdrawal at open cubicle door (optional)<br />

11 Blocking device against cubicle door opening (optional)<br />

<strong>12</strong> Slide in rail<br />

13 Coding of circuit breaker rated current<br />

14 Protection earthing – contact module for withdrawable device<br />

(optional)<br />

15 Coding of withdrawable device (optional)<br />

16 Lever for insulation cover opening (optional)<br />

17 Position signal switches in the withdrawable device (optional)<br />

18 Sliding contact module<br />

(<strong>12</strong>) <br />

(11) <br />

(10) <br />

<br />

(9)<br />

58


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - fixed design<br />

Rear horizontal connection<br />

5) 4)<br />

<br />

<br />

<br />

<br />

60.5<br />

<br />

33.5<br />

<br />

<br />

<br />

<br />

ø13.5<br />

<br />

434<br />

NSE00611<br />

275<br />

439.5 439,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

270 15<br />

300 10<br />

390<br />

541.5<br />

461.5 <br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

327.5<br />

<br />

5) 4)<br />

<br />

ø13.5 <br />

<br />

<br />

270 15<br />

300 10<br />

390<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

NSE00619<br />

b<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection one series of holes<br />

434<br />

NSE00611<br />

275<br />

439.5 439,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

Front connection two series of holes<br />

434<br />

NSE00611<br />

5) 4)<br />

275<br />

439.5 439,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

270 15<br />

300 10<br />

390<br />

Rear vertical connection<br />

5) 4)<br />

434<br />

275<br />

439.5 439,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

267.5 <br />

<strong>12</strong>7.5 <br />

<br />

3)<br />

NSE00611<br />

270 15<br />

300 10<br />

390<br />

ø13.5 <br />

113.5 <br />

<strong>12</strong>8.5<br />

60 90 90 90<br />

4-pole design<br />

1) Installation space for replacement of arc chutes.<br />

2) De-ionization space, space for connection of auxiliary circuits.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) Fastening points for circuit breaker installation.<br />

8) Locking device against unauthorized closing, on the front<br />

control panel.<br />

9) Locking device against mechanical On/Off.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 20<br />

<strong>12</strong>50 ÷ 1600 A 15 15 15<br />

59


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - withdrawable design<br />

Rear horizontal connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<br />

<br />

<br />

<br />

NSE00630<br />

<br />

<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

465.5 465,5<br />

<br />

<br />

<br />

<br />

<br />

<br />

367.5<br />

382.5<br />

<br />

<br />

<br />

<strong>12</strong>1.5<br />

140.5 <br />

327.5<br />

<br />

3)<br />

10)<br />

55<br />

15<br />

90 90 90<br />

10)<br />

<br />

<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

Front connection one series of holes<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

62.5 <br />

<br />

ø13.5 <br />

<br />

<br />

<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

465.5 465,5<br />

<br />

<br />

<br />

169.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection two series of holes<br />

10)<br />

320<br />

270<br />

5)<br />

13<br />

210<br />

300<br />

4)<br />

NSE00621<br />

30<br />

55<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

465.5 465,5<br />

<br />

<br />

<br />

62.5<br />

<br />

<br />

169.5<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 20<br />

<strong>12</strong>50 ÷ 1600 A 15 15 15<br />

60


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - withdrawable design<br />

Rear vertical connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<br />

ø13.5<br />

<br />

NSE00629<br />

b<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3,5 <strong>12</strong>3.5 275<br />

465.5 465,5<br />

267.5 <br />

<strong>12</strong>7.5<br />

<br />

<br />

<br />

<br />

<br />

327.5<br />

3)<br />

15 90 90 90<br />

Rear flanged connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<strong>12</strong>3,5 <strong>12</strong>3.5 275<br />

465.5 465,5<br />

<br />

NSE00631<br />

Ø M <strong>12</strong><br />

282,5<br />

26 33<br />

3)<br />

142,5<br />

55 55 55 55<br />

59 59<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>1<br />

NSE00632<br />

15 90 90 90<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 20<br />

<strong>12</strong>50 ÷ 1600 A 15 15 15<br />

61


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size II - fixed design<br />

Rear horizontal connection<br />

<br />

5)<br />

4)<br />

<br />

<br />

NSE00642<br />

<br />

<br />

<br />

<br />

434<br />

NSE00633<br />

10<br />

270 85<br />

440<br />

570<br />

Front connection one series of holes<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

435.5 435,5<br />

541.5 <br />

461.5<br />

<br />

<br />

<br />

<br />

<br />

5.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

327.5 <br />

<br />

3)<br />

90 130 130 130<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

5)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

434<br />

NSE00633<br />

10<br />

270 85<br />

440<br />

570<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

435.5 435,5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ø13.5 <br />

<br />

Front connection two series of holes<br />

5)<br />

4)<br />

<br />

<br />

<br />

<br />

<br />

434<br />

NSE00633<br />

10<br />

270 85<br />

440<br />

570<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

435.5 435,5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ø13.5 <br />

<br />

Rear vertical connection<br />

5)<br />

4)<br />

<br />

<br />

ø13.5<br />

b<br />

NSE00641<br />

434<br />

NSE00633<br />

10<br />

270 85<br />

440<br />

570<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

435.5 435,5<br />

<br />

134.5<br />

<br />

<br />

<br />

<br />

113.5<br />

<strong>12</strong>8.5<br />

3)<br />

90 130 130 130<br />

4-pole design<br />

1) Installation space for replacement of arc chutes.<br />

2) De-ionization space, space for connection of auxiliary circuits.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) Fastening points for circuit breaker installation.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 2000 A 10 10 20<br />

2500 A 15 15 15<br />

3200 A 30 30 30<br />

62


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size II - withdrawable design<br />

Rear horizontal connection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

465.5 <br />

<br />

<br />

<br />

<br />

<br />

<br />

40.5 <br />

<br />

<br />

367.5<br />

382.5<br />

<br />

<br />

<br />

88.5<br />

<strong>12</strong>1.5 <br />

140.5 <br />

<br />

<br />

327.5 <br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection one series of holes<br />

<br />

<br />

<br />

62.5 <br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

465.5 <br />

<br />

<br />

<br />

<br />

169.5<br />

<br />

<br />

<br />

45.1<br />

<br />

<br />

<br />

<br />

Front connection two series of holes<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

465.5 <br />

<br />

62.5<br />

<br />

<br />

<br />

<br />

<br />

169.5<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 2000 A 10 10 20<br />

2500 A 15 15 15<br />

3200 A 30 30 30<br />

63


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size II - withdrawable design<br />

Rear vertical connection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

b<br />

NSE00651<br />

<br />

<strong>12</strong>3.5 <br />

465.5 <br />

<br />

<br />

<br />

3)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

55 45 130 130 130<br />

Rear flanged connection<br />

<br />

<br />

<br />

NSE00653<br />

Ø M <strong>12</strong><br />

90<br />

40<br />

NSE00654<br />

<br />

26<br />

33<br />

<strong>12</strong>3.5 <br />

465.5 <br />

282.5 282,5<br />

3)<br />

142.5 142,5<br />

59<br />

59<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>1<br />

45 130 130 130<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 2000 A 10 10 20<br />

2500 A 15 15 15<br />

3200 A 30 30 30<br />

64


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size III - fixed design<br />

Rear horizontal connection<br />

NSE00655<br />

5) 4)<br />

<br />

<br />

<br />

<br />

434<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

439<br />

<br />

541.5 <br />

461.5<br />

<br />

<br />

<br />

<br />

327.5<br />

<br />

890<br />

270<br />

680<br />

205<br />

<strong>12</strong><br />

<br />

5.5 <br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection one series of holes<br />

NSE00655<br />

5) 4)<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

434<br />

890<br />

270<br />

680<br />

205<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

439<br />

<strong>12</strong><br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

4-pole design<br />

1) Installation space for replacement of arc chutes.<br />

2) De-ionization space, space for connection of auxiliary circuits.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) Fastening points for circuit breaker installation.<br />

11) Contact area.<br />

65


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size III - fixed design<br />

Front connection two series of holes<br />

NSE00655<br />

5) 4)<br />

<br />

<br />

ø13.5<br />

<br />

<br />

434<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

439<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

890<br />

270<br />

680<br />

205<br />

<strong>12</strong><br />

<br />

<br />

<br />

<br />

<br />

<br />

Rear vertical connection<br />

NSE00655<br />

5) 4)<br />

<br />

<br />

<br />

20<br />

10<br />

NSE00663<br />

434<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

439<br />

330.5 <br />

<br />

94.5 <br />

<br />

<br />

3)<br />

890<br />

270<br />

680<br />

205<br />

<strong>12</strong><br />

ø13.5<br />

<br />

<br />

<br />

<br />

85 210 210 210<br />

4-pole design<br />

1) Installation space for replacement of arc chutes.<br />

2) De-ionization space, space for connection of auxiliary circuits.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) Fastening points for circuit breaker installation.<br />

11) Contact area.<br />

66


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size III - withdrawable design<br />

Rear horizontal connection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

466.5<br />

<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

40.5 <br />

367.5<br />

382.5 <br />

<br />

<br />

<br />

88.5<br />

<strong>12</strong>1.5 <br />

140.5<br />

<br />

<br />

327.5 <br />

<br />

NSE00674<br />

160 160 160 160<br />

57 85 210 210 210<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection one series of holes<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

466.5<br />

<br />

<br />

<br />

<br />

<br />

169.5<br />

62.5<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Front connection two series of holes<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

466.5<br />

<br />

<br />

<br />

<br />

62.5<br />

<br />

<br />

<br />

169.5<br />

<br />

<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

4-pole design<br />

3) Slots (4 mm wide, 5 mm deep) for interphase barriers.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b<br />

up to 4000 A 40 210<br />

5000 A 40 210<br />

6300 A 5 245<br />

67


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size III - withdrawable design<br />

Rear vertical connection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

466.5<br />

<br />

<br />

330.5<br />

94.5 <br />

<strong>12</strong>4.5<br />

ø13.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Rear flanged connection<br />

<br />

<br />

<br />

NSE00675<br />

Ø M <strong>12</strong><br />

26<br />

33<br />

704<br />

160 160 160 160<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>12</strong>3.5 <br />

466.5<br />

<br />

<br />

<strong>12</strong>1<br />

282,5 282.5<br />

142,5 142.5<br />

5<br />

30<br />

57 85 210 210 210<br />

590 800<br />

914<br />

59 59<br />

NSE00676<br />

4-pole design<br />

3) Slots (4 mm wide, 5 mm deep) for interphase barriers.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed cubicle door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b<br />

up to 4000 A 40 210<br />

5000 A 40 210<br />

6300 A 5 245<br />

68


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - accessories<br />

Voltage transformers - 3WL9111-0BB70-0AA0<br />

3WL9111-0BB68-0AA0<br />

3WL9111-0BB64-0AA0<br />

277<br />

<strong>12</strong>5<br />

NSE0_01103a<br />

99<br />

Installation Montá na standardní on DIN lištu rail 35 mm<br />

External current transformer for N conductor with Cu busbars - size I - 3WL9111-0AA31-0AA0<br />

Ø ø13.5 13,5<br />

83<br />

55<br />

15<br />

97<br />

41<br />

130<br />

68<br />

51 44<br />

170<br />

NSE00606<br />

External current transformer for N conductor with Cu busbars - size II - 3WL9111-0AA32-0AA0<br />

Ø ø13.5 13,5<br />

30 30<br />

3x10<br />

50,5 50.5<br />

130<br />

68<br />

51 44<br />

170<br />

NSE00607<br />

90<br />

131<br />

External current transformer for N conductor with Cu busbars - size III - 3WL9111-0AA33-0AA0<br />

Ø ø13.5 13,5<br />

30<br />

30 30<br />

3x10<br />

52<br />

130<br />

68<br />

51 44<br />

170<br />

NSE00608<br />

160<br />

<strong>12</strong>3<br />

External current transformer for N conductor without Cu busbars - size I - 3WL9111-0AA21-0AA0<br />

R13.1<br />

13,1<br />

60<br />

16<br />

8<br />

8,9<br />

8.9<br />

R 22<br />

22<br />

81<br />

96,8<br />

40<br />

96.8<br />

NSE0_01375<br />

36<br />

70<br />

83<br />

18<br />

51<br />

69


ARION WL - Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - accessories<br />

External current transformer for N conductor without Cu busbars - size II - 3WL9111-0AA22-0AA0<br />

65.5<br />

65,5<br />

R 27<br />

54<br />

115<br />

131<br />

NSE0_01376<br />

88<br />

95<br />

113 3<br />

51<br />

External current transformer for N conductor without Cu busbars - size III - 3WL9111-0AA23-0AA0<br />

161<br />

45<br />

3<br />

31<br />

R 15<br />

107<br />

<strong>12</strong>3<br />

NSE0_01377<br />

160<br />

184<br />

51<br />

Cutout in the cubicle door for control panel at use of the sealing frame<br />

! "<br />

5 - $ ?<br />

! <br />

" <br />

ø5.5 # #<br />

4 # 4 #<br />

ø5.5<br />

<br />

# #<br />

! <br />

" <br />

& #<br />

1) Mounting plane<br />

2) Control panel axis<br />

3) 8 mounting holes for the door sealing frame<br />

4) 3 mounting holes for the cubicle door blocking<br />

! # <br />

% #<br />

" <br />

" <br />

& <br />

$ #<br />

ø5.5 # #<br />

65.5 #<br />

<br />

<br />

<br />

" <br />

" <br />

Cutout in the cubicle door for control panel at use of the transparent cover<br />

4xR5<br />

4x 5,5<br />

NSE0_01030a<br />

80<br />

°<br />

295-300<br />

444<br />

341<br />

330<br />

17<br />

Circuit Montání breaker rovina<br />

mounting jistièe plane<br />

149<br />

Circuit Montání breaker rovina mounting jistièe plane<br />

70


ARION WL - Technical information<br />

WITHDRAWABLE DEVICE 3P 4P<br />

Description<br />

Withdrawable circuit breaker/switch-disconnector is intended for<br />

harsh industrial environment, which requires quick replacement<br />

of the circuit breaker, frequent inspections, and visible, galvanic<br />

disconnection of the circuit.<br />

Circuit breaker positions in the withdrawable device<br />

Figure<br />

Position<br />

signalling<br />

Main current<br />

paths<br />

Auxiliary circuits Cubicle door Insulation cover<br />

Position for<br />

maintenance<br />

<br />

<br />

<br />

<br />

<br />

<br />

disconnected disconnected open closed<br />

<br />

<br />

Disconnected<br />

position<br />

<br />

<br />

<br />

<br />

disconnected disconnected closed closed<br />

<br />

<br />

Test position<br />

(Inspection<br />

position)<br />

<br />

<br />

<br />

<br />

<br />

disconnected connected closed closed<br />

<br />

Operating<br />

position<br />

<br />

<br />

connected connected closed open<br />

<br />

<br />

<br />

<br />

Arc chute covers<br />

3WL9111-0AS..-0AA0 or complement code „R10“<br />

Arc chute cover is used for the protection of the switchgear equipment<br />

which is installed directly above the circuit breaker arch chutes. The<br />

cover is optional accessory for the withdrawable device.<br />

3WL111-0AR<strong>12</strong>-0AA0<br />

Withdrawable circuit breaker and withdrawable device can be<br />

optionally equipped with an additional coding device, which is<br />

set according to the circuit breaker equipment. The coding device<br />

enables custom coding of both the circuit breaker and withdrawable<br />

device according to installed equipment. If the frame and the<br />

circuit breaker have different codes, it is not possible to slide the<br />

circuit breaker into the withdrawable device. The coding device has<br />

36 different codes.<br />

Insulation cover<br />

3WL9111-0AP..-0AA0 or complement code „R21“<br />

Insulation cover consists of insulating strips, which cover lamellar<br />

contacts of main current paths in the withdrawable device. The<br />

insulation cover prevents from contact with the live parts of the<br />

device. The insulation strips can be lifted manually from the protective<br />

position by a lever. The insulation strips can be fixed in various<br />

positions by padlocks, which prevent from unauthorized handling.<br />

Coding device according to rated current<br />

Withdrawable circuit breaker and withdrawable device are normally<br />

equipped with coding device according to rated current.<br />

This coding device enables insertion into the withdrawable device<br />

only of the circuit breaker of relevant size, with compatible size of<br />

contact blades of the main current paths.<br />

<br />

<br />

<br />

<br />

<br />

(1) Withdrawable device, left internal side; right side by analogy<br />

(2) Coding pin on the guide rail on the withdrawable device<br />

(3) Guide rail<br />

(4) Withdrawable circuit breaker, right side; left side by analogy<br />

(5) Coding pin in the withdrawable device<br />

<br />

<br />

71


ARION WL - Technical information<br />

WITHDRAWABLE DEVICE 3P 4P<br />

3WL9111-0AH11-0AA0<br />

or complement code<br />

Position signal switches in the withdrawable device<br />

Plug-in can be additionally equipped with position signal switches.<br />

They enable determination of the circuit breaker position in the<br />

frame. Position signal switches are delivered installed on the<br />

bearing plate, with connecting cables long 1.5 m. Two types are<br />

delivered with various number of contacts.<br />

1<br />

3WL9111-0AH<strong>12</strong>-0AA0<br />

or complement code<br />

Number of contacts according to type<br />

Type Position Disconnected Test Operating<br />

3WL9111-0AH11-0AA0<br />

or complement code „R16“<br />

1 make-and-break 1 make-and-break 1 make-and-break<br />

3WL9111-0AH<strong>12</strong>-0AA0<br />

or complement code „R16“<br />

1 make-and-break 2 make-and-break 3 make-and-break<br />

States of position signal switches<br />

Signal switch Contacts Circuit breaker position<br />

Disconnected position Test position Operating position<br />

S30<br />

S31 / S32<br />

S33 / S34 / S35<br />

- contact opened<br />

- contact closed<br />

Parameters of the position signal switches<br />

Rated operating voltage U e<br />

250 V a.c./d.c.<br />

Rated insulation voltage U i<br />

440 V a.c./250 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated operating current I e<br />

AC-<strong>12</strong> 10 A/24 ÷ 440 V<br />

AC-15<br />

4 A/230 V, 3 A/440 V<br />

DC-<strong>12</strong><br />

10 A/24 V, 2.5 A/48 V, 0.2 A/240 V<br />

DC-13<br />

3 A/24 V, 0.1 A/240 V<br />

Protection Fuse Max. PV10 8A gG<br />

Circuit breaker Max. LSN 8C/1<br />

72


ARION WL - Technical information<br />

OVERCURRENT RELEASE 3P 4P<br />

Description<br />

Basic description<br />

The releases are used for protection of transformers, lines,<br />

circuits, motors and other devices such as, for example,<br />

frequency converters etc. For each application it is possible<br />

to select an optimal overcurrent release according to requirements<br />

from the viewpoint of protective and other functions,<br />

e.g. data communication. For more information about data<br />

communication and measurement function see page 85.<br />

Overcurrent releases are electronic and controlled by a microprocessor.<br />

They work independently of the voltage in the<br />

circuit. The releases do not need an external power supply<br />

for their protective function. The power supply is necessary, if<br />

the circuit breaker is equipped with measuring function Plus<br />

or data communication. All releases enable the control of<br />

rated current in the range 0.4 ÷ 1 I n<br />

. Overview of parameters<br />

of overcurrent releases is on page 74. On other pages there is<br />

a description of individual releases including tripping characteristics.<br />

Release models ETU45B and higher enable the<br />

setting of I 4 t = constant The tripping (time-current) characteristic<br />

thus gets near to the fuse time-current characteristic.<br />

This ensures higher degree of selectivity between the circuit<br />

breaker and the fuses. Eventual failure of the microprocessor<br />

is signalled on all releases by red LED.<br />

Display<br />

Overcurrent release ETU45B can be equipped with a 4-line<br />

LCD display. Release ETU76B has an integrated graphic<br />

display. The displays can show, for instance, the values of<br />

measured quantities in a circuit. The parameters of ETU76B<br />

are set by means of the display and push-buttons.<br />

Overcurrent release parameter setting<br />

For overcurrent releases ETU15B to ETU45B, the basic parameters<br />

of protective functions are set by means of rotary<br />

switches. Some other parameters of ETU45B are set only via<br />

data communication. These functions are only accessible if<br />

the circuit breaker is equipped with measuring function Plus<br />

see page 85. ETU55B can be set only via data communication.<br />

Release ETU76B can be set directly by means of push-buttons<br />

and display via menu or also via data communication.<br />

Rated current module<br />

The releases, except ETU15B, contain a „Rated current module”<br />

(rating plug). Normally, each circuit breaker is equipped<br />

with a rated current module of the rating corresponding to<br />

maximum rated current of the circuit breaker. If a lower<br />

rated current of the circuit breaker is required, it is possible<br />

to deliver the circuit breaker with an overcurrent release containing<br />

the rated current module of required value, see page<br />

31. The rated current module can also be replaced additionally<br />

to decrease the circuit breaker rated current, see page<br />

39. The rated current module can be used for permanent<br />

or temporary reduction of the rated current. For example,<br />

in commissioning of a new plant a lower rated current is<br />

needed initially. The rated current control 0.4 ÷ 1 I n<br />

depends<br />

on the rated current module and not on the maximum current<br />

of the circuit breaker.<br />

Example:<br />

Circuit breaker with max. rated current 2500 A with standard<br />

rated current module - setting I r<br />

1000 ÷ 2500 A<br />

Circuit breaker with max. rated current 2500 A and rated<br />

current module with I n<br />

= 1000 A - setting I r<br />

400 ÷ 1000 A<br />

Switchable set of parameters<br />

Overcurrent releases ETU55 and ETU76B allow for setting of<br />

two parameter sets (two various tripping characteristics)<br />

in the memory for protection of two different devices. By<br />

simple switching over between these sets of parameters (for<br />

ETU55B and UTU76B via data communication, for ETU76B<br />

also via the menu of the release), the circuit breaker is ready<br />

to protect other device in 200 ms.<br />

N conductor protection or switching<br />

N conductor protection is ensured by overcurrent releases<br />

ETU27B or higher. For N conductor protection, the 3-pole circuit<br />

breaker must be completed by an external current transformer<br />

for N conductor, see page 40. 4-pole circuit breakers<br />

must be equipped with an internal current transformer for N<br />

conductor, see page 32. For 4-pole circuit breakers without<br />

the internal current transformer for N conductor N conductor<br />

is only switched. For possible setting of N conductor protection<br />

see the table on page 74.<br />

Earth-fault protection<br />

See page 84.<br />

Testing of overcurrent releases and disconnection<br />

signalling<br />

The functionality of an overcurrent release can be tested on<br />

the release itself. Basic test of protective functions of the<br />

release is activated by pressing the „TEST“ key on the release.<br />

Overcurrent releases can also be tested by special testers see<br />

page 39. For more information, please contact OEZ’s technical<br />

support. See the contact at the end of the catalogue. Detailed<br />

information about the overcurrent release testing will<br />

be delivered on request or see „Detailed Instructions for Use“<br />

at www.oez.com. Overcurrent releases can signal a cause of<br />

disconnection by means of LEDs. LEDs are installed directly<br />

on the release. The signalling can be activated by „QUERY“<br />

key. The LED corresponding to the protective function which<br />

caused the circuit breaker disconnection, lights when the key<br />

is pressed. The overcurrent release remembers the cause of<br />

the last disconnection until its memory is cleared by „CLEAR“<br />

key, however maximum for 24 hours.<br />

Tripping characteristics<br />

Each type of the ARION WL release has its own characteristic.<br />

Complete characteristic of a release is created by combining<br />

individual parts of characteristics. Characteristics illustrate<br />

the response of the overcurrent release to current under<br />

the state, when current already passes through the circuit<br />

breaker. If the release is activated immediately after the circuit<br />

breaker closing i.e. when the release has not measured<br />

current, the relevant off-time is extended by up to 15 ms depending<br />

on the value of the current. Time and current tolerances<br />

are specified for the characteristics. The characteristics<br />

are valid at ambient temperature –5 to +55°C. The release<br />

can be operated at –20 to +70°C. For these temperature<br />

there is an extended tolerance range. The circuit breaker<br />

with overcurrent release ETU76B with graphic display can be<br />

operated at temperature up to +55°C. See program Sichr for<br />

visual demonstration of the tripping characteristics.<br />

Reset after circuit breaker switching off by overcurrent<br />

release<br />

After circuit breaker switching off by an overcurrent release,<br />

the release must be reset. It is not possible to switch on the<br />

circuit breaker without the release reset. After the circuit<br />

breaker switching off by overcurrent release, the red indicating<br />

push-button on the release, which is used for mechanical<br />

local signalling of „switched off by overcurrent release“ and<br />

also for local manual reset of the release, slips out.<br />

Automatic reset<br />

The circuit breaker can be equipped with automatic reset<br />

function (complement code „K01“). If the circuit breaker is<br />

equipped with this function, after its switching off by overcurrent<br />

release, the overcurrent release is reset automatically<br />

immediately and the circuit breaker is ready-to-close. The<br />

red indicating push-button remains extended after the<br />

automatic reset. It signals the circuit breaker switching off by<br />

overcurrent release until its manual or remote reset.<br />

Remote reset<br />

The circuit breaker equipped with the automatic reset can be<br />

also equipped with remote reset. The remote reset function<br />

makes it possible to carry out remote electrical reset of the<br />

indicating push-button signalling the switching off by overcurrent<br />

release. It is also possible to perform manual reset of<br />

the indicating push-button.<br />

Overcurrent release sealing<br />

It is possible to put a sealable transparent cover on the overcurrent<br />

release. The elements used for parameter setting are<br />

covered, and thus unauthorized access to parameter setting<br />

is eliminated. The openings in the cover enable access to<br />

query and test push-buttons. There is also a lockable cap,<br />

which prevents from manual reset of the „switched off by<br />

overcurrent release“ indicator.<br />

73


ARION WL - Technical information<br />

OVERCURRENT RELEASES - OVERVIEW OF PARAMETERS 3P 4P<br />

Parameters<br />

Basic functions Overcurrent release type ETU15B ETU25B ETU27B<br />

Overload protection + + +<br />

The function can be switched on and off − − −<br />

Setting range I R<br />

= I n<br />

x ... 0.5-0.6-0.7-0.8-0.9-1 0.4-0.45-0.5-0.55<br />

0.4-0.45-0.5-0.55<br />

0.6- 0.65-0.7-0.8-0.9-1<br />

0.6-0.65-0.7-0.8-0.9-1<br />

L Switchable overload protection (functional dependence I 2 t- or I 4 t) − − −<br />

I R<br />

Setting range of time lag t R<br />

for I 2 t 10 s fixed 10 s fixed 10 s fixed<br />

Setting range of time lag t R<br />

for I 4 t − − −<br />

Thermal memory − − −<br />

Sensitivity to phase failure − at t sd<br />

= 20 ms (M) 1) at t sd<br />

= 20 ms (M) 1)<br />

t R<br />

Protection of N conductor − − +<br />

N The function can be switched on and off − − + (by sliding switch)<br />

Setting range for N conductor I N<br />

= I n<br />

x ... − − 1<br />

Short-time delayed short-circuit protection − + +<br />

The function can be switched on and off − − −<br />

Setting range I = I x ... − 1.25-1.5-2-2.5-3-4-6-8-10-<strong>12</strong> 1.25-1.5-2-2.5-3-4-6-8-10-<strong>12</strong><br />

S<br />

sd n<br />

Setting range of time lag t sd<br />

− 0-M-100-200-300-400 0-M-100-200-300-400<br />

I sd<br />

Switchable short-time delayed short-circuit protection − − −<br />

Setting range of time lag t sd<br />

at I 2 t − − −<br />

t sd<br />

Function ZSS-s (short selectivity control) − − −<br />

Instantaneous short-circuit protection + + +<br />

The function can be switched on and off − − −<br />

I<br />

Setting range I i<br />

= I n<br />

x ... 2-3-4-5-6-7-8 fixed at I i<br />

≥ 20 x I n<br />

, max. 50 kA fixed at I i<br />

≥ 20 x I n<br />

, max. 50 kA<br />

I i<br />

Earth-fault protection − − + fixed integrated<br />

Tripping and alarm signalling function − − −<br />

The tripping function can be switched on and off − − + (by rotary switch)<br />

The alarm signalling function can be switched on and off − − −<br />

G<br />

Measurement of short-circuit current by vectorial addition<br />

of currents by means of internal<br />

− − +<br />

Measurement of short-circuit current by external<br />

current transformer on protective conductor<br />

− − −<br />

Setting range of limit for tripping I g<br />

− − A-B-C-D-E<br />

Setting range of limit for alarm signalling I g<br />

− − −<br />

Setting range of time lag t g<br />

− − 100-200-300-400-500 ms<br />

Switchable function of short-circuit protection (functional dependence I 2 t) − − −<br />

Setting range of time lag t g<br />

at I 2 t − − −<br />

Function ZSS-g (short selectivity control) − − −<br />

Switchable parameter sets − − −<br />

LCD display Alphanumeric, 4-line − − −<br />

Graphic − − −<br />

Data communication Integrated CubicleBUS − − −<br />

Possible communication via PROFIBUS protocol − − −<br />

Possible communication via MODBUS protocol − − −<br />

Measuring function Measuring function Plus − − −<br />

LED signalling active overcurrent release + + +<br />

alarm signalling + + +<br />

faulty ETU + + +<br />

switching off by function L − + +<br />

switching off by function S − + +<br />

switching off by function I − + +<br />

switching off by function N − − +<br />

switching off by function G − − +<br />

G - alarm signalling − − −<br />

switching off by extended protective function − − −<br />

communication − − −<br />

Reporting by signal contacts via external CubicleBUS modules (optocouplers or relays)<br />

alarm: overload − − −<br />

load reduction, load connection − − −<br />

load reduction, load connection − − −<br />

alarm: high temperature − − −<br />

phase asymmetry − − −<br />

instantaneous disconnection at short circuit − − −<br />

short-time delayed disconnection at short circuit − − −<br />

tripping from overload − − −<br />

tripping from overload of N conductor − − −<br />

earth-fault tripping − − −<br />

alarm: earth fault − − −<br />

auxiliary relay − − −<br />

faulty ETU − − −<br />

− the function is unavailable; + the function is available; the function is optional<br />

1)<br />

- M = motor protection<br />

74


ARION WL - Technical information<br />

OVERCURRENT RELEASES - OVERVIEW OF PARAMETERS 3P 4P<br />

Parameters<br />

Basic functions ETU45B ETU55B ETU76B<br />

Overload protection + + +<br />

The function can be switched on and off − + (On/Off by means of data communication) +<br />

Setting range I R<br />

= I n<br />

x ... 0.4-0.45-0.5-0.55<br />

0.6-0.65-0.7-0.8-0.9-1<br />

0.4 ÷1 2) 0.4 ÷ 1 2)<br />

Switchable overload protection (functional dependence I 2 t or I 4 t) + (by sliding switch) + (On/Off by means of data communication) +<br />

Setting range of time lag t R<br />

pro I 2 t 2-3-5-5.5-8-10-14-17-21-25-30 s 2 ÷ 30 s 2) 2 ÷ 30 s 2)<br />

Setting range of time lag t R<br />

pro I 4 t 1-2-3-4-5 s 1-2-3-4-5 s 1-2-3-4-5 s<br />

Thermal memory + (On/Off by sliding switch) + (On/Off by means of data communication) 2) + (by means of menu/data communication)<br />

Sensitivity to phase failure at t sd<br />

= 20 ms (M) 1) + (On/Off by means of data communication) + (by means of menu/data communication)<br />

Protection of N conductor + + +<br />

The function can be switched on and off + by sliding switch + (by means of data communication) + (by means of menu/data communication)<br />

Setting range for N conductor I N<br />

= I n<br />

x ... 0.5 ÷ 1 0.5 ÷ 2 2) 0.5 ÷ 2 2)<br />

Short-time delayed short-circuit protection + + +<br />

The function can be switched on and off + (by rotary switch) + (by means of data communication) + (by means of menu/data communication)<br />

Setting range of I sd<br />

= I n<br />

x ... 1.25-1.5-2-2.5-3-4-6-8-10-<strong>12</strong> 1.25 ÷ 0.8 x I 2) cw<br />

1.25 ÷ 0.8 x I 2)<br />

cw<br />

Setting range of time l ag<br />

t sd<br />

M-100-200-300-400 ms M- 80 ÷ 4000 ms 2) M- 80 ÷ 4000 ms 2)<br />

Switchable short-time delayed short-circuit protection (functional dependence I 2 t) + (by rotary switch) + (by means of data communication) + (by means of menu/data communication)<br />

Setting range of time t sd<br />

at I 2 t 100-200-300-400 ms 100 ÷ 400 ms 2) 100 ÷ 400 ms 2)<br />

Function ZSS-s (short selectivity control) by means of CubicleBUS by means of CubicleBUS by means of CubicleBUS<br />

Instantaneous short-circuit protection + + +<br />

The function can be switched on and off + (by rotary switch) + (by means of data communication) + (by means of menu/data communication)<br />

Setting range of I i<br />

= I n<br />

x ... 1.5-2.2-3-4-6-8-10-<strong>12</strong>-0.8 × I cs<br />

2)<br />

1.5 x I n<br />

÷ 0.8 × I cs<br />

1.5 x I n<br />

÷ 0.8 × I 2)<br />

cs<br />

Earth-fault protection <br />

Tripping and alarm signalling function + + (by means of data communication) +<br />

The tripping function can be switched on and off + (by rotary switch) + (by means of data communication) + (by means of menu/data communication)<br />

The alarm signalling function can be switched on and off − + (by means of data communication) + (by means of menu/data communication)<br />

Measurement of short-circuit current by vectorial addition of currents by<br />

means of internal or external current transformer on N conductor<br />

+ + +<br />

Measurement of short-circuit current by external current transformer on<br />

protective conductor<br />

+ + +<br />

Setting range of limit for tripping I g<br />

A-B-C-D-E A-B-C-D-E A-B-C-D-E<br />

Setting range of limit for alarm signalling I g<br />

A-B-C-D-E A-B-C-D-E A-B-C-D-E<br />

Setting range of time t g<br />

100-200-300-400-500 ms 100 ÷ 500 ms 2) 100 ÷ 500 ms 2)<br />

Switchable function of short-circuit protection (functional dependence I 2 t) + + +<br />

Setting range of time t g<br />

at I 2 t 100-200-300-400-500 ms 100 ÷ 500 ms 2) 100 ÷ 500 ms 2)<br />

Function ZSS-g (short selectivity control) by means of CubicleBUS module by means of CubicleBUS module by means of CubicleBUS module<br />

Switchable parameter sets − + +<br />

LCD display Alphanumeric, 4-line + − −<br />

Graphic − − +<br />

Data communication Integrated CubicleBUS + + +<br />

Possible communication via PROFIBUS-DP <br />

Possible communication via MODBUS <br />

Measuring function Measuring function Plus + + +<br />

LED signalling active overcurrent release + + +<br />

alarm signalling + + +<br />

faulty ETU + + +<br />

switching off by function L + + +<br />

switching off by function S + + +<br />

switching off by function I + + +<br />

switching off by function N + + +<br />

switching off by function G + (only with earth-fault protection module) + (only with earth-fault protection module) + (only with earth-fault protection module)<br />

G - alarm signalling + (only with earth-fault protection module) + (only with earth-fault protection module) + (only with earth-fault protection module)<br />

switching off by extended protective function + + +<br />

data communication + + +<br />

Reporting by signal contacts via external CubicleBUS modules (optocouplers or relays)<br />

alarm: overload + + +<br />

load reduction, load connection + + +<br />

load reduction, load connection + + +<br />

alarm: high temperature + + +<br />

phase asymmetry + + +<br />

instantaneous disconnection at short circuit + + +<br />

short-time delayed disconnection at short circuit + + +<br />

tripping from overload + + +<br />

tripping from overload of N conductor + + +<br />

earth-fault tripping + (only with earth-fault protection module) + (only with earth-fault protection module) + (only with earth-fault protection module)<br />

alarm: earth fault + (only with earth-fault protection module) + (only with earth-fault protection module) + (only with earth-fault protection module)<br />

auxiliary relay + + +<br />

faulty ETU + + +<br />

2)<br />

- value setting step: Range 0 ÷ 1 1 ÷ 100 100 ÷ 500 500 ÷ 1000 1000 ÷ 1600 1600 ÷ 10000 10000 ÷ max<br />

Step 0.1 1 5 10 50 100 1000<br />

75


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU15B 3P 4P<br />

Description<br />

Use<br />

Simple protection of installations in buildings and protection of<br />

equipment without time selectivity up to 3200 A.<br />

Properties<br />

adjustable overload protection with characteristic I 2 t<br />

with fixed delay t R<br />

= 10 s at 6 × I R<br />

Mechanical reset<br />

of reclosing<br />

blocking<br />

Option: safety lock,<br />

prevents from pressing<br />

of reset push-button after<br />

switching off<br />

by overcurrent<br />

instantaneous short-circuit protection in the range 2 ... 8 × I n<br />

protective function setting by rotary switch.<br />

For other technical data see the table on page 74<br />

Function<br />

Signalling: overcurrent<br />

release activated’<br />

Alarm signalling: overload<br />

<br />

Signalling: faulty<br />

overcurrent release<br />

Rotary switch:<br />

setting of limit of<br />

switching off by overcurrent<br />

Rotary switch:<br />

setting of limit<br />

of instantaneous tripping<br />

at short circuit<br />

Sealing lug<br />

Tripping characteristic<br />

10000<br />

1000<br />

R min<br />

. .<br />

R max<br />

NSE0_01527<br />

<br />

Test connector<br />

100<br />

10<br />

1<br />

i min<br />

i max<br />

0,1 .<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

Tolerance at set current:<br />

L: tripping between 1.05 and 1.2 I R<br />

I: - 0 %, +20 %<br />

Tripping time tolerance:<br />

L: - 20 %, + 0 % for characteristic I 2 t<br />

I: < 50 ms<br />

76


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU25B 3P 4P<br />

Description<br />

Use<br />

Classical protection of building installations, motors and<br />

equipment with time selectivity up to 6300 A.<br />

Properties<br />

adjustable overload protection with characteristic I 2 t<br />

with fixed delay t R<br />

= 10 s at 6 × I R<br />

short-time delayed short-circuit protection, adjustable to<br />

1.25 ... <strong>12</strong>× I n<br />

and<br />

instantaneous short-circuit protection set to 20 × I n<br />

, max. 50 kA<br />

overload signalling<br />

LED signalling of tripping cause<br />

release testing function<br />

protective function setting by rotary switch<br />

For other technical data see the table on page 74<br />

Function<br />

I R<br />

Mechanical reset<br />

of reclosing<br />

blocking<br />

Signalling: overcurrent<br />

release activated<br />

Alarm signalling: overload<br />

Rated current module<br />

Rotary switch: setting of limit<br />

of switching off by overcurrent<br />

Rotary switch: setting of<br />

short-time delayed<br />

short-circuit protection<br />

Fixed instantaneous<br />

short-circuit protection<br />

<br />

<br />

Option: safety lock,<br />

prevents from pressing<br />

of reset push-button after<br />

switching off<br />

by overcurrent<br />

Signalling: faulty<br />

overcurrent release<br />

Signalling of release<br />

tripping cause<br />

Rotary switch:<br />

setting of tripping delay<br />

at short circuit<br />

Sealing lug<br />

I sd<br />

t sd<br />

Query push-button<br />

Test push-button<br />

<br />

<br />

Reset push-button<br />

Test connector<br />

Tripping characteristic<br />

10000<br />

R min<br />

1000 0,4 . ... 1,0 . x n<br />

R max<br />

NSE0_01520<br />

100<br />

10<br />

1<br />

sd min<br />

sd max<br />

1,25 . ... <strong>12</strong> x n<br />

0 ... 0,4 . s<br />

0,1<br />

i i > 20 x n<br />

max. 50 kA<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

Tolerance at set current:<br />

L: - 20 %, + 0 % for characteristic I R<br />

S: - 0 %, +20 %<br />

I: - 0 %, +20 %<br />

Tripping time tolerance:<br />

L: - 20 %, + 0 % for characteristic I 2 t<br />

S: - 0 %, + 60 ms or –0 %, +10% for characteristic with fixed delay<br />

I: < 50 ms<br />

77


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU27B 3P 4P<br />

Description<br />

Use<br />

Classical protection of building installations, motors and equipment<br />

with time selectivity up to 6300 A. The release has fixed integrated<br />

earth-fault protection module.<br />

Properties<br />

adjustable overload protection with characteristic I 2 t<br />

with fixed delay t R<br />

= 10 s at 6 × I R<br />

short-time delayed short-circuit protection, adjustable to<br />

1.25 ... <strong>12</strong>× I n<br />

instantaneous short-circuit protection set to 20 × I n<br />

, max. 50 kA<br />

overload signalling<br />

LED signalling of tripping cause<br />

release testing function<br />

protective function setting by rotary or sliding switches<br />

possible protection of N conductor<br />

fixed integrated earth fault module - calculation of<br />

earth current from vector sum of individual currents<br />

For other technical data see the table on page 74<br />

Function<br />

Mechanical reset<br />

of reclosing<br />

blocking<br />

Signalling: overcurrent<br />

release activated<br />

Alarm signalling:<br />

overload<br />

Rated current module<br />

Rotary switch: setting of limit<br />

of switching off by overcurrent<br />

Rotary switch: setting of<br />

short-time delayed<br />

short-circuit protection<br />

Fixed instantaneous<br />

short-circuit protection<br />

Rotary switch: setting of<br />

earth-fault protection<br />

Query push-button<br />

Test push-button<br />

<br />

<br />

<br />

<br />

<br />

<br />

Option: safety lock,<br />

prevents from pressing<br />

of reset<br />

push-button after switching<br />

off by overcurrent<br />

Protection of N conductor:<br />

On/Off<br />

Signalling: faulty<br />

overcurrent release<br />

Signalling of release<br />

tripping cause<br />

Rotary switch:<br />

setting of tripping delay<br />

at short circuit<br />

Sealing lug<br />

Rotary switch:<br />

setting of delay of protection<br />

at earth fault<br />

Reset push-button<br />

Test connector<br />

Tripping characteristic<br />

Function LSI<br />

Function G<br />

10000<br />

1000<br />

R min<br />

0,4 . ... 1,0 . x n<br />

R max<br />

N<br />

NSE0_01519<br />

10000<br />

1000<br />

NSE0_01521<br />

100<br />

100<br />

10<br />

10<br />

g min<br />

g max<br />

1<br />

sd min<br />

sd max<br />

1,25 . ... <strong>12</strong> x n<br />

0 ... 0,4 . s<br />

0,1 .<br />

i i > 20 x n<br />

max. 50 kA<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

100 ... <strong>12</strong>00 A 1)<br />

1<br />

g max<br />

0,1 . ... 0,5 . s<br />

0,1 .<br />

g min<br />

0,01 .<br />

100 1000 10000 100000<br />

A<br />

Tolerance at set current:<br />

L: tripping between 1.05 and 1.2 x I R<br />

S: - 0 %, +20 %<br />

I: - 0 %, +20 %<br />

G: - 0 %, +20 %<br />

1) Size Velikost I and II: 100 ... <strong>12</strong>00 A<br />

Size Velikost III: 400 ... <strong>12</strong>00 A.<br />

Tripping time tolerance:<br />

L: - 20 %, + 0 % for characteristic I 2 t<br />

S: - 0 %, + 60 ms or –0 %, +10 % for characteristics with fixed delay<br />

I: < 50 ms<br />

G: - 0 ms, + 60 ms or –0 %, +10 % for characteristics with fixed delay<br />

78


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU45B 3P 4P<br />

Description<br />

Use<br />

Budget-priced universal release for intelligent buildings and for all<br />

industrial applications.<br />

Properties<br />

adjustable overload protection with characteristic I 2 t or I 4 t<br />

with fixed delay t R<br />

= 10 s at 6 × I R<br />

short-time delayed short-circuit protection, adjustable to<br />

1.25 ... <strong>12</strong>× I n<br />

instantaneous short-circuit protection set to 20 × I n<br />

, max. 50 kA<br />

overload signalling<br />

LED signalling of tripping cause<br />

release testing function<br />

adjustable delay class for overload protection<br />

switchable characteristics I 2 t and I 4 t in overload area and in the<br />

area of short-time delayed short-circuit protection for better<br />

current selectivity with assigned fuses or circuit breakers<br />

thermal memory, which is used for protection at the circuit<br />

breaker reclosing after switching off by overload - it can be disabled<br />

possible protection of N conductor (separately adjustable)<br />

optional earth-fault protection module with separately<br />

adjustable alarm signalling and tripping functions<br />

possible connection of data communication and measuring<br />

function Plus<br />

optional high contract display with possibility of angle setting<br />

for better visibility<br />

protective function setting by rotary or sliding switches<br />

For other technical data see the table on page 74<br />

Mechanical reset of<br />

reclosing blocking<br />

Scrolling up<br />

Signalling: overcurrent<br />

release activated<br />

Alarm signalling:<br />

overload<br />

COMMUNICATION<br />

EXTENSION F.<br />

Rated current module<br />

Rotary switch: setting If limit <br />

of switching off by overcurrent<br />

Rotary switch: setting<br />

of short-time delayed<br />

short-circuit protection<br />

Rotary switch: setting<br />

of limit of instantaneous<br />

short-circuit protection <br />

Earth fault measurement switch<br />

Rotary switch: setting<br />

<br />

of limit of earth<br />

fault protection<br />

<br />

Rotary switch: setting of limit<br />

<br />

of earth fault alarm<br />

Test push-button<br />

Query push-button<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Option: safety lock, prevents<br />

from pressing of reset<br />

push-button after switching<br />

off by overcurrent<br />

Optional alphanumeric display<br />

Scrolling down<br />

Signalling: faulty<br />

overcurrent release<br />

Thermal memory: On/Off<br />

Protection of N conductor: On/Off<br />

Setting of overload limit<br />

of N conductor<br />

Switching of overload<br />

characteristics I 2 t/I 4 t<br />

Rotary switch: setting of<br />

tripping delay at overload<br />

Rotary switch: setting of<br />

tripping delay at short circuit<br />

Tripping cause signalling<br />

Sealing lug<br />

Optional earth-fault protection module<br />

Alarm signalling: earth fault<br />

Signalling: tripping<br />

by earth fault<br />

Rotary switch: setting of delay<br />

of earth-fault protection - t g<br />

/I 2 t g<br />

Reset push-button<br />

Test connector<br />

Function<br />

79


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU45B 3P 4P<br />

Tripping characteristic<br />

Function L<br />

Function S<br />

10000<br />

1000<br />

R<br />

0,4 . ... 1,0 . x n<br />

4 = const<br />

NSE0_01522<br />

10000<br />

1000<br />

sd<br />

NSE0_01523<br />

100<br />

2 = const<br />

100<br />

.<br />

1,25 ... <strong>12</strong> x n<br />

2 sd = const<br />

2 sd = const<br />

10<br />

1<br />

R<br />

2 ... 30 for 2<br />

1 ... 5 for 4<br />

10<br />

1<br />

0,1 .<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

sd = const 0,1 . ... 0,4 . s<br />

0,1<br />

0,02 . ... 0,4 . s<br />

0,01<br />

0,1 1 10 100<br />

/ n<br />

Function I<br />

Function G<br />

10000<br />

1000<br />

NSE0_01524<br />

10000<br />

1000<br />

NSE0_01525<br />

100<br />

100<br />

g<br />

10<br />

10<br />

1<br />

0,1 .<br />

. .<br />

i<br />

1,5 x n ... 0,8 x cs<br />

0,01<br />

1<br />

0,1 .<br />

100 ... <strong>12</strong>00 A 1) A<br />

g 0,1 . ... 0,5 . s<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

.<br />

100 1000 10000 100000<br />

1) Size Velikost I and II : 100 ... <strong>12</strong>00 A<br />

Size Velikost III : 400 ... <strong>12</strong>00 A<br />

Tolerance at set current:<br />

L: tripping between 1.05 and 1.2 x I R<br />

S: - 0 %, +20 %<br />

I: - 0 %, +20 %<br />

G: - 0 %, +20 %<br />

Tripping time tolerance:<br />

L: - 20 %, + 0 % for characteristic I 2 t<br />

S: - 0 %, + 60 ms or –0 %, +10% for characteristics with fixed delay<br />

I: < 50 ms<br />

G: - 0 ms, + 60 ms or –0 %, +10% for characteristics with fixed delay<br />

80


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU55B 3P 4P<br />

Description<br />

Use<br />

Releases for special safety requirements for adjustability with<br />

exclusively external parameterization. For protection of generators<br />

and motors, for industrial applications.<br />

Mechanical reset of<br />

reclosing blocking<br />

Option: safety lock, prevents<br />

from pressing of reset<br />

push-button after switching<br />

off by overcurrent<br />

Properties<br />

adjustable overload protection with characteristic I 2 t or I 4 t<br />

with fixed delay t R<br />

= 10 s at 6 × I R<br />

short-time delayed short-circuit protection, adjustable to<br />

1.25 ... <strong>12</strong>× I n<br />

and<br />

instantaneous short-circuit protection set to 20 × I n<br />

, max. 50 kA<br />

overload signalling<br />

LED signalling of tripping cause<br />

release testing function<br />

protective function setting by rotary switch<br />

adjustable delay class for overload protection<br />

switchable characteristics I 2 t and I 4 t in overload area and in<br />

the area of short-time delayed short-circuit protection for better<br />

current selectivity with assigned fuses or circuit breakers<br />

thermal memory, which is used for protection at the circuit<br />

breaker reclosing after switching off by overload – it can be disabled<br />

possible protection of N conductor (separately adjustable)<br />

optional earth-fault protection module with separately<br />

adjustable alarm signalling and tripping functions<br />

possible connection of data communication and measuring<br />

function Plus<br />

recognition of energy flow direction<br />

two parameter sets stored in the electronic release memory<br />

(switching over by an external signal)<br />

switchable overload protection for protection of modern drives<br />

adjustable delay of short-circuit protection up to 4000 ms<br />

adjustable protection of N conductor up to I N<br />

= 2 I n<br />

protective function setting by means of data communication<br />

For other technical data see the table on page 74<br />

Signalling: overcurrent<br />

release activated<br />

Alarm signalling:<br />

overload<br />

COMMUNICATION<br />

EXTENSION F.<br />

Rated current module <br />

Field for designation of<br />

set values<br />

Optional earth fault<br />

<br />

protection module<br />

Field for designation of<br />

set values<br />

Test push-button<br />

Query push-button<br />

<br />

<br />

<br />

<br />

<br />

<br />

Signalling: faulty<br />

overcurrent release<br />

Field for designation of<br />

set values<br />

Signalling of release<br />

tripping cause<br />

Alarm signalling<br />

at earth fault<br />

Signalling: tripping<br />

by earth fault<br />

Field for designation of<br />

set values<br />

Reset push-button<br />

Test connector<br />

Function<br />

Tripping characteristic identical to the overcurrent release ETU76B see page 83<br />

81


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU76B 3P 4P<br />

Description<br />

Use<br />

Release with versatile options for network analysis with graphic display.<br />

Properties<br />

adjustable overload protection with characteristic I 2 t or I 4 t<br />

with fixed delay t R<br />

= 10 s at 6 I R<br />

short-time delayed short-circuit protection, adjustable to<br />

1.25 ... <strong>12</strong>× I n<br />

and<br />

instantaneous short-circuit protection set to 20 I n<br />

, max. 50 kA<br />

overload signalling<br />

LED signalling of tripping cause<br />

release testing function<br />

protective function setting by rotary switch<br />

adjustable delay class for overload protection<br />

switchable characteristics I 2 t and I 4 t in overload area and in<br />

the area of short-time delayed short-circuit protection for better<br />

current selectivity with assigned fuses or circuit breakers<br />

thermal memory, which is used for protection at the circuit<br />

breaker reclosing after switching off by overload – it can be disabled<br />

possible protection of N conductor (separately adjustable)<br />

optional earth-fault protection module with separately<br />

adjustable alarm signalling and tripping functions<br />

possible connection of data communication and measuring<br />

function Plus<br />

recognition of energy flow direction<br />

two parameter sets stored in the electronic release memory<br />

(switching over by an external signal or directly on the release)<br />

switchable overload protection for protection of modern drives<br />

adjustable delay of short-circuit protection up to 4000 ms<br />

adjustable protection of N conductor up to I N<br />

= 2 I n<br />

protective function setting by means of data communication<br />

graphic presentation of all parameters and events and curves<br />

storage of events and tripping causes for specific fault analysis<br />

high contrast backlit graphic display with quiet mode.<br />

Mechanical reset of<br />

reclosing blocking<br />

Signalling: overcurrent<br />

release activated<br />

Alarm signalling:<br />

overload<br />

COMMUNICATION<br />

EXTENSION F.<br />

Signalling of release<br />

<br />

tripping cause<br />

Rated current module <br />

Optional module of<br />

<br />

earth-fault protection<br />

Field for designation of<br />

set value<br />

Test push-button<br />

Query push-button<br />

<br />

<br />

<br />

<br />

<br />

Option: safety lock, prevents<br />

from pressing of reset pushbutton<br />

after switching off by<br />

overcurrent<br />

Graphic display<br />

Control keys for<br />

setting of release parameters<br />

Signalling: faulty<br />

overcurrent release<br />

Alarm signalling<br />

at earth fault<br />

Signalling: tripping<br />

by earth fault<br />

Field for designation of<br />

set value<br />

Reset push-button<br />

Test connector<br />

For other technical data see the table on page 74<br />

Function<br />

82


ARION WL - Technical information<br />

OVERCURRENT RELEASES - ETU55B, ETU76B 3P 4P<br />

Tripping characteristic<br />

Function L<br />

Function S<br />

10000<br />

1000<br />

R<br />

0,4 . ... 1,0 . x n<br />

4 = const<br />

NSE0_01522<br />

10000<br />

1000<br />

sd<br />

NSE0_01526<br />

100<br />

2 = const<br />

100<br />

1,25 . x n ... 0,8 . x cw<br />

10<br />

R<br />

2 ... 30 for 2<br />

1 ... 5 for 4<br />

10<br />

1<br />

0,1 .<br />

1<br />

0,1 .<br />

sd = const<br />

0,02 . ... 4 s<br />

2<br />

sd = const<br />

0,1 . ... 0,4 . s<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

0,01 .<br />

0,1 .<br />

1 10 1<br />

/ n / cw<br />

Function I<br />

Function G<br />

10000<br />

1000<br />

NSE0_01524<br />

10000<br />

1000<br />

NSE0_01525<br />

100<br />

100<br />

g<br />

10<br />

10<br />

1<br />

0,1 .<br />

.<br />

i<br />

.<br />

0,1 .<br />

1,5 x n ... 0,8 x cs<br />

0,01<br />

1<br />

100 ... <strong>12</strong>00 A 1) A<br />

g 0,1 . ... 0,5 . s<br />

0,01 .<br />

0,1 .<br />

1 10 100<br />

/ n<br />

.<br />

100 1000 10000 100000<br />

1) Size Velikost I and II : 100 ... <strong>12</strong>00 A<br />

Size Velikost III : 400 ... <strong>12</strong>00 A<br />

Tolerance at set current:<br />

L: tripping between 1.05 and 1.2 x I R<br />

S: - 0 %, +20 %<br />

I: - 0 %, +20 %<br />

G: - 0 %, +20 %<br />

Tripping time tolerance:<br />

L: - 20 %, + 0 % for characteristic I 2 t<br />

S: - 0 %, + 60 ms or –0 %, +10% for characteristics with fixed delay<br />

I: < 50 ms<br />

G: - 0 ms, + 60 ms or –0 %, +10% for characteristics with fixed delay<br />

83


ARION WL - Technical information<br />

OVERCURRENT RELEASES - EARTH-FAULT PROTECTION MODULE 3P 4P<br />

Description<br />

The earth-fault protection module measures earth-fault current.<br />

Adjustable delay (time lag) enables selective sequencing<br />

of more circuit breakers. On the module it is possible to select<br />

the function of signalling or tripping (Alarm/Trip) at exceeding<br />

of a set limit of the earth current. By pressing the Query<br />

push-button the tripping cause is indicated by LED. In the<br />

overcurrent release ETU27B the earth-fault protection module<br />

is integrated. Releases ETU45B, ETU55B and ETU76B are available<br />

in two variants: without earth-fault protection module or<br />

with integrated earth-fault protection module.<br />

For other technical data see the table on page 74<br />

Method of measurement<br />

1. Vectorial sum of currents<br />

Overcurrent release measures currents in all three phases<br />

and also in N conductor and evaluates earth-fault current by<br />

means of vectorial addition of these currents. 3-pole circuit<br />

breakers must be completed by an external current transformer<br />

for N conductor see page 40. 4-pole circuit breakers must be<br />

equipped with an internal current transformer see page 32.<br />

Earth-fault protection module GFM AT 45B<br />

Earth fault measurement<br />

mode switch<br />

Rotary switch setting<br />

the limits of tripping at<br />

earth fault<br />

Rotary switch setting<br />

the limits of alarm<br />

at earth fault<br />

Earth-fault protection module GFM AT 55B - 76B<br />

Field for designation of<br />

the set measurement mode<br />

Alarm signalling<br />

of earth fault<br />

Signalling of tripping<br />

by earth fault<br />

Rotary switch of earthfault<br />

protection delay<br />

t g<br />

/ I 2 t g<br />

Alarm signalling<br />

of earth fault<br />

Signalling of tripping<br />

by earth fault<br />

2. Direct measurement of earth-fault current<br />

Direct measurement of earth-fault current is performed by<br />

current transformer with ratio <strong>12</strong>00 A/1A and accuracy class<br />

1. Internal resistance of the circuit for the current transformer<br />

connection is 0.11 Ohm. The current transformer is installed on<br />

the earth conductor of the (power) transformer unit.<br />

Setting<br />

For ETU27B and ETU45B release the earth-fault protection<br />

module is set by switches. For ETU55B it is set by means of<br />

communication. For ETU76B it is set via menu or communication.<br />

It is possible to set:<br />

earth fault measurement mode<br />

alarm limits for signalling of earth-fault tripping<br />

earth-fault tripping delay<br />

Earth-fault protection with characteristic I 2 t<br />

All releases - except ETU27B - have switchable characteristic I 2 t<br />

= constant. The use of this characteristic reduces thermal load<br />

of protective conductor PE at short circuit.<br />

Field for designation of<br />

set limits<br />

3-pole circuit breaker, current transformer on N conductor,<br />

vector sum of currents<br />

3-pole circuit breaker, current transformer on earth<br />

conductor of the transformer unit, direct measurement<br />

Field for designation of<br />

set limits<br />

Setting range of I g<br />

Circuit breaker size<br />

I and II<br />

III<br />

A 100 A 400 A<br />

B 300 A 600 A<br />

C 600 A 800 A<br />

D 900 A 1000 A<br />

E <strong>12</strong>00 A <strong>12</strong>00 A<br />

4-pole circuit breaker, current transformer on earth<br />

conductor of the transformer unit, direct measurement<br />

84


ARION WL - Technical information<br />

MEASUREMENT AND DATA COMMUNICATION 3P 4P<br />

Description<br />

Measurement<br />

Circuit breaker equipped with relevant modules can measure<br />

electrical quantities in the protected circuit, e.g. current,<br />

voltage or power. The values can be displayed directly on the<br />

overcurrent release display or transferred by means of data<br />

communication.<br />

PLC SIMATIC S7<br />

data acquisition and<br />

processing<br />

PC with program Switch ES Power<br />

parameterization and visualization by<br />

means of PROFIBUS<br />

Data communication<br />

Data communication can be implemented via PROFIBUS or<br />

MODBUS protocol. Values can be obtained also in analog form<br />

via CubicleBUS module. Another method of transfer of the<br />

measured value is via BDA adapter with Ethernet protocol.<br />

This makes it possible to view the values on a standard PC. This<br />

solution is intended above all for service actions.<br />

The circuit breaker equipped with data communication enables:<br />

remote control<br />

setting of overcurrent release parameters<br />

state monitoring<br />

transfer of measured values<br />

Ethernet/<br />

Intranet/<br />

Internet<br />

BDA<br />

BDA Plus<br />

Output device<br />

e.g. notebook<br />

COM15<br />

BSS<br />

ETU<br />

Measuring function<br />

Plus<br />

Module with digital outputs<br />

Module with configurable digital outputs<br />

Module with analog outputs<br />

Module with digital inputs<br />

ZSS module<br />

GSD files necessary for control unit programming will be<br />

delivered on request.<br />

Measurement<br />

Measurement variants and properties<br />

Variant Standard variant – without measuring function Plus Extended variant – with measuring function Plus<br />

Current, voltage, power (active, apparent, reactive), Energy, Cos φ,<br />

frequency, harmonic analysis<br />

Measured quantities<br />

Current<br />

- displays instantaneous value and records minimum and maximum value<br />

- enables storage of behaviour (curves) of current and voltage in the memory 4)<br />

- signals exceeding of the set limits of measured quantities 4)<br />

- extends protective functions 4)<br />

Necessary circuit breaker equipment<br />

Overcurrent release ETU45B or ETU55B 1) or ETU76B ETU45B or ETU55B 1) or ETU76B<br />

Measuring function Plus<br />

No – current measurement is standard function of the release<br />

ETU45B, ETU55B 1) , ETU76B<br />

Yes<br />

Voltage transformers No Yes<br />

Power supply No Yes<br />

Display of measured values<br />

Local Yes – on the overcurrent release display 2) Yes – on the overcurrent release display 2)<br />

Remote<br />

(PC, PLC, analog measuring instruments)<br />

Yes – the circuit breaker must be equipped with data communication<br />

PROFIBUS, MODBUS, CubicleBUS or with BDA adapter<br />

Yes – the circuit breaker must be equipped with data communication<br />

PROFIBUS, MODBUS or CubicleBUS<br />

Type designation for ordering<br />

Component/module type designation/complement code type designation/complement code<br />

ETU45B without display 1) ARION WL1-EB- ARION WL1-EB-<br />

Overcurrent release<br />

ETU45B with display ARION WL1-FB- ARION WL1-FB-<br />

ETU55B 1) ARION WL1-JB- ARION WL1-JB-<br />

ETU76B ARION WL1-NB- ARION WL1-NB-<br />

Measuring function Plus No „F05“<br />

Voltage transformers for 400 V a.c. 3) No 3WL9111-0BB68-0AA0<br />

Power supply No 6EP1333-2AA01<br />

1)<br />

- the circuit breaker must be equipped with data communication PROFIBUS, MODBUS or CubicleBUS for transfer and display of measured values - ETU55B has not a display<br />

2)<br />

- the circuit breaker must be equipped with overcurrent release ETU45B with display or ETU76B with graphic display<br />

3)<br />

- measuring transformers for other voltage see page 40<br />

4)<br />

- Detailed information about measuring function Plus will be delivered on request or see „Detailed Instructions for Use“ at www.oez.com.<br />

85


86<br />

ARION WL - Technical information<br />

MEASUREMENT AND DATA COMMUNICATION 3P 4P<br />

Data communication - PROFIBUS, MODBUS, BDA adapter<br />

Data communication methods and properties<br />

Method of data communication PROFIBUS MODBUS BDA adapter<br />

Communication protocol PROFIBUS MODBUS Ethernet<br />

Connectible display and control unit PC, PLC - e.g. SIMATIC S7 On request PC<br />

SW of connected PC Switch ES Power On request Internet Explorer + JAVA 2 Virtual Machine<br />

HW of desktop PC 6GK1561-3AA01 – PCI card On request network card or port RS232<br />

HW of portable PC<br />

6GK1551-2AA00 – PCMCI card<br />

C79459-A1890-A10 – adapter for PCMCI card<br />

On request<br />

network card or port RS232<br />

Necessary circuit breaker equipment<br />

Overcurrent release ETU45B, ETU55B, ETU76B ETU45B, ETU55B, ETU76B ETU45B, ETU55B, ETU76B<br />

Power supply Yes Yes Yes 4)<br />

Communication module COM15 3) COM16 3) BDA adapter 3)<br />

Circuit breaker control<br />

Circuit breaker On/Off Yes Yes Yes 1)<br />

Reset of signalling „switched off by overcurrent release“ Yes 5) Yes 5) Yes 5)<br />

Free user digital output On/Off Yes Yes Yes 1)<br />

Signalling of circuit breaker state<br />

Circuit breaker state On/Off Yes Yes Yes 6)<br />

Switched off by overcurrent release Yes Yes Yes 6)<br />

Circuit breaker position in the withdrawable device Yes Yes<br />

1) 6)<br />

Yes<br />

Disconnected by undervoltage release Yes Yes No<br />

Ready-to-close Yes Yes Yes 6)<br />

Energy-storing mechanism state Yes Yes Yes 6)<br />

Ready-to-close Yes Yes Yes 6)<br />

Monitoring of input state of CubicleBUS module with digital inputs Yes Yes Yes 6)<br />

Parameter setting<br />

Change of parameters of protective functions 2) Yes 2) Yes Yes<br />

Parameter set switching 2) Yes 2) Yes Yes<br />

Maintenance information reset Yes Yes Yes<br />

Reset of minimum and maximum measured values Yes Yes Yes<br />

Event memory and behaviour memory clearing Yes Yes Yes 1)<br />

Setting of limits for measured value exceeding alarm Yes Yes Yes<br />

Setting of parameters of extended protective functions Yes Yes Yes<br />

Reading of parameters<br />

Reading of event protocol Yes Yes Yes 1)<br />

Reading of overcurrent release tripping protocol Yes Yes Yes 1)<br />

Download of protective function parameters Yes Yes Yes<br />

Contact wear Yes Yes Yes 6)<br />

Circuit breaker identification Yes Yes Yes<br />

Number of switching at load and in total, number of operating hours Yes Yes Yes 1)<br />

Number of switching off by release (function L, S, I total) Yes Yes Yes<br />

Download of limits for measured value exceeding alarm Yes Yes Yes<br />

Download of parameters of extended protective functions Yes Yes Yes<br />

Download of record of current and voltage behaviour Yes Yes Yes<br />

Alarms<br />

Alarm of switching off by overcurrent release with breaking current value/including time Yes Yes Yes<br />

Alarm with information of its start and end/including time Yes Yes Yes<br />

Alarm of exceeding of limits of measured value Yes Yes Yes<br />

Measured quantities<br />

Current in all phases including max. and min. value/including time Yes Yes Yes/No<br />

Temperature in the circuit breaker including max. and min. value/including time Yes Yes Yes/No<br />

Temperature in the cubicle including max. and min. value/including time Yes Yes No<br />

Current, voltage, power (active, apparent, reactive), Energy, Cos φ,<br />

frequency, harmonic analysis including max. and min. value<br />

Yes Yes Yes<br />

Type designation for ordering<br />

Component/module type designation/complement code type designation/complement code type designation/complement code<br />

ETU45B without display ARION WL1-EB- ARION WL1-EB- ARION WL1-EB-<br />

Overcurrent release<br />

ETU45B with display ARION WL1-FB- ARION WL1-FB- ARION WL1-FB-<br />

ETU55B ARION WL1-JB- ARION WL1-JB- ARION WL1-JB-<br />

ETU76B ARION WL1-NB- ARION WL1-NB- ARION WL1-NB-<br />

Data communication „F02“ „F<strong>12</strong>“ 3WL9111-0AT33-0AA<br />

BSS module included „F02“ included „F<strong>12</strong>“ optional „F01“<br />

Source 6EP1333-2AA01 6EP1333-2AA01 6EP1333-2AA01 4)<br />

- only for circuit breaker equipped with measuring function Plus, see page 85<br />

1)<br />

- only if the circuit breaker is equipped with data communication PROFIBUS or MODBUS<br />

2)<br />

- only with ETU55B or ETU76B<br />

3)<br />

- COM15 is the module of data communication via protocol PROFIBUS, COM16 is the module of data communication via protocol MODBUS, BDA adapter is the module of data communication via protocol ETHERNET<br />

4)<br />

- only if power supply is not provided for data communication or measuring function Plus<br />

5)<br />

- the circuit breaker must be equipped with remote and automatic reset see page 32<br />

6)<br />

- the circuit breaker must be equipped with BSS module see page 32


ARION WL - Technical information<br />

MEASUREMENT AND DATA COMMUNICATION 3P 4P<br />

Data communication - CubicleBUS<br />

Module with digital outputs<br />

6 digital outputs<br />

outputs by means of relays or optocouplers<br />

outputs can be assigned to selected circuit breaker state signals<br />

output assignment by means of rotary switch<br />

max. 2 modules can be connected to the circuit breaker<br />

Module with configurable digital outputs<br />

6 digital outputs<br />

outputs by means of relays or optocouplers<br />

outputs can be assigned to selected circuit breaker state signals<br />

max. 1 module can be connected to the circuit breaker<br />

configuration by means of BDA adapter or PC with software<br />

„ES Switch Power“ via PROFIBUS<br />

Module with analog outputs<br />

four analog outputs (3 phases + N pole)<br />

at a time it can transfer one selected measured quantity<br />

with values in all three phases and N pole<br />

possibility of selection of analog output type 0 ÷ 10 V or 4 ÷ 20 mA<br />

selection of quantities to be transferred and selection of analog output<br />

type is possible by means of rotary switch<br />

max. 2 modules can be connected to the circuit breaker<br />

Module with digital inputs<br />

module has two modes<br />

control voltage 24 V d.c.<br />

max. 2 modules can be connected to the circuit breaker; one in mode 1 and<br />

the other in mode 2<br />

MODE 1: user inputs transferred via protocol PROFIBUS<br />

or Ethernet (BDA adapter) - 6 digital inputs<br />

MODE 2: switching of overcurrent release parameter sets<br />

(for ETU55B, ETU76B) - 1 digital input<br />

ZSS module – short selectivity control<br />

at connection of circuit breakers ARION WL at more levels it ensures full<br />

selectivity at short-circuit protection<br />

ensures as short breaking time as possible in case of short circuit<br />

all controlled circuit breakers must be equipped with one ZSS module<br />

At short circuit in the protected circuit, the affected circuit breaker sends “short circuit<br />

protected” alarm. Consequently, the system can determine the place of short<br />

circuit, and disconnect the circuit breaker, which is closest to the short circuit in<br />

the energy flow direction. Higher-level circuit breakers are in standby mode. If the<br />

circuit breaker, which is closest to the short circuit, does not send the information<br />

of the short circuit (for example, the circuit breaker is set incorrectly), the short<br />

circuit will switch off the closest higher-level circuit breaker immediately, without<br />

waiting for expiration of selectivity time.<br />

3WL9111-0AT25-0AA0 – outputs with optocouplers<br />

3WL9111-0AT26-0AA0 – relay outputs<br />

3WL9111-0AT30-0AA0 – outputs with optocouplers<br />

3WL9111-0AT20-0AA0 – relay outputs<br />

3WL9111-0AT23-0AA0<br />

3WL9111-0AT27-0AA0<br />

3WL9111-0AT21-0AA0<br />

Detailed information about CubicleBUS modules will be delivered<br />

on request or see „Detailed Instructions for Use“ at www.oez.com.<br />

Parameters of CubicleBUS modules<br />

Name Module with digital outputs Module with configurable Module with analog outputs Module with digital inputs ZSS module<br />

digital outputs<br />

Type designation – – 3WL9111-0AT23-0AA0 3WL9111-0AT27-0AA0 3WL9111-0AT21-0AA0<br />

Outputs with optocouplers 3WL9111-0AT25-0AA0 3WL9111-0AT30-0AA0 – – –<br />

Relay outputs 3WL9111-0AT26-0AA0 3WL9111-0AT20-0AA0 – – –<br />

Function digital outputs programmable digital outputs analog outputs digital inputs short selectivity control<br />

Number of inputs – – – 6/1 according to mode, see the text –<br />

Number of outputs 6 6 4 (3f + N) – –<br />

Output/input type digital digital analog digital –<br />

Rated operating current U e<br />

Relay output AC15 6 A/250 V a.c. 6 A/250 V a.c. – – –<br />

DC13 2 A/24 V d.c., 0,2 A/250 V d.c. 2 A/24 V d.c., 0,2 A/250 V d.c. – – –<br />

Output with optocoupler 100 mA/24 V d.c. 100 mA/24 V d.c. – – –<br />

87


ARION WL - Technical information<br />

AUXILIARY SWITCHES, SIGNAL SWITCHES 3P 4P<br />

Description<br />

Auxiliary switches<br />

The switches signal always the state of main contacts of<br />

the circuit breaker. Each circuit breaker is equipped with<br />

two make and break contacts. The circuit breaker can by<br />

completed by additional contacts.<br />

Parameters<br />

Auxiliary switches – designation in the diagram: S1, S2, S3, S4, S7, S8<br />

Rated operating voltage U e<br />

500 V a.c./d.c.<br />

Rated insulation voltage U i<br />

500 V a.c/d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated operating current I e<br />

AC-<strong>12</strong> 10 A/24 ÷ 500 V<br />

AC-15<br />

4 A/24 ÷ 230 V, 3 A/400 V, 2 A/500 V<br />

DC-<strong>12</strong><br />

10 A/24 V, 8 A/48 V, 3.5 A/110 V, 1 A/220 V<br />

DC-13<br />

8 A/24 V, 4 A/48 V, 1.2 A/110 V, 0.4 A/220 V<br />

Signal switch<br />

„switched off by overcurrent release”<br />

– designation in the diagram: S24<br />

This contact signals the circuit breaker disconnection by<br />

overcurrent release due to overload, short circuit or earth<br />

fault. The signal switch is optional accessory. If the circuit<br />

breaker is equipped with data communication, this contact<br />

is standard accessory.<br />

Signal switch “ready-to-close”<br />

– designation in the diagram: S20<br />

Circuit breakers are standardly equipped with an optical<br />

indicator of readiness to closing. The switch enables remote<br />

signalling „ready-to-close“. The signal switch is optional<br />

accessory. If the circuit breaker is equipped with data communication,<br />

this contact is standard accessory.<br />

Signal switch of energy-storing mechanism state<br />

– designation in the diagram: S21<br />

Circuit breakers are standardly equipped with an optical<br />

indicator of energy-storing mechanism state. The switch<br />

enables remote signalling, whether the energy-storing<br />

mechanism is wound up or released. The signal switch is<br />

optional accessory. If the circuit breaker is equipped with<br />

data communication, this contact is standard accessory.<br />

Parameters<br />

Signal switches<br />

Rated operating voltage U e<br />

250 V a.c./d.c.<br />

Rated insulation voltage U i<br />

440 V a.c./250 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated operating current I e<br />

AC-<strong>12</strong> 8 A/250 V<br />

DC-<strong>12</strong><br />

6 A/24 V, 0.4 A/<strong>12</strong>5 V, 0.2 A/250 V<br />

Diagram see page 54<br />

88


ARION WL - Technical information<br />

SHUNT RELEASE, AUXILIARY POWER SOURCE FOR SHUNT RELEASE 3P 4P<br />

Description<br />

Shunt release<br />

Shunt release causes immediate disconnection of the circuit<br />

breaker when voltage is applied on it. The shunt release is<br />

delivered in the version for short-time excitation (overexcitation)<br />

with load factor 5% and in the variant for continuous<br />

excitation with load factor 100%. Continuously excited release<br />

enables circuit breaker blocking in disconnected state and<br />

blocking of eventual circuit breaker reclosing. It is possible to<br />

buy an auxiliary power source for shunt release, which enables<br />

circuit breaker disconnection at interruption of control circuit<br />

power supply.<br />

Auxiliary release signal switch<br />

Shunt release state is signalled by the auxiliary signal switch.<br />

Diagram see page 54<br />

Parameters<br />

Shunt release – designation in the diagram: F1, F2<br />

Rated operating voltage U e<br />

110, 230 V a.c.<br />

24, 30, 48, 60, 110, 220 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Power input I e<br />

15 W/15 VA<br />

Characteristic<br />

U>= 0.7 U e<br />

circuit breaker must be switched off<br />

Control pulse<br />

min. 60 ms<br />

Time to switching off<br />

80 ms<br />

Protection Circuit breaker LSN 1C/1<br />

Shunt release signal switch – designation in the diagram: S22 or S23<br />

Rated operating voltage U e<br />

250 V a.c./d.c.<br />

Rated insulation voltage U i<br />

440 V a.c./250 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated operating current I e<br />

AC-<strong>12</strong> 8 A/250 V<br />

DC-<strong>12</strong><br />

6 A/24 V, 0.4 A/<strong>12</strong>5 V, 0.2 A/250 V<br />

Auxiliary power source for shunt release<br />

Operating voltage Type Maximum power supply time<br />

110 V a.c./d.c. 3WL9111-0BA13-0AA0 5 min from failure<br />

230 V a.c./220 d.c. 3WL9111-0BA14-0AA0 5 min from failure<br />

UNDERVOLTAGE RELEASE 3P 4P<br />

Description<br />

Undervoltage release<br />

Undervoltage release causes instantaneous disconnection of<br />

the circuit breaker at drop of control voltage of the release<br />

under a specified limit or at full loss of voltage. If the undervoltage<br />

release is not excited, it is not possible to switch on<br />

the circuit breaker mechanically or electrically. The release is<br />

delivered in two variants; short-time delayed with delay of 80<br />

or 200 ms and long-time delayed with delay of 0.2 to 3.2 s.<br />

Auxiliary release signal switch<br />

Undervoltage release state is signalled by the auxiliary signal<br />

switch.<br />

Parameters<br />

Shunt release – designation in the diagram: F3, F4<br />

Rated operating voltage U e<br />

110 , 230 V, 400 V a.c.<br />

24 1) , 30 1) , 48, 110, 220 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Power input I e<br />

5 W/5 VA (holding 200 W/200 V)<br />

Characteristic<br />

U>=0.85 U e<br />

circuit breaker can be switched on<br />

U


ARION WL - Technical information<br />

LOCKING AND BLOCKING DEVICES 3P 4P<br />

Description<br />

Locking device against unauthorized closing<br />

This function prevents from circuit breaker closing and meets the<br />

requirements of EN 60 204 (VDE 0113) for safe disconnection<br />

from the network. The locking device is effective only on given<br />

circuit breaker. After circuit breaker replacement, the closing is<br />

not prevented until the new circuit breaker is locked against<br />

unauthorized closing. After activation of the locking device the<br />

circuit breaker must be switched off. The lock is effective only<br />

with withdrawn key. The key can be withdrawn only in position<br />

“OFF”. With the circuit breaker “ON” the locking device is blocked.<br />

Locking device against unauthorized closing,<br />

independent of the circuit breaker<br />

This special function for withdrawable circuit breakers prevents<br />

from circuit breaker closing, is independent of the circuit<br />

breaker, and meets the requirements of EN 60 204 (VDE<br />

0113) for safe disconnection from the network. It prevents<br />

from unauthorized closing of the circuit breaker also after<br />

its replacement by other circuit breaker. The locking is effec-<br />

tive only with the circuit breaker switched off and the key<br />

withdrawn. The key can be withdrawn only in position “OFF”.<br />

With the circuit breaker “ON” the locking device is blocked.<br />

Protective caps for mechanical On/Off<br />

They prevent from unauthorized closing/opening of the circuit<br />

breaker on the control panel. For the variant with locking by<br />

means of a safety lock, it is only possible to press the push-buttons,<br />

if the key is inserted. The circuit breaker can be switched<br />

on/off remotely. The lock is effective only with withdrawn key. For<br />

the variant with locking by means of a padlock, the push-buttons<br />

are covered by the caps with hole of diameter 6.5 mm. The holes<br />

enable the circuit breaker control by means of a special tool.<br />

Locking of the energy-storing mechanism hand drive<br />

lever<br />

The energy-storing mechanism drive lever can be locked by<br />

a padlock. After it, it is not possible to wind up the energystoring<br />

mechanism by the lever.<br />

Locking device against shifting of withdrawable<br />

circuit breaker<br />

It prevents from withdrawal of the crank for circuit breaker<br />

shifting. The circuit breaker is thus secured against withdrawing.<br />

The lock is effective only at the key withdrawn.<br />

Blocking device against circuit breaker shifting at<br />

open cubicle door<br />

The crank for circuit breaker withdrawing/inserting is blocked<br />

and cannot be withdrawn. Circuit breaker cannot be moved.<br />

The blocking is effective only with the crank inserted.<br />

Blocking device against cubicle door opening<br />

Blocking is transferred by Bowden cable.<br />

It is not possible to open the cubicle door, if:<br />

fixed circuit breaker is switched on<br />

withdrawable circuit breaker is in operating position<br />

Mechanical interlocking<br />

Mechanical interlocking can block 2 or 3 circuit breakers/<br />

switch-disconnectors. The interlocking is solved by means of<br />

Bowden cables. It is possible to interlock circuit breakers and<br />

switch-disconnectors of both fixed and withdrawable design.<br />

For example, it is possible to block 3 devices: 2 circuit breakers<br />

of withdrawable design and one switch-disconnector of fixed<br />

design. Mechanical interlocking is only functional if the circuit<br />

breaker of withdrawable design is in operating position. The<br />

distance between blocked circuit breakers/switch-disconnectors<br />

is given by the length of the used Bowden cables.<br />

Circuit breakers/switch-disconnectors can be installed next<br />

to each other or above each other. Circuit breakers/switchdisconnectors<br />

equipped with mechanicalinterlocking are<br />

standardly equipped with 2 m Bowden cables. It is possible<br />

to buy separately Bowden cables of the length 2 m, 3 m or<br />

4.5 m. At use of mechanical interlocking for three circuit<br />

breakers/switch-disconnectors, it is necessary to order to each<br />

circuit breaker/switch-disconnector separately one additional<br />

Bowden cable of relevant length. Mechanical endurance of the<br />

mechanical interlocking is 10 000 cycles.<br />

Conditions of use and correct function of mechanical<br />

interlocking:<br />

Bowden cables must be, if possible, led straight, without<br />

undue bends<br />

Bend radius of the Bowden cable must be higher than<br />

500 mm<br />

The sum of all bend angles of the Bowden cable must not<br />

be higher than 640°<br />

At arrangement of the interlocked circuit breakers/<br />

switch-disconnectors above each other the interlocking<br />

mechanisms must be in row above each other<br />

The distance between the blocked circuit breakers/<br />

switch-disconnectors is given by the length of the<br />

Bowden cables which must be led according to the<br />

mentioned rules<br />

Bowden cables must be fixed in the cubicle already<br />

before mechanical interlocking setting<br />

Fixed Bowden cables must not prevent circuit breaker/<br />

switch-disconnector handling or cubicle door opening<br />

Example of possible interlocking<br />

- max. 1 circuit breaker can be<br />

switched on<br />

- max. 2 arbitrary circuit<br />

breakers can be switched on<br />

- max 1 circuit breaker can be<br />

switched on<br />

- 2 transformers or only generator can<br />

be switched on<br />

- transformer and generator are blocked<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

For other information see Detailed Instructions for Use at www.oez.com.<br />

90


ARION WL - Technical information<br />

DRIVES AND CLOSING RELEASES 3P 4P<br />

Description<br />

Hand drive<br />

Each circuit breaker is equipped with the hand drive. Hand<br />

drive lever is used for mechanical winding up of the energystoring<br />

mechanism.<br />

Motor drive<br />

It is used for automatic winding up of the spring energystoring<br />

mechanism of the closing mechanism. The drive is<br />

switched on automatically, if the energy-storing mechanism is<br />

not wound up (if supply voltage is applied). After energy-storing<br />

mechanism winding up, the drive is switched off automatically.<br />

Manual winding up of the energy-storing mechanism by<br />

a lever is independent of the motor drive.<br />

Motor drive switch<br />

It switches the motor drive off.<br />

Operating cycle counter<br />

The circuit breaker with the motor drive can be equipped<br />

with 5-place cycle counter. The counter adds „1” after each full<br />

winding up of the energy-storing mechanism.<br />

Closing release<br />

It enables local (by electrical ON push-button on the front<br />

control panel) or remove switching the circuit breaker on by<br />

electrical pulse. The closing release is delivered in the version<br />

for short-time excitation (overexcitation) with load factor 5%<br />

and in the version for continuous excitation with load factor<br />

100%. Circuit breakers switching on by means of mechanical<br />

“ON” push-button on the front panel of the circuit breaker is<br />

independent of the closing release.<br />

Parameters<br />

Hand drive<br />

Number of lever pushing for full<br />

9<br />

winding up of the energy-storing<br />

mechanism<br />

Control force<br />

230 N<br />

Motor drive<br />

Rated operating voltage U e<br />

110 , 230 V a.c.<br />

24, 30 1) , 48, 60 1) , 110, 220 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Power input I e<br />

110 W/110 VA<br />

Time to energy-storing<br />

mechanism winding up<br />

> 10 s<br />

Protection 24 ÷ 60 V PV10 2A gG, LSN 2C/1<br />

110 ÷ 230 V LSN 1C/1<br />

Closing release<br />

Rated operating voltage U e<br />

110 , 230 V a.c.<br />

24 1) , 30 1) , 48, 60, 110, 220 V d.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Power input I e<br />

15 W/15 VA<br />

Control pulse<br />

min. 60 ms<br />

Time to switching off<br />

80 ms<br />

Protection Circuit breaker LSN 1C/1<br />

1)<br />

- only for release with load factor 100 %<br />

Diagram see page 54<br />

91


ARION WL - Technical information<br />

GLOSSARY OF TERMS<br />

Note: Precise wording of definitions and texts relating to a given term are detailed in the respective standards (see Name).<br />

Name Symbol Explanation<br />

Rated operating voltage<br />

EN 60947-1; 4.3.1.1<br />

Rated insulation voltage<br />

EN 60947-1; 4.3.1.2<br />

Rated current<br />

EN 60947-2; 4.3.2.3<br />

U e<br />

U i<br />

I n<br />

Voltage fixed by the manufacturer. Several pertinent tests relate to its determination, as may also the utilization<br />

category. Along with the rated (operating) current, it determines the device’s utilization. The highest<br />

value of rated operating voltage may in no case be greater than the value of the rate insulation voltage U i<br />

.<br />

Voltage measure to which are related tests of dielectric strength and creepage distance.<br />

Current value of particular circuit breaker that can be handled uninterruptedly. The highest current<br />

valued tripping the circuit breaker in conformity with a specifically stated tripping characteristic.<br />

Reduced rated current I r<br />

Specifically established, reduced value of I n<br />

current for a regulated time-dependent (thermal) release<br />

and that the circuit breaker can handle continuously. Maximum setting is at value equal to I n<br />

. Changing<br />

I r<br />

shifts the release’s tripping characteristic along the current axis. (I r<br />

= k x I n<br />

holds where k ≤ 1)<br />

Tripping time at a given I r<br />

multiple t r<br />

Time after which circuit breaker will trip, if a current flows through it that is equal to the given multiple<br />

of I r<br />

. Changing t r<br />

shifts the tripping characteristic along the time axis.<br />

Actuating current of (selective) release’s timeindependent<br />

delay<br />

I rmv<br />

Minimum current value causing the release’s time-independent delay to actuate.<br />

Delay of time-independent delayed release t v<br />

If a current flows through the circuit breaker equal to at least I rmv<br />

but not reaching I rm<br />

the circuit breaker<br />

will trip with time delay t v<br />

. Total shut-off time is influenced by the tripping of the circuit breaker itself<br />

and is about 10 ÷ 20 ms longer.<br />

Actuating current of time-independent<br />

instantaneous (short-circuit) release<br />

Rated operating current<br />

EN 60947-1; 4.3.2.3<br />

Rated normal current<br />

EN 60947-1; 4.3.2.4<br />

Rated ultimate short-circuit breaking capacity<br />

EN 60947-2; 2.15.1; 4.3.5.2.1<br />

Rated short-circuit service breaking capacity<br />

EN 60947-2; 2.15.2; 4.3.5.2.2<br />

Rated short-time withstand current<br />

EN 60947-1; 4.3.6.1<br />

EN 60947-2; 4.3.5.4<br />

EN 60947-3; 4.3.6.1<br />

I rm<br />

I e<br />

I u<br />

I cu<br />

I cs<br />

I cw<br />

Minimum current value causing the time-independent instantaneous release to actuate.<br />

Rated operating current of device (switch-disconnector) is fixed by the manufacturer with consideration<br />

for the rated operating voltage, rated frequency, rated operation, utilization category and type of<br />

protective cover, if that comes into consideration.<br />

Current value set by the manufacturer and which the device can handle in continuous operation, i.e.<br />

during a period longer than 8 hours (weeks, months, or longer).<br />

Ultimate short-circuit breaking capacity value expressed as the rms value of the alternating component<br />

of the assumed short-circuit current that the circuit breaker must be able to manage in the mode: 1x<br />

switching off of the short circuit and a following 1x make-break sequence. After testing, the circuit<br />

breaker need not be able to conduct the rated current uninterruptedly. I cu<br />

is set for the rated operating<br />

voltage at the rated frequency and at the established power factor for alternating current or at the time<br />

constant for direct current. Must fulfil the condition: I cu<br />

≥ I k<br />

“<br />

Value of the operating short-circuit breaking capacity expressed as the rms value of the alternating<br />

component of the assumed short-circuit current that the circuit breaker must be able to manage in<br />

the mode: 1x switching off of the short circuit and a following 2x make-break sequence. May also<br />

be expressed as a percentage of I cu<br />

. After testing, the circuit breaker must be able uninterruptedly to<br />

conduct the rated current and to switch off the overcurrent. Temperature increase of the main terminals<br />

may be greater. I cs<br />

is set for the rated operating voltage at the rated frequency and at the established<br />

power factor for alternating current or at the time constant for direct current. Permitted: I cs<br />

≥ I k<br />

“<br />

Value of short-time withstand current specified by the manufacturer that the device is able to handle<br />

without damage during a designated time period (short-time delay). In case of alternating current, it<br />

is the rms value of the alternating component of the assumed short-circuit current I p<br />

.<br />

92


GLOSSARY OF TERMS<br />

ARION WL - Technical information<br />

Note: Precise wording of definitions and texts relating to a given term are detailed in the respective standards (see Name).<br />

Name Symbol Explanation<br />

Rated short-circuit making capacity<br />

EN 60947-1; 4.3.6.2<br />

EN 60947-2; 4.3.5.1<br />

EN 60947-3; 4.3.6.2<br />

Initial peak short-circuit current<br />

EN 60909-0; 1.3.5<br />

Surge short-circuit current<br />

EN 60909-0; 1.3.8<br />

Prospective short-circuit current<br />

EN 60947-1; 2.5.5<br />

EN 60909-0; 1.3.3<br />

Rated pulse withstand voltage<br />

EN 60947-1; 4.3.1.3<br />

Overvoltage category<br />

EN 60947-1; 2.5.60<br />

Rated frequency<br />

EN 60947-1; 4.3.3<br />

Utilization category<br />

(circuit breakers - timing selectivity)<br />

EN 60947-2; 4.4<br />

Utilization category<br />

(switch-disconnectors - switching mode)<br />

EN 60947-3; 4.4<br />

Pollution degree<br />

EN 60947-1; 2.5.58; 6.1.3.2<br />

I cm<br />

“<br />

I k<br />

i p<br />

I p<br />

U imp<br />

f n<br />

Value of short-circuit making capacity specified by the manufacturer for the rated operating voltage<br />

at the rated frequency and at the established power factor for alternating current or at the time<br />

constant for direct current. It is expressed as the maximum assumed peak current. Must fulfil the<br />

condition: I cm<br />

≥ i p<br />

Short-circuit current value at the moment of its arising at a given point in the electrical distribution<br />

expressed as the rms value of the alternating symmetrical component of the assumed short-circuit<br />

current.<br />

Maximum possible momentary value of the assumed short-circuit current. (Corresponds to the<br />

moment the short arises, as a result of which there occurs the peak value of the short-circuit current.)<br />

Short-circuit current value, which would flow through the circuit if the protection device were replaced<br />

and a short circuit were experienced by conductors with negligible impedance. (In a three-phase<br />

distribution, it is assumed that the short circuit is simultaneous in all phases.)<br />

Peak value of the voltage impulse of the prescribed form and polarity which the device is able to<br />

withstand without failure at the established conditions and pertinent to which is the value of the<br />

separating air distance. U imp<br />

of the device must be equal to or higher than the value established for<br />

momentary overvoltage at the point in the circuit (overvoltage category) where the device is used.<br />

Numerically defined level of momentary overvoltage, i.e. overvoltage having its origin in atmospheric<br />

or switching. Standard EN 60664-1 establishes for electrical equipment the overvoltage categories:<br />

Overvoltage category IV - service entrance, outside lead<br />

Overvoltage category III - fixed wiring<br />

Overvoltage category II - appliances<br />

Overvoltage category I - light-current appliances<br />

Frequency of the supply network for which the device is proposed and that corresponds to its other<br />

characteristics values.<br />

Utilization category of circuit breaker establishes whether or not the circuit breaker specifically is<br />

intended for providing selectivity by means of intentional time delay (timing selectivity) with other<br />

protective devices connected in series on the load side in short-circuiting conditions.<br />

Utilization category:<br />

A - circuit breakers are not specifically intended for providing timing selectivity<br />

B - circuit breakers are specifically intended for providing timing selectivity<br />

Utilization category defines the assumed use of switch devices (switch-disconnectors). Characterised<br />

by values of current and voltage, expressed as multiples of rated operating current and rated operating<br />

voltage, and further by power factors or time constants of the circuit.<br />

Utilization category:<br />

AC-21B (DC-21B) - infrequent switching of resistive loads, including moderate overloading<br />

AC-22B (DC-21B) - infrequent switching of mixed resistive and inductive loads, including moderate overloading<br />

AC-23B (DC-23B) - infrequent switching of motor loads or other highly inductive loads.<br />

Pollution degree relates to the conditions of the surrounding environment for which the device is intended.<br />

Pollution degree:<br />

1 - No contamination will occur, or only dry, non-conducting contamination.<br />

2 - Normally occurs only non-conducting contamination, but sometimes there may occur temporary<br />

conductibility due to condensation.<br />

3 - There occurs conductive contamination or dry non-conducting contamination that with the effect of<br />

condensation will become conductive.<br />

4 - Contamination generates continuous conductibility, by means of, for example, conductive dust, rain or snow.<br />

93


ARION WL - Technical information<br />

NOTES<br />

94


ARION WL - Commercial information<br />

NOTES<br />

95


Air circuit breakers ARION WL<br />

CONFORMITY DECLARATION<br />

Assurance of issued Conformity Declarations for products made by OEZ s.r.o.<br />

presented in this catalogue according to Law No.22/97 LD and consecutive statutory rules<br />

Conformity No. Declaration of Unit Type<br />

219600/0701 Air circuit breaker - switch-disconnector ARION WL11<br />

<strong>2197</strong>00/0701 Air circuit breaker - switch-disconnector ARION WL<strong>12</strong><br />

219900/0701 Air circuit breaker - switch-disconnector ARION WL13<br />

Place of issue: Letohrad Authorized person: Ing. Jaroslav Toman<br />

Date of issue: 7. <strong>12</strong>. 2006 Position: Managing Director<br />

96


OEZ s.r.o.<br />

Šedivská 339<br />

561 51 Letohrad<br />

Czech Republic<br />

tel.: +420 465 672 379<br />

fax: +420 465 672 398<br />

e-mail: oeztrade@oez.cz<br />

www.oez.com<br />

OEZ s.r.o.<br />

Trade Office Prague<br />

Podnikatelská 547<br />

190 11 Prague 9<br />

Czech Republic<br />

tel.: +420 257 181 710<br />

fax: +420 235 315 026<br />

e-mail: oeztrade@oez.cz<br />

www.oez.com<br />

OEZ Slovakia, spol. s r.o.<br />

Rybničná 36c<br />

831 07 Bratislava<br />

Slovakia<br />

tel.: +421 2 44 87 27 66-9<br />

fax: +421 2 44 87 27 70<br />

e-mail: info@oez.sk<br />

www.oez.sk<br />

OEZ Deutschland GmbH<br />

Hagenower Strasse 73<br />

190 61 Schwerin<br />

Germany<br />

tel.: +49 385 39 93 305<br />

fax: +49 385 39 93 307<br />

e-mail: info@oez-deutschland.de<br />

www.oez-deutschland.de<br />

OOO “OEZ-R“<br />

3. Tverskaya-Yamskaya 36/40<br />

<strong>12</strong>5047 Moscow<br />

Russian Federation<br />

tel.: +7 499 978 26 45<br />

fax: +7 495 783 66 96<br />

e-mail: sales@oez.ru<br />

www.oez.ru<br />

OEZ Polska Sp. z o.o.<br />

Czereśniowa 19<br />

02-457 Warszawa<br />

Poland<br />

tel.: +48 22 863 15 21<br />

fax: +48 22 863 71 82<br />

e-mail: info@oez.pl<br />

www.oez.pl<br />

DP ”OEZ Ukraine”<br />

Vasilkovskaya 34, of. A-208<br />

03022 Kiev<br />

Ukraine<br />

tel./fax: +38 044 455 71 62/63/64/65<br />

e-mail: ukr@oez.cz<br />

www.oez.cz


VJ1-2007-A<br />

WWW.OEZ.COM<br />

Any changes reserved


Appendix of the catalogue<br />

Air circuit breakers Arion WL (VJ1-2007-A)<br />

by new design of Arion WL11<br />

Arion<br />

Air circuit breakers


www.oez.com


Arion<br />

CONTENT – Commercial information<br />

DATA FOR SELECTION OF CIRCUIT BREAKER AND SWITCH-DISCONNECTOR .........................................................2<br />

DATA FOR SELECTION OF OVERCURRENT RELEASE .....................................................................................................3<br />

MEANING OF TYPE DESIGNATION POSITIONS ..............................................................................................................4<br />

QUICK COMPOSITION OF TYPE DESIGNATION ...............................................................................................................5<br />

COMPOSITION OF TYPE DESIGNATION 3-pole circuit breakers, switch-disconnectors for AC operation<br />

Fixed design ..................................................................................................................................................................6<br />

Withdrawable design ....................................................................................................................................................7<br />

COMPOSITION OF TYPE DESIGNATION 4-pole circuit breakers, switch-disconnectors for AC operation<br />

Fixed design ..................................................................................................................................................................8<br />

Withdrawable design ....................................................................................................................................................9<br />

BASIC ACCESSORIES - drives, auxiliary releases and switches ............................................................................10<br />

CONTENT – Technical information<br />

AIR CIRCUIT BREAKERS, SWITCH-DISCONNECTORS<br />

- specifications ............................................................................................................................................................11<br />

- connection ................................................................................................................................................................13<br />

- dimensions ...............................................................................................................................................................14<br />

GLOSSARY ................................................................................................................................................................................17<br />

1


Arion<br />

Commercial information<br />

DATA FOR SELECTION OF CIRCUIT BREAKERS<br />

››› for AC operation<br />

Size<br />

I<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

Rated operating voltage U e<br />

690 V a.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated short-circuit ultimate<br />

breaking capacity<br />

I cu<br />

N - 55 kA/415 V a.c.<br />

S - 66 kA/415 V a.c.<br />

H - 85 kA/415 V a.c.<br />

Rated short-time withstand current I cw<br />

N - 42 kA /1 s<br />

S - 50 kA/1 s<br />

H - 66 kA/1 s<br />

Rated short-circuit making capacity I cm<br />

N - <strong>12</strong>1 kA/415 V a.c.<br />

S - 145 kA/415 V a.c.<br />

H - 187 kA/415 V a.c.<br />

Number of poles 3, 4<br />

Max. rated current of the circuit breaker<br />

I n<br />

[A]<br />

Rated short-circuit ultimate<br />

breaking capacity<br />

I cu<br />

at 415 V [kA] a.c.<br />

fi x e d<br />

3/4 pole<br />

Dimensions<br />

withdrawable<br />

3/4 pole<br />

630<br />

291 / 291<br />

385 / 385<br />

depth<br />

800<br />

Size I<br />

1000<br />

<strong>12</strong>50<br />

1600<br />

N S H<br />

55 66 85<br />

440.5 / 440.5<br />

320 / 410<br />

468.5 / 468.5<br />

320 / 410<br />

height<br />

width<br />

2000<br />

NEWS<br />

NEWS<br />

DATA FOR SELECTION OF SWITCH-DISCONNECTOR<br />

››› for AC operation<br />

Size<br />

I<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

Rated operating voltage U e<br />

690 V a.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated short-circuit making capacity I cm<br />

N - <strong>12</strong>1 kA/415 V a.c.<br />

S - 145 kA/415 V a.c.<br />

H - 187 kA/415 V a.c.<br />

Rated short-time withstand current I cw<br />

N - 42 kA/1 s<br />

S - 50 kA/1 s<br />

H - 66 kA/1 s<br />

Number of poles 3, 4<br />

2


Commercial information<br />

Arion<br />

DATA FOR SELECTION OF OVERCURRENT RELEASE<br />

Rating Plug<br />

I R<br />

I sd<br />

t sd<br />

Overcurrent release name ETU15B ETU25B ETU27B ETU45B ETU76B<br />

Overload protection L + + + + +<br />

Short-time delayed short-circuit protection S – + + + +<br />

Instantaneous short-circuit protection I + + + + +<br />

Neutral conductor protection N – – + + +<br />

Earth fault protection G – – + • •<br />

Additional functions +<br />

Neutral conductor protection ON/OFF – – +/+ +/+ +/+<br />

Short-time delayed short-circuit protection ON/OFF – – – +/+ +/+<br />

Instantaneous short-circuit protection ON/OFF – – – +/+ +/+<br />

Thermal memory ON/OFF – – – + +<br />

Load guarding – – – + +<br />

Short-time delayed short-circuit protection<br />

switchable to I 2 t<br />

– – – + +<br />

Instantaneous short-circuit protection adjustable + – – + +<br />

Overload protection switchable to I 4 t – – – + +<br />

Overload protection ON/OFF – – – – +<br />

Adjustable neutral conductor protection N – – – + +<br />

Switchable parameter sets – – – – +<br />

Parameterization and display<br />

Parameterization by rotary switches (10 positions) + + + + –<br />

Parameterization by means of communication<br />

(absolute values)<br />

– – – – +<br />

Parameterization by means of menu (absolute values) – – – – +<br />

Remote parameterization of basic functions – – – – +<br />

Remote parameterization of additional functions – – – + +<br />

4-line LCD – – – • –<br />

Graphic LCD – – – – +<br />

Measuring function<br />

Measuring function Plus – – – • •<br />

Communication<br />

CubicleBUS – – – + +<br />

PROFIBUS-DP/MODBUS – – – • •<br />

Ethernet – – – • •<br />

+ YES, – NO, • Optional<br />

3


Arion<br />

Commercial information<br />

MEANING OF TYPE DESIGNATION POSITIONS<br />

Example of type designation: ARION WL1<strong>12</strong>0-3CB36-4GA2-Z K07<br />

Position number: 5 6 - 7 8 9 - 10 11 <strong>12</strong> 13 14 15 16<br />

Type designation: ARION WL1 1 20 - 3 CB 3 6 - 4 G A 2 - Z K07<br />

Size<br />

Rated current<br />

Rated short-circuit ultimate breaking capacity<br />

Overcurrent release<br />

Number of poles<br />

Design and type of connection<br />

Drive<br />

1st auxiliary release<br />

2nd auxiliary release<br />

Auxiliary switches<br />

Accessories (it is possible to fill in more codes at a time separated by plus sign)<br />

ARION WL1<strong>12</strong>0-3CB36-4GA2-Z K07<br />

Parameters and description of circuit breaker according to positions:<br />

5) size I<br />

6 - 7) rated current I n<br />

= 2000 A<br />

8) rated short-circuit ultimate breaking capacity I cu<br />

= 80 kA<br />

9 - 10) overcurrent release ETU25B<br />

11) 3-pole design<br />

<strong>12</strong>) withdrawable design, rear horizontal connection<br />

13) hand and motor drive with closing release for 230 V a.c./220 V d.c.<br />

14) shunt trip 230 V a.c./220 V d.c.<br />

15) without 2nd auxiliary release<br />

16) 2NO + 2NC auxiliary contacts<br />

Accessory code - signal switch „switched off by overcurrent release“ - K07<br />

STANDARD EQUIPMENT OF CIRCUIT BREAKER/SWITCH-DISCONNECTOR<br />

Each circuit breaker/switch-disconnector has the following standard equipment<br />

Fixed design<br />

• Push-button for mechanical ON<br />

• Push-button for mechanical OFF<br />

• Hand drive with storage device<br />

• Mechanical indicator of circuit breaker state - ON/OFF state<br />

• Mechanical storage device state - wound up/released<br />

• Mechanical indicator „ready-to-close“<br />

• Auxiliary switches - 2NO + 2NC contacts<br />

• Terminal blocks and connectors for connection of auxiliary circuits -<br />

the circuit breaker/switch-disconnector is always equipped with all necessary<br />

terminal blocks and connectors; terminal block has screw terminals<br />

• Mechanical indicator of switching off by overcurrent release<br />

• Mechanical interlocking of reset after switching off by overcurrent release<br />

Withdrawable design - withdrawable design contains additionally:<br />

• Mechanical indicator of the circuit breaker position in the<br />

withdrawable device<br />

• Locking device against shifting of circuit breaker using a padlock<br />

4


Commercial information<br />

Arion<br />

QUICK COMPOSITION OF TYPE DESIGNATION<br />

The table can be used for quick and simple selection and composition of type designation of a circuit breaker/switch-disconnector ARION WL.<br />

The table contains only common types of circuit breakers/switch-disconnectors. For complete offer, use the catalogue.<br />

Type designation ARION WL1 1 20 - 3 CB 3 6 - 4 G A 2 - Z K07<br />

Size<br />

size I from 630 to 2000 A 1<br />

size II from 800 to 3200 A 2<br />

size III from 4000 to 6300 A 3<br />

Rated current<br />

630 A only size I 06<br />

800 A recommended size I 08<br />

1000 A recommended size I 10<br />

<strong>12</strong>50 A recommended size I <strong>12</strong><br />

1600 A recommended size I 16<br />

2000 A only size I 20<br />

2000 A only size II 20<br />

2500 A only size II 25<br />

3200 A only size II 32<br />

4000 A only size II 40<br />

4000 A only size III 40<br />

5000 A only size III 50<br />

6300 A only size III 63<br />

Rated short-circuit ultimate breaking capacity<br />

N – ECO 55 kA for size I, 66 kA for size II 2<br />

S – STANDARD 80 kA for size II, 66 kA for size I 3<br />

H – HIGH 85 kA for size I, 100 kA for size II and size III 4<br />

C – EXTRA 150 kA for size III (3-pole), 130 kA for size III (4-pole) 5<br />

Overcurrent release<br />

without overcurrent release Switch-disconnector AA<br />

ETU25B Circuit breaker CB<br />

ETU45B - without display Circuit breaker EB<br />

ETU45B - with display Circuit breaker FB<br />

ETU76B - with graphic display Circuit breaker NB<br />

Design<br />

3 – pole 3<br />

4 – pole 4<br />

Design<br />

fixed rear vertical connection 1<br />

fixed rear horizontal connection 2<br />

fixed front connection 4<br />

withdrawable rear horizontal connection 6<br />

withdrawable rear vertical connection 7<br />

Drive<br />

hand drive 1<br />

hand and motor drive, closing release 230 V a.c./220 V d.c. 4<br />

hand and motor drive, closing release 110 V a.c./d.c. 5<br />

hand and motor drive, closing release 24 V d.c. 6<br />

1st auxiliary release<br />

without 1st auxiliary release A<br />

shunt trip 24 V d.c. B<br />

shunt trip 110 V a.c./d.c. F<br />

shunt trip 230 V a.c./220 V d.c. G<br />

2nd auxiliary release<br />

without 2nd auxiliary release A<br />

shunt trip 24 V d.c. B<br />

shunt trip 110 V a.c./d.c. F<br />

shunt trip 230 V a.c./220 V d.c. G<br />

undervoltage release 24 V d.c. J<br />

undervoltage release 110 V a.c./d.c. M<br />

undervoltage release 230 V a.c./220 V d.c. N<br />

Auxiliary switches<br />

2 NO + 2 NC 2<br />

4 NO + 4 NC 4<br />

Accessories (it is possible to fill in more codes at a time separated by plus sign)<br />

Electrical ON push-button on the front panel C11<br />

Signal switch of the storage device state C20<br />

Signal switch „ready-to-close” C22<br />

Signal switch „switched off by release“ K07<br />

Position signal switches in the withdrawable device R15<br />

Door sealing frame T40<br />

Locking device against unauthorized closing on the front control panel S01<br />

• Example of type designation: ARION WL1<strong>12</strong>0-3CB36-4GA2-Z K07<br />

5


Arion<br />

Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Fixed design, 3-pole, AC<br />

Rear horizontal connections<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/415 V<br />

[A]<br />

55 kA – size I 66 kA – size I 85 kA – size I<br />

N S H<br />

630 ARION WL1106-232- ARION WL1106-332- ARION WL1106-432-<br />

800 ARION WL1108-232- ARION WL1108-332- ARION WL1108-432-<br />

1000 ARION WL1110-232- ARION WL1110-332- ARION WL1110-432-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-232- ARION WL11<strong>12</strong>-332- ARION WL11<strong>12</strong>-432-<br />

1600 ARION WL1116-232- ARION WL1116-332- ARION WL1116-432-<br />

2000 ARION WL1<strong>12</strong>0-232- ARION WL1<strong>12</strong>0-332- ARION WL1<strong>12</strong>0-432-<br />

<br />

Rear vertical connections<br />

630 ARION WL1106-231- ARION WL1106-331- ARION WL1106-431-<br />

800 ARION WL1108-231- ARION WL1108-331- ARION WL1108-431-<br />

1000 ARION WL1110-231- ARION WL1110-331- ARION WL1110-431-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-231- ARION WL11<strong>12</strong>-331- ARION WL11<strong>12</strong>-431-<br />

1600 ARION WL1116-231- ARION WL1116-331- ARION WL1116-431-<br />

2000 ARION WL1<strong>12</strong>0-231- ARION WL1<strong>12</strong>0-331- ARION WL1<strong>12</strong>0-431-<br />

<br />

Front connections one series of holes<br />

630 ARION WL1106-233- ARION WL1106-333- -<br />

800 ARION WL1108-233- ARION WL1108-333- -<br />

1000 ARION WL1110-233- ARION WL1110-333- -<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-233- ARION WL11<strong>12</strong>-333- -<br />

1600 ARION WL1116-233- ARION WL1116-333- -<br />

2000 - - -<br />

<br />

Front connections two series of holes<br />

630 ARION WL1106-234- ARION WL1106-334- ARION WL1106-434-<br />

800 ARION WL1108-234- ARION WL1108-334- ARION WL1108-434-<br />

1000 ARION WL1110-234- ARION WL1110-334- ARION WL1110-434-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-234- ARION WL11<strong>12</strong>-334- ARION WL11<strong>12</strong>-434-<br />

1600 ARION WL1116-234- ARION WL1116-334- ARION WL1116-434-<br />

2000 ARION WL1<strong>12</strong>0-234- ARION WL1<strong>12</strong>0-334- ARION WL1<strong>12</strong>0-434-<br />

<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective functionLSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

NB<br />

DG<br />

EG<br />

FG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2NO + 2NC)<br />

(you will find other accessories on page 10)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker.<br />

If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page <strong>12</strong> (only for AC applications).<br />

3)<br />

Measuring current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

• For weight see page. <strong>12</strong><br />

6


Commercial information<br />

Arion<br />

COMPOSITION OF TYPE DESIGNATION<br />

3P<br />

Withdrawable design, 3-pole, AC<br />

Rear horizontal connections<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/415 V<br />

[A]<br />

55 kA – size I 66 kA – size I 85 kA – size I<br />

N S H<br />

630 ARION WL1106-236- ARION WL1106-336- ARION WL1106-436-<br />

800 ARION WL1108-236- ARION WL1108-336- ARION WL1108-436-<br />

1000 ARION WL1110-236- ARION WL1110-336- ARION WL1110-436-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-236- ARION WL11<strong>12</strong>-336- ARION WL11<strong>12</strong>-436-<br />

1600 ARION WL1116-236- ARION WL1116-336- ARION WL1116-436-<br />

2000 ARION WL1<strong>12</strong>0-236- ARION WL1<strong>12</strong>0-336- ARION WL1<strong>12</strong>0-436-<br />

<br />

Without withdrawable device<br />

630 ARION WL1106-235- ARION WL1106-335- ARION WL1106-435-<br />

800 ARION WL1108-235- ARION WL1108-335- ARION WL1108-435-<br />

1000 ARION WL1110-235- ARION WL1110-335- ARION WL1110-435-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-235- ARION WL11<strong>12</strong>-335- ARION WL11<strong>12</strong>-435-<br />

1600 ARION WL1116-235- ARION WL1116-335- ARION WL1116-435-<br />

2000 ARION WL1<strong>12</strong>0-235- ARION WL1<strong>12</strong>0-335- ARION WL1<strong>12</strong>0-435-<br />

Rear vertical connections<br />

630 ARION WL1106-237- ARION WL1106-337- ARION WL1106-437-<br />

800 ARION WL1108-237- ARION WL1108-337- ARION WL1108-437-<br />

1000 ARION WL1110-237- ARION WL1110-337- ARION WL1110-437-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-237- ARION WL11<strong>12</strong>-337- ARION WL11<strong>12</strong>-437-<br />

1600 ARION WL1116-237- ARION WL1116-337- ARION WL1116-437-<br />

2000 ARION WL1<strong>12</strong>0-237- ARION WL1<strong>12</strong>0-337- ARION WL1<strong>12</strong>0-437-<br />

<br />

Rear flanged connections<br />

630 ARION WL1106-238- ARION WL1106-338- ARION WL1106-438-<br />

800 ARION WL1108-238- ARION WL1108-338- ARION WL1108-438-<br />

1000 ARION WL1110-238- ARION WL1110-338- ARION WL1110-438-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-238- ARION WL11<strong>12</strong>-338- ARION WL11<strong>12</strong>-438-<br />

1600 ARION WL1116-238- ARION WL1116-338- ARION WL1116-438-<br />

2000 ARION WL1<strong>12</strong>0-238- ARION WL1<strong>12</strong>0-338- ARION WL1<strong>12</strong>0-438-<br />

<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSIN, grafický displej 3)<br />

Overcurrent release - with earth fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

NB<br />

DG<br />

EG<br />

FG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2NO + 2NC)<br />

(you will find other accessories on page 10)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker.<br />

If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page <strong>12</strong> (only for AC applications).<br />

3)<br />

Measuring current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

• For weight see page <strong>12</strong><br />

7


Arion<br />

Commercial information<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Fixed design, 4-pole, AC<br />

Rear horizontal connections<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/415 V<br />

[A]<br />

55 kA – size I 66 kA – size I 85 kA – size I<br />

N S H<br />

630 ARION WL1106-242- ARION WL1106-342- ARION WL1106-442-<br />

800 ARION WL1108-242- ARION WL1108-342- ARION WL1108-442-<br />

1000 ARION WL1110-242- ARION WL1110-342- ARION WL1110-442-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-242- ARION WL11<strong>12</strong>-342- ARION WL11<strong>12</strong>-442-<br />

1600 ARION WL1116-242- ARION WL1116-342- ARION WL1116-442-<br />

2000 ARION WL1<strong>12</strong>0-242- ARION WL1<strong>12</strong>0-342- ARION WL1<strong>12</strong>0-442-<br />

<br />

Rear vertical connections<br />

630 ARION WL1106-241- ARION WL1106-341- ARION WL1106-441-<br />

800 ARION WL1108-241- ARION WL1108-341- ARION WL1108-441-<br />

1000 ARION WL1110-241- ARION WL1110-341- ARION WL1110-441-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-241- ARION WL11<strong>12</strong>-341- ARION WL11<strong>12</strong>-441-<br />

1600 ARION WL1116-241- ARION WL1116-341- ARION WL1116-441-<br />

2000 ARION WL<strong>12</strong>20-241- ARION WL<strong>12</strong>20-341- ARION WL<strong>12</strong>20-441-<br />

<br />

Front connections one series of holes<br />

630 ARION WL1106-243- ARION WL1106-343- -<br />

800 ARION WL1108-243- ARION WL1108-343- -<br />

1000 ARION WL1110-243- ARION WL1110-343- -<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-243- ARION WL11<strong>12</strong>-343- -<br />

1600 ARION WL1116-243- ARION WL1116-343- -<br />

2000 - - -<br />

<br />

Front connections two series of holes<br />

630 ARION WL1106-244- ARION WL1106-344- ARION WL1106-444-<br />

800 ARION WL1108-244- ARION WL1108-344- ARION WL1108-444-<br />

1000 ARION WL1110-244- ARION WL1110-344- ARION WL1110-444-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-244- ARION WL11<strong>12</strong>-344- ARION WL11<strong>12</strong>-444-<br />

1600 ARION WL1116-244- ARION WL1116-344- ARION WL1116-444-<br />

2000 ARION WL<strong>12</strong>20-244- ARION WL<strong>12</strong>20-344- ARION WL<strong>12</strong>20-444-<br />

<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

NB<br />

DG<br />

EG<br />

FG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2NO + 2NC)<br />

(you will find other accessories on page 10)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker.<br />

If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page <strong>12</strong> (only for AC applications).<br />

3)<br />

Internal measuring current transformer for protection of N conductor can be ordered with „F23“ code, see page 32 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

• For weight see page. <strong>12</strong><br />

8


Commercial information<br />

Arion<br />

COMPOSITION OF TYPE DESIGNATION<br />

4P<br />

Withdrawable design, 4-pole, AC<br />

Rear horizontal connections<br />

Rated current I 1)<br />

n<br />

Rated short-circuit ultimate breaking capacity I cu<br />

/415 V<br />

[A]<br />

55 kA – size I 66 kA – size I 85 kA – size I<br />

N S H<br />

630 ARION WL1106-246- ARION WL1106-346- ARION WL1106-446-<br />

800 ARION WL1108-246- ARION WL1108-346- ARION WL1108-446-<br />

1000 ARION WL1110-246- ARION WL1110-346- ARION WL1110-446-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-246- ARION WL11<strong>12</strong>-346- ARION WL11<strong>12</strong>-446-<br />

1600 ARION WL1116-246- ARION WL1116-346- ARION WL1116-446-<br />

2000 ARION WL1<strong>12</strong>0-246- ARION WL1<strong>12</strong>0-346- ARION WL1<strong>12</strong>0-446-<br />

<br />

Without withdrawable device<br />

630 ARION WL1106-245- ARION WL1106-345- ARION WL1106-445-<br />

800 ARION WL1108-245- ARION WL1108-345- ARION WL1108-445-<br />

1000 ARION WL1110-245- ARION WL1110-345- ARION WL1110-445-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-245- ARION WL11<strong>12</strong>-345- ARION WL11<strong>12</strong>-445-<br />

1600 ARION WL1116-245- ARION WL1116-345- ARION WL1116-445-<br />

2000 ARION WL1<strong>12</strong>0-245- ARION WL1<strong>12</strong>0-345- ARION WL1<strong>12</strong>0-445-<br />

Rear vertical connections<br />

630 ARION WL1106-247- ARION WL1106-347- ARION WL1106-447-<br />

800 ARION WL1108-247- ARION WL1108-347- ARION WL1108-447-<br />

1000 ARION WL1110-247- ARION WL1110-347- ARION WL1110-447-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-247- ARION WL11<strong>12</strong>-347- ARION WL11<strong>12</strong>-447-<br />

1600 ARION WL1116-247- ARION WL1116-347- ARION WL1116-447-<br />

2000 ARION WL1<strong>12</strong>0-247- ARION WL1<strong>12</strong>0-347- ARION WL1<strong>12</strong>0-447-<br />

<br />

Rear flanged connections<br />

630 ARION WL1106-248- ARION WL1106-348- ARION WL1106-448-<br />

800 ARION WL1108-248- ARION WL1108-348- ARION WL1108-448-<br />

1000 ARION WL1110-248- ARION WL1110-348- ARION WL1110-448-<br />

<strong>12</strong>50 ARION WL11<strong>12</strong>-248- ARION WL11<strong>12</strong>-348- ARION WL11<strong>12</strong>-448-<br />

1600 ARION WL1116-248- ARION WL1116-348- ARION WL1116-448-<br />

2000 ARION WL1<strong>12</strong>0-248- ARION WL1<strong>12</strong>0-348- ARION WL1<strong>12</strong>0-448-<br />

<br />

Switch-disconnector unit (switch-disconnector) 2)<br />

Overcurrent release - without earth fault protection (circuit breaker)<br />

Overcurrent release ETU15B – protective function LI<br />

Overcurrent release ETU25B – protective function LSI<br />

Overcurrent release ETU45B – protective function LSIN 3)<br />

Overcurrent release ETU45B – protective function LSIN, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSIN, graphic display 3)<br />

Overcurrent release - with earth fault protection (circuit breaker)<br />

Overcurrent release ETU27B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING 3)<br />

Overcurrent release ETU45B – protective function LSING, with display, number of lines 4 3)<br />

Overcurrent release ETU76B – protective function LSING, graphic display 3)<br />

AA<br />

BB<br />

CB<br />

EB<br />

FB<br />

NB<br />

DG<br />

EG<br />

FG<br />

NG<br />

1AA2<br />

Standard type designation<br />

Hand drive with mechanical closing<br />

Auxiliary switches: contacts 2200 (2NO + 2NC)<br />

(you will find other accessories on page 10)<br />

1)<br />

Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker.<br />

If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

2)<br />

Permissible short-time withstand current I cw<br />

and rated short-circuit making capacity I cm<br />

of a switch-disconnector see page <strong>12</strong> (only for AC applications).<br />

3)<br />

Internal measuring current transformer for protection of N conductor can be ordered with „F23“ code, see page 32 in the catalogue Air circuit breakers Arion VJ1-2007-A.<br />

• For weight see page <strong>12</strong><br />

9


Arion<br />

Commercial information<br />

BASIC ACCESSORIES 3P 4P<br />

Selected type designation ARION WL1--<br />

Hand drives with mechanical closing 1<br />

Hand drives with electrical closing – closing release: load factor 100 %<br />

110 V a.c./110 V d.c. 2<br />

230 V a.c./220 V d.c. 3<br />

Motor and hand drives with electrical closing – closing release: load factor 100 % - for permanent load<br />

230 V a.c./220 V d.c. 4<br />

110 V a.c./d.c. 5<br />

24 V d.c. 6<br />

- different operating voltages for motor drive and closing release<br />

1st auxiliary release<br />

Without 1st auxiliary release<br />

A<br />

Shunt trips – load factor 100 % - for permanent load<br />

24 V d.c. B<br />

30 V d.c. C<br />

48 V d.c. D<br />

60 V d.c. E<br />

110 V a.c./d.c. F<br />

230 V a.c./220 V d.c. G<br />

2nd auxiliary release<br />

Without 2nd auxiliary release<br />

A<br />

Shunt trips – load factor 100 % - for permanent load<br />

24 V d.c. B<br />

30 V d.c. C<br />

48 V d.c. D<br />

60 V d.c. E<br />

110 V a.c./d.c. F<br />

230 V a.c./220 V d.c. G<br />

Undervoltage releases – short-time delayed 80 or 200 ms<br />

24 V d.c. J<br />

30 V d.c. K<br />

48 V d.c. L<br />

60 V d.c. U<br />

110 V a.c./d.c. M<br />

230 V a.c./220 V d.c. N<br />

400 V a.c. P<br />

Undervoltage releases – delayed 0.2 ÷ 3.2 s<br />

48 V d.c. Q<br />

110 V a.c./d.c. R<br />

230 V a.c./220 V d.c. S<br />

400 V a.c. T<br />

Auxiliary switches<br />

2NO + 2NC 2<br />

4NO + 4NC 4<br />

6NO + 2NC 7<br />

5NO + 3NC 8<br />

10


Technical information<br />

Arion<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P<br />

Specifications<br />

Type<br />

ARION WL11...<br />

Size<br />

I<br />

Standards EN 60947-2<br />

IEC 60947-2<br />

DIN VDE 0660 section 101<br />

Approval marks<br />

Size I<br />

Number of poles 3, 4<br />

Rated current I n<br />

630 A<br />

800 A<br />

1000 A<br />

<strong>12</strong>50 A<br />

1600 A<br />

2000 A<br />

Rated operating voltage U e<br />

690 V a.c.<br />

Rated frequency f n<br />

50/60 Hz<br />

Rated pulse voltage - main current path U imp<br />

<strong>12</strong> kV<br />

- auxiliary circuits 4 kV<br />

- control circuits 2.5 kV<br />

Rated insulation voltage U i<br />

1000 V<br />

Utilization category (selectivity)<br />

B<br />

Rated short-time withstand current I cw<br />

See the table on page <strong>12</strong><br />

Rated short-circuit ultimate breaking capacity I cu<br />

See the table on page <strong>12</strong><br />

Rated short-circuit service breaking capacity I cs<br />

100% I cu<br />

Rated short-circuit making capacity I cm<br />

See the table on page <strong>12</strong><br />

Switching off time at I cu<br />

50 ms 1)<br />

Mechanical switching on time<br />

35 ms<br />

Mechanical switching off time<br />

38 ms<br />

Switching off time by shunt trip<br />

73 ms<br />

Switching off time by undervoltage release<br />

73 ms<br />

Switching on time by closing release<br />

80 ms<br />

Power loss at I n<br />

See the table on page <strong>12</strong><br />

Mechanical endurance<br />

- without maintenance 10 000 cycles<br />

(for I cu<br />

55, 66 kA/415 V a.c.)<br />

- with maintenance 3) 20 000 cycles (up to 1600 A), 15 000 cycles (2000 A)<br />

Electrical endurance<br />

- without maintenance (U e<br />

= 1000 V) 10 000 cycles (up to 1600 A), 7 500 cycles (2000 A)<br />

(for I cu<br />

55, 66 kA/415 V a.c.)<br />

- with maintenance 3) 20 000 cycles (up to 1600 A), 15 000 cycles (2000 A)<br />

Mechanical endurance<br />

- without maintenance 10 000 cycles<br />

(for I cu<br />

85 kA/415 V a.c.)<br />

- with maintenance 3) 15 000 cycles<br />

Electrical endurance<br />

- without maintenance 7 500 cycles<br />

(for I cu<br />

85 kA/415 V a.c.)<br />

- with maintenance 3) 15 000 cycles (3P), 10 000 cycles (4P)<br />

Switching frequency U e<br />

= 690 V a.c. (1000 V a.c.) 60 cycles/h<br />

Minimum dwell between circuit breaker switching off<br />

80 ms 2)<br />

by overcurrent release and subsequent reclosing<br />

Degree of protection<br />

IP20, IP41 with sealing frame, IP55 with transparent cover<br />

Reference ambient temperature 40 °C<br />

Ambient temperature range operation -25 °C ÷ +70 °C<br />

(it is necessary to observe special conditions for LCD) storage -40 °C ÷ +70 °C<br />

Sea level<br />

2000 m<br />

Climatic resistance IEC 68 section 30-20<br />

Weight m See the table on page <strong>12</strong><br />

1)<br />

- with ETU15B switching off time is 85 ms<br />

2)<br />

- only with automatic reset of reclosing blocking<br />

- circuit breakers of size I with I cu<br />

= H can operate in IT networks up to 690 a.c.<br />

3)<br />

- at replacement of main contacts and arc chutes<br />

11


Arion<br />

Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P<br />

Parameters<br />

Rated short-time withstand current I cw<br />

1)<br />

Size - Type<br />

I – ARION WL11…<br />

Designation of breaking capacity N S H<br />

0,5 s 50 kA 66 kA 75<br />

1 s 42 kA 50 kA 66<br />

2 s 29.5 kA 35 kA 46<br />

3 s 24 kA 29 kA 37<br />

1)<br />

- at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Rated short-circuit ultimate breaking capacity I cu<br />

1)<br />

Size - Type<br />

I – ARION WL11…<br />

Designation of breaking capacity N S H<br />

415 V a.c., 500 V a.c. 55 kA 66 kA 85 kA<br />

690 V a.c. 42 kA 50 kA 66 kA<br />

1)<br />

- at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Rated short-circuit ultimate making capacity I cm<br />

1)<br />

Size - Type<br />

I – ARION WL11…<br />

Designation of breaking capacity N S H<br />

415 V a.c., 500 V a.c. <strong>12</strong>1 kA 145 kA 187 kA<br />

690 V a.c. 88 kA 105 kA 145 kA<br />

1)<br />

- at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Rated conditional short-circuit current I 1)<br />

cc<br />

Size - Type<br />

I – ARION WL11…<br />

Designation of breaking capacity N S H<br />

500 V a.c. 55 kA 66 kA 75 kA<br />

690 V a.c. 42 kA 50 kA 66 kA<br />

1)<br />

- at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)<br />

Losses at I n<br />

- per 3 pole<br />

Type Fixed design Withdrawable design<br />

ARION WL1106… 100 W 195 W<br />

ARION WL1108… 100 W 195 W<br />

ARION WL1110… 100 W 195 W<br />

ARION WL11<strong>12</strong>… 105 W 205 W<br />

ARION WL1116… 150 W 350 W<br />

ARION WL1<strong>12</strong>0… 240 W 440 W<br />

Weight<br />

Type 3-pole 4-pole<br />

Fixed design<br />

Withdrawable circuit breaker<br />

+ withdrawable device<br />

Fixed design<br />

Withdrawable circuit breaker<br />

+ withdrawable device<br />

ARION WL1106… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

ARION WL1108… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

ARION WL1110… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

ARION WL11<strong>12</strong>… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

ARION WL1116… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

ARION WL1<strong>12</strong>0… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg<br />

Maximum load of the circuit breaker/switch-disconnector depending on ambient temperature<br />

Type 55 °C 60 °C 70 °C<br />

ARION WL1106… 630 A 630 A 630 A<br />

ARION WL1108… 800 A 800 A 800 A<br />

ARION WL1110… 1000 A 1000 A 1000 A<br />

ARION WL11<strong>12</strong>… <strong>12</strong>50 A <strong>12</strong>50 A <strong>12</strong>10 A<br />

ARION WL1116… 1600 A 1600 A 1490 A<br />

ARION WL1<strong>12</strong>0… 2000 A 1930 A 1780 A<br />

<strong>12</strong>


Technical information<br />

Arion<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Connection and installation<br />

Recommended dimensions of main connections<br />

and min. cross-sections<br />

Type<br />

Dimensions<br />

Cu busbars [mm]<br />

Min. cross-section [mm 2 ]<br />

ARION WL1106... 1x 60 x 10 600<br />

ARION WL1108... 1x 60 x 10 600<br />

ARION WL1110... 1x 60 x 10 600<br />

ARION WL11<strong>12</strong>... 2x 40x10 800<br />

ARION WL1116... 2x 50 x 10 1000<br />

ARION WL1<strong>12</strong>0... 3x 50x10 1500<br />

Main (power) circuit<br />

- is connected by Cu busbars<br />

- to extend connection options, use connecting sets see „types of main connections“<br />

- reverse connection is possible (inversion of input and output terminals) without limitation<br />

of rated ultimate short-circuit breaking capacity I cu<br />

- we recommend to coat the busbars with paint<br />

- input and output conductors/busbars must be reinforced mechanically to eliminace transfer<br />

of electrodynamic forces into circuit breaker/switch-disconnector at short-circuits see fig.<br />

Rear horizontal connection<br />

Rear vertical connection<br />

Rear flanged connection<br />

Front connection one series of holes<br />

Front connection two series of holes<br />

Types of main connections<br />

Fixed design<br />

<br />

<br />

<br />

<br />

Rear horizontal connection<br />

Front connection one series<br />

of holes - custom delivery<br />

Front connection two series<br />

of holes<br />

Rear vertical connection<br />

Withdrawable design<br />

<br />

<br />

<br />

<br />

<br />

Rear horizontal connection<br />

Front connection one series<br />

of holes - custom delivery<br />

Front connection two series<br />

of holes<br />

Rear vertical connection<br />

Rear flanged connection<br />

- custom delivery<br />

13


Arion<br />

Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - fixed design<br />

Rear horizontal connection<br />

5) 4)<br />

<br />

<br />

<br />

<br />

60.5<br />

<br />

33.5<br />

13.5<br />

437.5 437,5<br />

NSE00611<br />

275<br />

440.5 440,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

270 15<br />

300 10<br />

390<br />

541.5 <br />

461.5 <br />

<br />

<br />

<br />

<br />

5.5 <br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

5) 4)<br />

<br />

270 15<br />

300 10<br />

390<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

NSE00619<br />

b<br />

<br />

327.5 <br />

Front connection one series of holes<br />

13.5<br />

437.5 437,5<br />

NSE00611<br />

275<br />

440.5 440,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

Front connection two series of holes<br />

5) 4)<br />

13.5<br />

437.5 437,5<br />

275<br />

440.5 440,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

NSE00611<br />

270 15<br />

300 10<br />

390<br />

Rear vertical connection<br />

5) 4)<br />

437.5 437,5<br />

275<br />

440.5 440,5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5<br />

267.5 <br />

<strong>12</strong>7.5 <br />

<br />

3)<br />

NSE00611<br />

270 15<br />

300 10<br />

390<br />

13.5<br />

<br />

113.5 <br />

<strong>12</strong>8.5<br />

60 90 90 90<br />

4-pole design<br />

1) Installation space for replacement of arc chutes.<br />

2) Deionization space, space for connection of auxiliary circuits.<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed switchboard door.<br />

7) Fastening points for circuit breaker installation.<br />

8) Locking device against unauthorized closing, on the front control panel.<br />

9) Locking device against mechanical ON/OFF.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 10<br />

<strong>12</strong>50 ÷ 2000 A 15 15 15<br />

14


Technical information<br />

Arion<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - withdrawable design<br />

Rear horizontal connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<br />

<br />

<br />

<br />

NSE00630<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3,5 <strong>12</strong>3.5 275<br />

468,5 468.5<br />

<br />

<br />

<br />

<br />

<br />

<br />

367.5 <br />

382.5 <br />

327.5 <br />

<br />

<br />

88.5 <br />

<strong>12</strong>1.5 <br />

140.5 <br />

3)<br />

10)<br />

55<br />

15<br />

90 90 90<br />

10)<br />

13.5<br />

Front connection one series of holes<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

62.5 <br />

<br />

13.5<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

468.5 468,5<br />

<br />

<br />

<br />

169.5<br />

Front connection two series of holes<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

62.5 <br />

<br />

13.5<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

468.5 468,5<br />

<br />

<br />

<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<br />

169.5<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed switchboard door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 10<br />

<strong>12</strong>50 ÷ 2000 A 15 15 15<br />

15


Arion<br />

Technical information<br />

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P<br />

Dimensions - size I - withdrawable design<br />

Rear vertical connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<br />

13.5<br />

<br />

NSE00629<br />

b<br />

<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

468.5 468,5<br />

267.5 <br />

<strong>12</strong>7.5<br />

<br />

<br />

<br />

<br />

3)<br />

15 90 90 90<br />

Rear flanged connection<br />

320<br />

270<br />

5)<br />

4)<br />

NSE00621<br />

<strong>12</strong>3.5 <strong>12</strong>3,5 275<br />

468.5 468,5<br />

<br />

NSE00631<br />

Ø M <strong>12</strong><br />

282,5 282.5<br />

26 33<br />

3)<br />

142.5 142,5<br />

55 55 55 55<br />

59 59<br />

10)<br />

13<br />

210<br />

300<br />

30<br />

55<br />

<strong>12</strong>1<br />

NSE00632<br />

15 90 90 90<br />

4-pole design<br />

4) Connectors of auxiliary circuits with screw terminals (SIGUT).<br />

5) Connectors of auxiliary circuits with spring terminals.<br />

6) Dimension to internal surface of closed switchboard door.<br />

7) ARION WL in operating position.<br />

8) ARION WL in test position.<br />

9) ARION WL in disconnected position.<br />

10) Holes for fastening screws, diameter 10 mm.<br />

11) Contact area.<br />

Rated current Dimension a b c<br />

up to 1000 A 10 10 10<br />

<strong>12</strong>50 ÷ 2000 A 15 15 15<br />

16


Technical information<br />

Arion<br />

GLOSSARY<br />

Note: Precise wording of definitions and texts relating to a given term are detailed in the respective standards (see Name).<br />

Title Symbol Explanation<br />

Rated operating voltage<br />

EN 60947-1; 4.3.1.1<br />

U e<br />

Voltage fixed by the manufacturer. Several pertinent tests relate to its determination, as may also the utilization<br />

category. Along with the rated (operating) current, it determines the device’s utilization. The highest value of<br />

rated operating voltage may in no case be greater than the value of the rate insulation voltage U i<br />

.<br />

Rated insulation voltage<br />

EN 60947-1; 4.3.1.2<br />

Rated current<br />

EN 60947-2; 4.3.2.3<br />

U i<br />

I n<br />

Voltage measure to which are related tests of dielectric strength and creepage distance.<br />

Current value of particular circuit breaker that can be handled uninterruptedly. The highest current valued<br />

tripping the circuit breaker in conformity with a specifically stated tripping characteristic.<br />

Reduced rated current I R<br />

Specifically established, reduced value of I n<br />

current for a regulated time-dependent (thermal) release, and<br />

that the circuit breaker can handle continuously. Maximum setting is at value equal to I n<br />

. Changing I r<br />

shifts the<br />

release’s tripping characteristic along the current axis. I r<br />

= k x I n<br />

holds where k ≤ 1<br />

Tripping time at a given I r<br />

multiple t R<br />

Time after which circuit breaker will trip, if a current flows through it that is equal to the given multiple of I r<br />

.<br />

Changing t r<br />

shifts the tripping characteristic along the time axis.<br />

Release current of independent time-delayed<br />

(selective) release<br />

I sd<br />

Minimum current value causing the release’s time-independent delay to actuate.<br />

Delay of time-independent delayed release t sd<br />

If a current flows through the circuit breaker equal to at least I rmv<br />

but not reaching I rm<br />

the circuit breaker will trip<br />

with time delay t v<br />

. Total switching off time is influenced by the tripping of the circuit breaker itself and is about<br />

10 ÷ 20 ms longer.<br />

Release current of independent instantaneous<br />

(short-circuit) release<br />

Rated operating current<br />

EN 60947-1; 4.3.2.3<br />

Rated normal current<br />

EN 60947-1; 4.3.2.4<br />

Rated short-circuit ultimate breaking capacity<br />

EN 60947-2; 2.15.1; 4.3.5.2.1<br />

Rated short-circuit service breaking capacity<br />

EN 60947-2; 2.15.2; 4.3.5.2.2<br />

Rated short-time withstand current<br />

EN 60947-1; 4.3.6.1<br />

EN 60947-2; 4.3.5.4<br />

EN 60947-3; 4.3.6.1<br />

Rated conditional short-circuit current<br />

EN 60947-1; 4.3.6.4<br />

EN 60947-2; Supplement L; L.4.2<br />

I i<br />

I e<br />

I u<br />

I cu<br />

I cs<br />

I cw<br />

I cc<br />

Minimum current value causing the time-independent instantaneous release to actuate.<br />

Rated operating current of device (switch-disconnector) is fixed by the manufacturer with consideration for the<br />

rated operating voltage, rated frequency, rated operation, utilization category and type of protective cover, if that<br />

comes into consideration.<br />

Current value set by the manufacturer, and which the device can handle in continuous operation,<br />

i.e. during a period longer than 8 hours (weeks, months, or longer).<br />

Ultimate short-circuit breaking capacity value expressed as the RMS value of the alternating component of the<br />

assumed short-circuit current, that the circuit breaker must be able to manage in the mode: 1x switching off of<br />

the short-circuit and a following 1x make-break sequence. After testing, the circuit breaker need not be able to<br />

conduct the rated current uninterruptedly. I cu<br />

is set for the rated operating voltage at the rated frequency and<br />

at the established power factor for alternating current or at the time constant for direct current. Must fulfil the<br />

condition: I cu<br />

≥ I k<br />

“<br />

Value of the operating short-circuit breaking capacity expressed as the rms value of the alternating component of<br />

the assumed short-circuit current, that the circuit breaker must be able to manage in the mode: 1x switching off<br />

of the short-circuit and a following 2x make-break sequence. May also be expressed as a percentage of I cu<br />

.<br />

After testing, the circuit breaker must be able uninterruptedly to conduct the rated current and to switch off the<br />

overcurrent. Temperature increase of the main terminals may be greater. I cs<br />

is set for the rated operating voltage<br />

at the rated frequency and at the established power factor for alternating current or at the time constant for<br />

direct current. Permitted: I cs<br />

≥ I k<br />

“<br />

Value of short-time withstand current specified by the manufacturer, that the device is able to handle without<br />

damage during a designated time period (short-time delay). In case of alternating current, it is the rms value of<br />

the alternating component of the assumed short-circuit current I p<br />

.<br />

The prospective short-circuit value given by the producer that can be transferred by the device, protected against<br />

short-circuit by protective device, within its operation.<br />

Must fulfil the condition: I cc<br />

≥ I k<br />

“<br />

17


Arion<br />

Technical information<br />

GLOSSARY<br />

Note: Precise wording of definitions and texts relating to a given term are detailed in the respective standards (see Name).<br />

Title Symbol Explanation<br />

Rated short-circuit making capacity<br />

EN 60947-1; 4.3.6.2<br />

EN 60947-2; 4.3.5.1<br />

EN 60947-3; 4.3.6.2<br />

I cm<br />

Value of short-circuit making capacity specified by the manufacturer for the rated operating voltage at the rated<br />

frequency and at the established power factor for alternating current or at the time constant for direct current.<br />

It is expressed as the maximum assumed peak current.<br />

Must fulfil the condition: I cm<br />

≥ i p<br />

Initial peak short-circuit current<br />

EN 60909-0; 1.3.5<br />

Surge short-circuit current<br />

EN 60909-0; 1.3.8<br />

Prospective short-circuit current<br />

EN 60947-1; 2.5.5<br />

EN 60909-0; 1.3.3<br />

Rated impulse withstand voltage<br />

EN 60947-1; 4.3.1.3<br />

Overvoltage category<br />

EN 60947-1; 2.5.60<br />

Rated frequency<br />

EN 60947-1; 4.3.3<br />

Utilization category<br />

(circuit breakers – time selectivity)<br />

EN 60947-2; 4.4<br />

Utilization category<br />

(switch-disconnectors – switching mode)<br />

EN 60947-3; 4.4<br />

Pollution degree<br />

EN 60947-1; 2.5.58; 6.1.3.2<br />

“<br />

I k<br />

i p<br />

I p<br />

U imp<br />

f n<br />

Short-circuit current value at the moment of its arising at a given point in the electrical distribution expressed as<br />

the RMS value of the alternating symmetrical component of the assumed short-circuit current.<br />

Maximum possible momentary value of the assumed short-circuit current. (Corresponds to the moment the short<br />

arises, as a result of which there occurs the peak value of the short-circuit current.)<br />

Short-circuit current value, which would flow through the circuit if the protection device were replaced and<br />

a short-circuit were experienced by conductors with negligible impedance (In a three-phase distribution, it is<br />

assumed that the short-circuit is simultaneous in all phases.)<br />

Peak value of the voltage impulse of the prescribed form and polarity, which the device is able to withstand<br />

without failure at the established conditions and pertinent to which is the value of the separating air distance.<br />

U imp<br />

of the device must be equal to or higher than the value established for momentary overvoltage at the point<br />

in the circuit (overvoltage category) where the device is used.<br />

Numerically defined level of momentary overvoltage, i.e. overvoltage having its origin in atmospheric or<br />

switching. Standard EN 60664-1 establishes for electrical equipment the overvoltage categories:<br />

Overvoltage category IV<br />

- wiring entrance, outside lead<br />

Overvoltage category III<br />

- fixed wiring<br />

Overvoltage category II<br />

- appliances<br />

Overvoltage category I<br />

- light-current appliances<br />

Frequency of the supply network for which the device is proposed and that corresponds to its other characteristics<br />

values.<br />

Utilization category of circuit breaker establishes whether or not the circuit breaker specifically is intended<br />

for providing selectivity by means of intentional time delay (time selectivity) with other protective devices<br />

connected in series on the load side in short-circuiting conditions.<br />

Utilization category:<br />

A - circuit breakers are not specifically intended for providing time selectivity<br />

B - circuit breakers are specifically intended for providing time selectivity<br />

Utilization category defined the assumed use of switch devices (switch-disconnectors).<br />

Characterized by values of current and voltage, expressed as multiples of rated operating current and rated<br />

operating voltage, and further by power factors or time constants of the circuit.<br />

Utilization category:<br />

AC-21B (DC-21B) - infrequent switching of resistive loads, including moderate overloading<br />

AC-22B (DC-21B) - infrequent switching of mixed resistive and inductive loads, including moderate overloading<br />

AC-23B (DC-23B) - infrequent switching of motor loads or other highly inductive loads<br />

Pollution degree relates to the conditions of the surrounding environment for which the device is intended.<br />

Pollution degree:<br />

1 - No contamination will occur, or only dry, non-conducting contamination.<br />

2 - Normally occurs only non-conducting contamination, but sometimes there may occur temporary conductibility<br />

due to condensation.<br />

3 - There occurs conductive contamination or dry non-conducting contamination that with the effect of condensation<br />

will become conductive.<br />

4 - Contamination generates continuous conductibility, by means of, for example, conductive dust, rain or snow.<br />

18


Arion<br />

NOTES<br />

19


Arion<br />

NOTES<br />

20


OEZ s.r.o.<br />

Šedivská 339<br />

561 51 Letohrad<br />

Czech Republic<br />

tel.: +420 465 672 111<br />

+420 465 672 101<br />

fax: +420 465 672 398<br />

+420 465 672 151<br />

e-mail: oeztrade.cz@oez.com<br />

www.oez.com


www.oez.com<br />

VJ1-2011-A<br />

Any changes reserved