DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT - PHASE 3B ITEM DESCRIPTION QTY UNIT UNIT COST AMOUNT 3.0 CLARK SUBSTATION 230/69kV A. ELECTRICAL WORKS Supply, manufacture, factory testing, and furnishing of labor, equipment, tools and incidental materials for the delivery, assembly, erection, installation, field testing commissioning and ready for operation of the following substation equipment and its associated control and protection system and accessories Bay 85 and Bay 86 At Clark 230 kV S/S A1. Power Transformer 150 MVA Three winding autotransformer 2 sets type 3-Phase 230/69kV wye-13.8 delta with neutral earthing resistor class ONAN/ONAF1/ONAF2 , complete with all appurtenances, accessories and onload tap changing mechanism with 16 taps of 0.625% above and 16 taps of 0.625% below 0 including paralleling device and control in accordance to the requirements of the Technical Data Sheet (TDS). A2. Power Circuit Breaker Dead Tank 230kV, 3-phase, 4 sets 2000A, 40, kA three pole operation, complete with the required accessories and support structure including bushing current transformers in accordance to the requirements of the Technical Data Sheet (TDS). A3. Power Circuit Breaker Dead Tank 69kV, 3-phase, 6 sets 2000A, 38 kA three pole operation, complete with the required accessories and bushing current transformer in accordance to the requirements of the Technical Data Sheet (TDS). A4. Ganged Disconnect Switch 230kV, 3-phase, 2000A, 10 sets 40KA equipped with 460 vac 3 phase motor and manually group operated, complete with the required accessories in accordance to the requirements of the Technical Data Sheet (TDS). A5. Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 4 sets kA equipped with earthing blades, 230 vac motor and manually group operated, complete with the required accessories in accordance to the requirements of the Technical Data Sheet (TDS). A6 Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 14 sets kA equipped with, 230 vac motor and manually group operated, complete with the required accessories in accordance to the requirements of the Technical Data Sheet (TDS). A7 Voltage Transformer Capacitive type 230 kV, complete 18 sets with the required accessories and support structure in accordance to the requirements of the Technical Data Sheet (TDS). A8 Voltage Transformer 69 kV, complete with the required 30 sets accessories in accordance to the requirements of the Technical Data Sheet (TDS). A9 Surge Arresters 192 kV, station type, complete with 12 sets support structure and the required accessories in accordance to the requirements of the Technical Data Sheet (TDS). Page 2 of 15

DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT - PHASE 3B ITEM DESCRIPTION QTY UNIT UNIT COST AMOUNT A10. Surge Arresters 60 kV, station type, complete with 24 sets support structure and the required accessories in accordance to the requirements of the Technical Data Sheet (TDS). A11. Substation Gantry and Pedestal Steel Structures 1 lot including bolts, washer, etc hot dipped galvanized complete with all the required accessories in accordance to the requirements of the Technical Data Sheet (TDS) A12. Metalclad Switchgear, 13.8 kv outdoor type outdoor 2 sets type complete with arresters, VT, CT, breaker and 150 KVA 13.8/460 vac 3-phase transformer type ONAN Outdoor type in accordance to the requirements of the Technical Data Sheet (TDS) A13 Installation Materials consisting of conductors, 1 lot insulators, connectors, pole line hardwares, bus supports, and other accessories in accordance to the requirements of the Technical Data Sheet (TDS) A14 Grounding Materials consisting of insulated and bare 1 lot copper cables, lightning rod, copper rods, fittings. complete with the required materials for aerial and grounding mat and to substation equipment and structures in accordance to the requirements of the Technical Data Sheet (TDS). A15. Distribution Board 125 VDC complete with enclosure, 2 sets main breaker, Automatic transfer switch, tie breaker, branch breakers, and accessories for installation. Number of breakers to supply four (4) bays in accordance to the requirements of the Technical Data Sheet (TDS) A16. Station Service Transformer 50 kva 480/230V, three 2 sets phase, dry type and accessories in accordance to the requirements of the Technical Data Sheet (TDS). A17. Distribution Board 3 Phase 460/230 VAC with 2 sets enclosure, main breaker, tie breaker, automatic transfer switch, branch circuit and accessories Number of circuit breaker to include 4 additional bays, breaker to panel at bay 3 and 4, and spare breaker in accordance to the requirements of the Technical Data Sheet (TDS) A18. Distribution Board 3 Phase 230 VAC with enclosure , 2 sets main breaker, tie breaker, automatic transfer switch, branch circuit and accessories Number of circuit breaker for four (4) bays, breaker for panel at bays 3 and 4 and spare breaker in accordance to the requirements of the Technical Data Sheet (TDS) A19 Power Control, Instrumentation and Protection 1 lot Cables, 35kV, 15 kV and 600 volt insulation complete with insulated terminal lugs, glands, marking etc. in accordance to the requirements of the Technical Data Sheet (TDS) A20. Cable Trays (various type) hot dipped galvanized, 1 lot complete with supports, fittings, and other accessories in accordance to the requirements of the Technical Data Sheet (TDS). Cost of cable tray included at cable trenches Page 3 of 15

DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A10. Surge Arresters 60 kV, station type, complete with 24 sets<br />

support structure and the required accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A11. Substation Gantry and Pedestal Steel Structures 1 lot<br />

including bolts, washer, etc hot dipped galvanized<br />

complete with all the required accessories in accordance<br />

to the requirements of the Technical Data Sheet (TDS)<br />

A12. Metalclad Switchgear, 13.8 kv outdoor type outdoor 2 sets<br />

type complete with arresters, VT, CT, breaker and 150<br />

KVA 13.8/460 vac 3-phase transformer type ONAN<br />

Outdoor type in accordance to the requirements of the<br />

Technical Data Sheet (TDS)<br />

A13 Installation Materials consisting of conductors, 1 lot<br />

insulators, connectors, pole line hardwares, bus<br />

supports, and other accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

A14 Grounding Materials consisting of insulated and bare 1 lot<br />

copper cables, lightning rod, copper rods, fittings.<br />

complete with the required materials for aerial and<br />

grounding mat and to substation equipment and<br />

structures in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A15. Distribution Board 125 VDC complete with enclosure, 2 sets<br />

main breaker, Automatic transfer switch, tie breaker,<br />

branch breakers, and accessories for installation.<br />

Number of breakers to supply four (4) bays in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS)<br />

A16. Station Service Transformer 50 kva 480/230V, three 2 sets<br />

phase, dry type and accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS).<br />

A17. Distribution Board 3 Phase 460/230 VAC with 2 sets<br />

enclosure, main breaker, tie breaker, automatic transfer<br />

switch, branch circuit and accessories Number of<br />

circuit breaker to include 4 additional bays, breaker to<br />

panel at bay 3 and 4, and spare breaker in accordance to<br />

the requirements of the Technical Data Sheet (TDS)<br />

A18. Distribution Board 3 Phase 230 VAC with enclosure , 2 sets<br />

main breaker, tie breaker, automatic transfer switch,<br />

branch circuit and accessories Number of circuit<br />

breaker for four (4) bays, breaker for panel at bays 3<br />

and 4 and spare breaker in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

A19 Power Control, Instrumentation and Protection 1 lot<br />

Cables, 35kV, 15 kV and 600 volt insulation complete<br />

with insulated terminal lugs, glands, marking etc. in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS)<br />

A20. Cable Trays (various type) hot dipped galvanized, 1 lot<br />

complete with supports, fittings, and other accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS). Cost of cable tray included at cable<br />

trenches<br />