12.04.2015 Views

BILL OF QUANTITIES

BILL OF QUANTITIES

BILL OF QUANTITIES

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>BILL</strong> <strong>OF</strong> <strong>QUANTITIES</strong><br />

DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

1.0 DETAILED ENGINEERING DESIGN<br />

Complete design of Clark - Mexico 230kV Double Circuit 1 lot<br />

Transmission Line, Expansion of Clark and Mexico<br />

230kV Substations, Expansion of Clark Substation<br />

Control House, and the Proposed Clark Substation<br />

Warehouse in accordance with PEC, IEC, ANSI, NESC,<br />

NBC, NSCP and DPWH Design Standards<br />

Compliance to NGCP requirements for the submission of<br />

factory tests, field tests, manuals, procedures and other<br />

documents for NGCP approval. Coordination and other<br />

requirements to energize the system.<br />

Permits, local and national and payments of fees and<br />

other documents as required to complete the project<br />

Compliance to the COA requirements for the submission<br />

of Detailed unit Cost Analysis of Items as listed in the Bill<br />

of Quantities<br />

Provide assistance in the R.O.W acquisition especially in<br />

the consultation/coordination with the Local Government<br />

Units and Barangay Officials having jurisdiction over the<br />

area that will be affected by the R.O.W. of the<br />

transmission line. Assists CDC on the procedure of<br />

payments and registration of property/ROW acquisition in<br />

accordance with R.A. 8974 and other applicable laws.<br />

Detailed Engineering Design Activities as per section 2 of<br />

scope of work<br />

a. Review of existing information<br />

b. Topographic and Parcellary survey<br />

c. Right of way acquisition<br />

d. Soil and material investigation<br />

e. Hydrological and hydraulic studies<br />

f. Environmental impact assessment (EIA)<br />

g. Detailed design plans and specifications<br />

h. Utility relocation plan<br />

i. Detailed estimate / unit price analysis<br />

j. Drawing submittals<br />

k. Reports<br />

Submit three (3) options of possible transmission line<br />

Alignments with cost benefit analysis, evaluation and<br />

recommendation (NLEX, existing 69 kv corridor, new<br />

route)<br />

2.0 230 Kv TRANSMISSION LINE From Clark S/S to Mexico S/S<br />

Construction of Double Circuit (1 x 410 TSAR) on Steel 35 KM<br />

poles or Steel towers, clearance over roadway as per<br />

PEC, IEC, ANSI, NESC, maximum span is 100 meters<br />

on 43 meter steel poles and 250 meters on 52 meters<br />

steel towers in accordance to the requirements of the<br />

Technical Data Sheet (TDS) and compliance to ATO<br />

requirements.<br />

Page 1 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

3.0 CLARK SUBSTATION 230/69kV<br />

A. ELECTRICAL WORKS<br />

Supply, manufacture, factory testing, and furnishing of<br />

labor, equipment, tools and incidental materials for the<br />

delivery, assembly, erection, installation, field testing<br />

commissioning and ready for operation of the following<br />

substation equipment and its associated control and<br />

protection system and accessories<br />

Bay 85 and Bay 86 At Clark 230 kV S/S<br />

A1. Power Transformer 150 MVA Three winding autotransformer<br />

2 sets<br />

type 3-Phase 230/69kV wye-13.8 delta with<br />

neutral earthing resistor class ONAN/ONAF1/ONAF2 ,<br />

complete with all appurtenances, accessories and onload<br />

tap changing mechanism with 16 taps of 0.625%<br />

above and 16 taps of 0.625% below 0 including<br />

paralleling device and control in accordance to the<br />

requirements of the Technical Data Sheet (TDS).<br />

A2. Power Circuit Breaker Dead Tank 230kV, 3-phase, 4 sets<br />

2000A, 40, kA three pole operation, complete with the<br />

required accessories and support structure including<br />

bushing current transformers in accordance to the<br />

requirements of the Technical Data Sheet (TDS).<br />

A3. Power Circuit Breaker Dead Tank 69kV, 3-phase, 6 sets<br />

2000A, 38 kA three pole operation, complete with the<br />

required accessories and bushing current transformer in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A4. Ganged Disconnect Switch 230kV, 3-phase, 2000A, 10 sets<br />

40KA equipped with 460 vac 3 phase motor and<br />

manually group operated, complete with the required<br />

accessories in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A5. Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 4 sets<br />

kA equipped with earthing blades, 230 vac motor and<br />

manually group operated, complete with the required<br />

accessories in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A6 Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 14 sets<br />

kA equipped with, 230 vac motor and manually group<br />

operated, complete with the required accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A7 Voltage Transformer Capacitive type 230 kV, complete 18 sets<br />

with the required accessories and support structure in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A8 Voltage Transformer 69 kV, complete with the required 30 sets<br />

accessories in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A9 Surge Arresters 192 kV, station type, complete with 12 sets<br />

support structure and the required accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

Page 2 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A10. Surge Arresters 60 kV, station type, complete with 24 sets<br />

support structure and the required accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A11. Substation Gantry and Pedestal Steel Structures 1 lot<br />

including bolts, washer, etc hot dipped galvanized<br />

complete with all the required accessories in accordance<br />

to the requirements of the Technical Data Sheet (TDS)<br />

A12. Metalclad Switchgear, 13.8 kv outdoor type outdoor 2 sets<br />

type complete with arresters, VT, CT, breaker and 150<br />

KVA 13.8/460 vac 3-phase transformer type ONAN<br />

Outdoor type in accordance to the requirements of the<br />

Technical Data Sheet (TDS)<br />

A13 Installation Materials consisting of conductors, 1 lot<br />

insulators, connectors, pole line hardwares, bus<br />

supports, and other accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

A14 Grounding Materials consisting of insulated and bare 1 lot<br />

copper cables, lightning rod, copper rods, fittings.<br />

complete with the required materials for aerial and<br />

grounding mat and to substation equipment and<br />

structures in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A15. Distribution Board 125 VDC complete with enclosure, 2 sets<br />

main breaker, Automatic transfer switch, tie breaker,<br />

branch breakers, and accessories for installation.<br />

Number of breakers to supply four (4) bays in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS)<br />

A16. Station Service Transformer 50 kva 480/230V, three 2 sets<br />

phase, dry type and accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS).<br />

A17. Distribution Board 3 Phase 460/230 VAC with 2 sets<br />

enclosure, main breaker, tie breaker, automatic transfer<br />

switch, branch circuit and accessories Number of<br />

circuit breaker to include 4 additional bays, breaker to<br />

panel at bay 3 and 4, and spare breaker in accordance to<br />

the requirements of the Technical Data Sheet (TDS)<br />

A18. Distribution Board 3 Phase 230 VAC with enclosure , 2 sets<br />

main breaker, tie breaker, automatic transfer switch,<br />

branch circuit and accessories Number of circuit<br />

breaker for four (4) bays, breaker for panel at bays 3<br />

and 4 and spare breaker in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

A19 Power Control, Instrumentation and Protection 1 lot<br />

Cables, 35kV, 15 kV and 600 volt insulation complete<br />

with insulated terminal lugs, glands, marking etc. in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS)<br />

A20. Cable Trays (various type) hot dipped galvanized, 1 lot<br />

complete with supports, fittings, and other accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS). Cost of cable tray included at cable<br />

trenches<br />

Page 3 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A21 Switchyard Lighting System (Bay and Perimeter) 1 lot<br />

complete with the required fixtures, posts, conduits,<br />

wires, magnetic contactor and photo cell, conduit<br />

fittings, conductors foundations, etc in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

A22 Substation Control System<br />

a. Microprocessor Based Substation Control System 1 sets<br />

(New back up set ) to include the integration of<br />

new and existing to accommodate all system (six<br />

bays). To include licensed copy of software (latest<br />

Version) and industrial type equipment for the<br />

Protection, control and monitoring of equipment for<br />

connection to SCADA, gateway, HMI and Work<br />

station. To include the integration, data base<br />

reconfiguration, parameterization of the existing<br />

and new MBSC system with BCU, and others to<br />

conform to the new set up of Clark S/S. To provide<br />

CDC with copy of license software in DVD or CD<br />

in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

b. Closed Circuit Television System (New set of<br />

1 sets<br />

CCTV) new system for bays 3,4, 5, 6 and<br />

perimeter fence complete with all the required<br />

peripherals, industrial computer, accessories,<br />

wires and cable reconfiguration and integration<br />

with existing CCTV system. To include the supply<br />

and replacement of existing CCTV controller and<br />

reconfiguration. (No of PTZ dome camera arm<br />

mounted at gantry = six(6), Pole mounted<br />

Motorized pan tilt camera = two(2), CCtv player<br />

recorder controller = (2), Working station with 21<br />

inch Monitor= two (2) and licensed software with<br />

CD or DVD in accordance to the requirements of<br />

the Technical Data Sheet (TDS).<br />

A23<br />

c. Access Control and Alarm Monitoring System<br />

1 lot<br />

(ACAMS) revision / expansion/ integration of<br />

system to include new warehouse and relocation<br />

of existing affected by control building renovation<br />

d. Main Control Switchboard, with all instrument, 1 lot<br />

meters, indicators, control switches, annunciators,<br />

push buttons, LED indicating lamps, terminal<br />

blocks, wiring and miscellaneous auxiliary and<br />

accessory devices<br />

Substation Protection System<br />

a. Transformer Protection ( Main 1) complete with 2 sets<br />

the required protective relays and accessories in<br />

one (1) panel. Different manufacturer from Main 2<br />

in accordance to the requirements of the<br />

Technical Data Sheet (TDS)<br />

b. Transformer Protection ( Main 2) complete with 2 sets<br />

the required protective relays and accessories in<br />

one (1) panel, Different manufacturer from Main 1<br />

in accordance to the requirements of the<br />

Technical Data Sheet (TDS)<br />

Page 4 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

c. Breaker Failure Protection System<br />

1 sets<br />

Complete with the required protective relays and<br />

accessories for four (4) 230 kV Power Circuit<br />

Breakers in one panel in accordance to the<br />

requirements of the Technical Data Sheet (TDS).<br />

d. 230 kV Bus Protection System, Main 1 - complete 1 sets<br />

with accessories for connection of new breaker 8-<br />

03CB24CLA and 8-04CB24CLA at Bus 8-<br />

BS03CLA to existing GE B30-8BS03CLA in<br />

accordance to the requirements of the Technical<br />

Data Sheet (TDS)<br />

e. 230 kV Bus Protection System, Main 1 - complete 1 sets<br />

with accessories for connection of new breaker 8-<br />

03CB08CLA and 8-04CB08CLA at Bus 8 -<br />

BS04CLA to existing GE B30-8BS04CLA in<br />

accordance to the requirements of the Technical<br />

Data Sheet (TDS)<br />

d. 230 kV Bus Protection System, (Main 2) complete 2 sets<br />

with the required protective relays and accessories<br />

for the integration of five (5) 230 kV Power Circuit<br />

Breakers (Bus Tie, Bay 3,4,5 and 6 Breakers) in<br />

accordance to the requirements of the Technical<br />

Data Sheet (TDS)<br />

f. 69 kV Feeder Protection System, complete with<br />

the required protective relays and accessories for<br />

the following outgoing 69 kV feeders in<br />

accordance to the requirements of the Technical<br />

Data Sheet (TDS)<br />

f.1 Three (3) 69 kV breakers with two (2) 69 kV 1 sets<br />

outgoing feeders in one (1) panel<br />

f.2 Three (3) 69 kV breakers with two (2) 69 kV 1 sets<br />

outgoing feeders in one (1) panel<br />

g. Bay Control Unit with provision for integration to 2 sets<br />

existing and new Microprocessor Based<br />

Substation Control system complete with<br />

necessary accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS)<br />

Bay 83 and Bay 84 at Clark 230 kV S/S<br />

A24 Line Protection System<br />

a. Line Protection for 230 kV system (Main 1 -<br />

2 sets<br />

Distance Relay) complete with the required<br />

protective relays and accessories in accordance to<br />

the requirements of the Technical Data Sheet<br />

(TDS).<br />

b. Line Protection for 230 kV system (Main 2 - Line 2 sets<br />

Differential Relay) complete with the required<br />

protective relays and accessories in accordance to<br />

the requirements of the Technical Data Sheet<br />

(TDS).<br />

A25 Capacitive Voltage Transformer 230 kV, complete with 6 units<br />

the required accessories and support structure in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

Page 5 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A26 Surge Arresters 192 kV, station type, complete with 6 units<br />

support structure and the required accessories in<br />

accordance to the requirements of the Technical Data<br />

Sheet (TDS).<br />

A27 Ganged Disconnect Switch 230kV, 3-phase, 2000A, 2 units<br />

40KA equipped with 460 vac 3 phase motor and<br />

manually group operated, complete with the required<br />

accessories in accordance to the requirements of the<br />

Technical Data Sheet (TDS).<br />

A28 Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 2 units<br />

kA equipped with 230 vac motor and manually group<br />

operated, complete with the required accessories in<br />

accordance to the requirements of the Technical Data<br />

A29 Ganged Disconnect Switch 69kV, 3-phase, 2000A, 38 2 units<br />

kA equipped with earthing blades, motor and manually<br />

group operated, complete with the required accessories<br />

in accordance to the requirements of the Technical Data<br />

Sheet (TDS)<br />

A30 Voltage Transformer 69 kV, complete with the required 12 units<br />

accessories in accordance to the requirements of the<br />

Technical Data Sheet (TDS)<br />

A31 BATTERY 125 VDC POWER SUPPLY SYSTEM 800 2 units<br />

amp-hour capacity indoor type complete with the<br />

required rack and accessories in accordance with the<br />

requirements of Technical Data Sheet (TDS)<br />

A32 Battery Charger 460 vac 3 phase in accordance with the 2 units<br />

requirements of the Technical Data Sheet (TDS).<br />

A33 Supply and Installation of Emergency Generators with 1 unit<br />

a capacity of 225 KVA, 460/230 vac, 60 HZ with diesel<br />

engine, Day Tank and four (4) 400 amps 480 vac 3-<br />

phase 4 poles ATS<br />

A32 NETWORK DISTURBANCE MONITORING<br />

1 lot<br />

EQUIPMENT (NDME)<br />

Supply of Data acquisition units complete with required<br />

peripherals and accessories. Reconfiguration of existing<br />

NDME to conform with the new set-up/configuration<br />

under this project to include Bay 81, 82, 83, 84, 85 & 86.<br />

The units should be the same brand or latest model and<br />

compatible with the existing unit at the control room.<br />

A33 FIBER OPTIC COMMUNICATION SYSTEM<br />

a. Fiber Optic Terminal Equipment complete with<br />

1 lot<br />

Optical Distribution Frame (ODF), access<br />

multiplexers, circuit protections, indicators,<br />

annunciators, appurtenances, pigtails, patch<br />

cords, complete with the required accessories.<br />

b. Fiber Optic Approach Cable, 36 fibers, 1550 nm, 1 lot<br />

Signal Mode (from station gantry to the Optical<br />

Distribution Frame at the FOT Equipment Room).<br />

Page 6 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

c. Protection Signaling Equipment complete with all 2 lot<br />

the necessary interface cables, software and<br />

manuals. Programmable teleprotection unit for<br />

transmitting / receiving minimum of four (4)<br />

independent command signals capable of<br />

communicating over analog and digital<br />

communication channel i.e., MUX (4WE&M,<br />

RS232, V.32, X.21, etc), PLC, copper wire and<br />

fiber optic.<br />

A34<br />

MICROWAVE RADIO COMMUNICATION SYSTEM<br />

a. Digital Microwave Radio Terminal, 16E1, 7GHz, 1+1<br />

MHSB including all necessary accessories i.e. mounting<br />

cabinet, rack/shelf assembly, order wire, fuse and alarm<br />

panel, power supply and jack field (for 16 tributaries)<br />

a.1 Clark S/S<br />

1 lot<br />

a.2 Mexico S/S<br />

1 lot<br />

b. Multiplex Equipment / Channel Bank and associated<br />

cards including all necessary peripheral equipment and<br />

installation accessories i.e. rack/shelf assembly, VF jack<br />

field, MDF, interface and data cable<br />

b.1 Clark S/S<br />

1 lot<br />

b.2 Mexico S/S<br />

1 lot<br />

c. Antenna System and Waveguides including all<br />

installation accessories and peripheral equipment i.e.<br />

antenna mount and support pipe, strut hardware kit,<br />

waveguide support hardware, flanging tools, waveguide<br />

connector etc.<br />

c.1 Clark S/S<br />

1 lot<br />

c.2 Mexico S/S<br />

1 lot<br />

d. Network Management System including all the<br />

necessary hardware and software modules for<br />

management of node element / sub network, i.e.<br />

industrial portable PC with licensed Windows Operating<br />

System and pre installed Network Management software.<br />

d.1 Clark - Mexico MW Radio link<br />

1 lot<br />

e. Protection Signaling Equipment complete with all the 2 lot<br />

necessary interface cables, software and manuals.<br />

Programmable teleprotection unit for transmitting /<br />

receiving minimum of four (4) independent command<br />

signals capable of communicating over analog and digital<br />

communication channel i.e., MUX (4WE&M, RS232,<br />

V.32, X.21, etc), PLC, copper wire and fiber optic.<br />

A35<br />

Spares, Spare parts and tools( see list as per TDS)<br />

a. Power Transformer 1 lot<br />

b. Power Circuit Breaker 230 kV and 69 kV 1 lot<br />

c. 230 kV and 69kV Ganged Disconnect Switches 1 lot<br />

d. 230 Kava and 69 kV Voltage Transformers 1 lot<br />

e. 230 kV and 69 kV Surge Arresters 1 lot<br />

f. Metal clad Switchgear 13.8 kV 1 lot<br />

g. Station Service Transformer 1 lot<br />

h. AC DC aux switchboard 1 lot<br />

Page 7 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

i. Storage Batteries 1 lot<br />

j. Battery Charger 1 lot<br />

k. MBSC 1 lot<br />

l. CCTV 1 lot<br />

m. Substation Protection System 1 lot<br />

n. Line Protection System 1 lot<br />

o. Network Disturbance Monitoring 1 lot<br />

p. Fibre Optical Terminal Equipment 1 lot<br />

q. Protection Signaling Equipment 1 lot<br />

r Microwave Radio Telephone equipment 1 lot<br />

Clark Load End Substation at PSPC<br />

A36 Station Service Transformer 75 kva 22.9/0.23kV, three 2 lot<br />

phase, Outdoor ONAN type, 35 kV xlpe cable, 300:5<br />

amp 22.9 kV CT, and accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS). To<br />

includes bus bar modification, current transformer, cover,<br />

support and wiring/termination to substation protection<br />

system. The scope covers the construction of<br />

foundation, HV and LV wiring and installation of new<br />

transformer.<br />

A37 Distribution Board 3 Phase 230 VAC with enclosure , 2 sets<br />

main breaker, tie breaker, automatic transfer switch, four<br />

(4) 3 poles branch circuit breakers, assorted copper<br />

wires, conduits and accessories in accordance to the<br />

requirements of the Technical Data Sheet (TDS). The<br />

scope includes the wiring and termination to existing<br />

MTS/AC panel and fire suppression panel.<br />

SUB-TOTAL FOR ITEM 3A ELECTRICAL WORKS<br />

B CIVIL WORKS<br />

FURNISH, INSTALL, CONSTRUCT, PLACE, APPLY<br />

AND / OR LAY, INCLUDING FURNISHING <strong>OF</strong> PLANT,<br />

LABOR, EQUIPMENT AND MATERIALS<br />

B1 EQUIPMENT FOUNDATION Consisting of concrete<br />

(211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars<br />

(Grade 275), Excavation and backfill, Leveling Concrete<br />

(141 kg/cm²) and other incidentals required to complete<br />

the works.<br />

a. Power Transformer 2 lot<br />

b. Power Circuit Breaker 12 lot<br />

c. Current Transformer 72 lot<br />

d. Voltage Transformer 12 lot<br />

e. Surge Arresters 24 lot<br />

f. Ganged Disconnect Switch 24 lot<br />

G. Bus Supports 48 lot<br />

f. Emergency Generator set 1 lot<br />

B2 230 kV Gantry Structure Foundation Consisting of<br />

concrete (211kg/cm²), Non-shirk Grout, Reinforcing Steel<br />

Bars (Grade 275), Excavation and backfill, Leveling<br />

Concrete (141 kg/cm²) and other incidentals required to<br />

complete the works.<br />

1 lot<br />

Page 8 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

B3 Roadways, Parking Area, Concrete Curve & Gutter, 2227 sq.m<br />

Open stock yard Construction of access road from the<br />

existing roadway to the transformer area and parking<br />

area at warehouse, consisting of Concrete Pavement<br />

(246kg/cm²), Curb and Gutter (211kg/cm²) including<br />

dowels, Reinforcing steel bars (Grade 275), Aggregate<br />

Sub-Base and other incidentals to complete the work.<br />

B4 Drainage System - Consisting of different sizes of 435 lm<br />

RCDP, Drainage Appurtenances consisting of Concrete (Main)<br />

(211kg/cm²), Reinforcing steel bars Grade 275,<br />

Excavation and backfill, Miscellaneous Steel (ASTM 300 lm<br />

A36), CHB including demolition/restoration works for the (Sec.)<br />

affected portion of the existing drainage appurtenances<br />

and other incidentals to complete the work.<br />

B5 Oil/Water Separator - Consisting of concrete 1 lot<br />

(211kg/cm²), Reinforcing Steel Bars (Grade 275),<br />

Excavation and backfill, Miscellaneous Steel, Galvanized<br />

Steel pipe, B.I. Pipe, including its tapping to the nearest<br />

drainage system and other incidentals required to<br />

complete the work.<br />

B6 Concrete Firewall - Between transformers consisting of 1 lot<br />

Concrete (211kg/cm²), Reinforcing Steel Bars (Grade<br />

275), Excavation and Backfill, Leveling Concrete<br />

(141kg/cm²) and other incidentals required to complete<br />

the work.<br />

B7 Cable Trenches - Consisting of Concrete (211kg/cm²) 400 l.m.<br />

Reinforcing Steel Bars (Grade 275), Excavation, leveling (Main)<br />

Concrete (141kg/cm²), Checkered Steel Plate Cover,<br />

Stiffener, Embedded Metals, Steel angle, galvanized<br />

cable tray, pits, Discharge Pipes including 200 l.m.<br />

demolition/restoration works for the affected portion of (Branches)<br />

the existing cable trench to connect the new cable trench<br />

and other incidentals to complete the work.<br />

B8 Cable Pipe Crossing Roadways - Consisting of 12 l.m.<br />

concrete (211kg/cm²), Reinforcing Steel Bars (Grade<br />

275) Excavation, Sand and Gravel bedding, uPCV Pipes,<br />

Discharge Pipes and other incidentals required to<br />

complete the works.<br />

B9 Switchyard Gravel Surfacing - Gravel surfacing on the 1200 cu.m<br />

bays where the equipment will be installed with the lines<br />

and extent as directed by the owner.<br />

B10 Seclusion Fence and Gate - Enclosing the 230kV and 235 l.m.<br />

69kV switchyard consisting of Hot Dipped Galvanized<br />

Wire Mesh Gauge #10, G.I. Pipes Schedule 40,<br />

Miscellaneous Steel (ASTM A36), Concrete (211 kg/cm²)<br />

Reinforcing Steel Bars (Grade 275), Excavation and<br />

Backfill, and other incidentals to complete the work.<br />

B11 Embankment of Substation Expansion Area -<br />

7040 sq.m.<br />

Consisting of clearing, grading, and embankment with<br />

compaction in layers to match the existing finish grade in<br />

accordance with DPWH Standard Specifications.<br />

Page 9 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

B12 Retaining Wall and Perimeter Fence of Substation 295 l.m.<br />

Expansion Area - Consisting of Concrete (211kg/cm²),<br />

Reinforcing steel bars Grade 275, Excavation and<br />

backfill, CHB including demolition/restoration works for<br />

the affected portion of the existing retaining<br />

wall/perimeter fence and other incidentals to complete<br />

the work. To include painting of walls and perimeter<br />

fence and affected areas.<br />

B13 69kV Gantry Structure Foundation Consisting of 1 set<br />

concrete (211kg/cm²), Non-shirk Grout, Reinforcing Steel<br />

Bars (Grade 275), Excavation and backfill, Leveling<br />

Concrete (141 kg/cm²) and other incidentals required to<br />

complete the works.<br />

B14 Expansion of Existing Clark 230KV S/S Control 115 sq.m.<br />

House Consisting of architectural, civil, electrical,<br />

mechanical, and finishing works to match the existing. To<br />

include supply of 3-3 tons split air conditioning units,<br />

industrial type exhaust fan, fire detection units to connect<br />

to existing Fire Alarm panel, lights and outlets, wiring and<br />

other accessories and incidentals to complete the work.<br />

To include repainting of Bldg external and affected<br />

areas.<br />

B15 Proposed Clark 230KV S/S Warehouse Consisting of 288 sq.m.<br />

architectural, civil/structural, electrical, and mechanical<br />

works for the construction of steel frame warehouse with<br />

minimum beam height of 6.00 meters. To include supply<br />

and installation of industrial exhaust fans, lighting fixtures<br />

and outlets. Painting of building internal and external.<br />

B16 Fire Water System,<br />

a. Cleaning & Flushing of following existing facilities<br />

1. 100 mm 440 mtrs<br />

2. 50 mm 110 mtrs<br />

3. 40 mm 200 mtrs<br />

4. Assorted sizes to control room, guard house 100 mtrs<br />

and green area<br />

5. Elevated Water Tank 10,000 gal<br />

1 set<br />

b. New Installation of the following<br />

1. 100 mm GI super sched 40 underground line 420 mtrs<br />

2.<br />

with fittings, valves sand beddings and with<br />

protection membrane<br />

Fire hose reel cabinet with 40 mm brass 12 sets<br />

nozzle, 40 mm x 30 mtrs hose, 40 mm brass<br />

valve, fittings, glass, painted gauge #10 metal<br />

sheet and concrete foundation.<br />

3. Road Crossing of Fire water line, include 9 mtrs<br />

cutting, excavation, backfilling, sand bedding<br />

and road concreting<br />

B17 Rehabilitation of Existing Water Well, includes<br />

100 mtrs<br />

suctioning/cleaning of existing water well including use of<br />

equipment (air compressor and other cleaning equipment)<br />

B18 Replacement of Existing Submersible Pump multistage<br />

type, 100 GPM, 95 meters TDH complete with control and<br />

including Pull out of existing and installation of new<br />

submersible pump.<br />

1 unit<br />

Page 10 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

B19 Rehabilitation of Existing Fire Pump, includes<br />

1 unit<br />

cleaning of pumps, testing, electrical system and ready<br />

for operation.<br />

B20 Rehabilitation of Existing Jockey Pump, includes 1 unit<br />

cleaning of pumps, testing, electrical system and ready<br />

for operation.<br />

B21 Brand New Truck Loader Cargo Crane 1 unit<br />

Gross vehicle mass including crane 8,000, Crane<br />

capacity 5,000 kg at 2.4 meters, Maximum lift above<br />

ground 10 Meters, With Hydraulic motors for winch, and<br />

swing, Hydraulic extended Outriggers, Hydraulic pump,<br />

and powered thru PTO. For turn over to CDC-ECMD<br />

SUB-TOTAL FOR ITEM 3B CIVIL WORKS<br />

TOTAL CLARK SUBSTATION 230/69KV<br />

4.0 Metering System (230kV System) 6 sets<br />

Current transformer Multi ratio 2000:5A 0.3 accuracy<br />

class, Burden B-0.1 to 0.9, Voltage transformer 0.3<br />

accuracy, weather proof enclosure for Billing meter for<br />

the electronic billing system in accordance to the<br />

requirements and specification of the power provider<br />

(NGCP/TRANSCO) for T1, T2, T3, T4, T5 and T6.<br />

5.0 GRID IMPACT STUDY, including request and payment 1 lot<br />

for the data, review and approval of NGCP<br />

6.0 OCCUPATIONAL HEALTH AND SAFETY 1 lot<br />

includes personal protective equipment, clinical<br />

materials, signage's and barricades, and the salary and<br />

wages of health and safety personnel.<br />

7.0<br />

Facilities For The Engineer such as temporary field<br />

office, including all necessary electricity, water,<br />

telephone services, office equipment, furniture and<br />

the following for the use of CDC/ECMD Engineers.<br />

For turn over to CDC-ECMD after the completion of<br />

the project<br />

a Field Office (20 ft Container with AC unit)<br />

2 units<br />

b Laptops Intel Core i7-2410 processor, Window 7 4 units<br />

c<br />

pro, MS Office 2007 with external 1TB hard Drive<br />

Desktop Intel i7-550 Processor, Window 7 pro, MS 2 units<br />

office 2007 with external 1TB hard drive<br />

d Licensed AUTOCAD (2010 or latest) softwares 2 units<br />

e Licensed Ms Project (2010 or latest) softwares 2 units<br />

f Service Vehicle Twin Cab Pick up 4 x 4 (3.0 diesel 2 units<br />

engine, common rail direct injection) with fuel,<br />

driver, maintenance, other costs (Toll fee, parking)<br />

for 14 months (lease to own)<br />

g Service Vehicle AUV 4 x 2 (2.5 Diesel engine) with 1 unit<br />

fuel, driver and maintenance, others (Toll, parking<br />

fee) costs for 14 months (lease to own)<br />

Page 11 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

h Digital SLR Camera 15 megapixel with zoom 105, 2 units<br />

extra 8GB memory card and bag.<br />

i Flat bed scanner A4<br />

1 unit<br />

j Color Printer A3 paper size complete with supply 1 unit<br />

of paper and ink for the duration of the project<br />

k Professional Infrared Thermal Imagers<br />

1 unit<br />

l Voice recorder 8GB, Built-in Li-Ion Battery<br />

1 unit<br />

8.0<br />

A<br />

MEXICO 230 KV SUBSTATION Bay 87 and 88<br />

(All in accordance with NGCP specifications)<br />

ELECTRICAL WORKS<br />

Supply, manufacture, factory testing, and furnishing of<br />

labor, equipment, tools and incidental materials for the<br />

delivery, assembly, erection, installation, field testing<br />

commissioning and ready for operation of the following<br />

substation equipment and its associated control and<br />

protection system and accessories<br />

A1 Power Circuit Breaker Live Tank 230kV, 3-phase, 2 sets<br />

3000A, 40, kA single and three pole operation (3+1),<br />

complete with the required accessories and support<br />

structure<br />

A2 Ganged Disconnect Switch 230kV, 3-phase, 3000A, 2 sets<br />

44KA equipped with 460 vac 3 phase motor and<br />

manually group operated, complete with the required<br />

accessories<br />

A3 Ganged Disconnect Switch 230kV, 3-phase, 3000A, 2 sets<br />

44KA equipped with earthing, 460 vac 3 phase motor<br />

and manually group operated, complete with the required<br />

accessories<br />

A4 Capacitor Voltage Transformer (CVT) 230 kV, 3 sets<br />

complete with the required accessories and support<br />

structure.<br />

A5 Surge Arresters 192 kV, station type, complete with 3 sets<br />

support structure and the required accessories<br />

A6 Substation Gantry and Pedestal Steel Structures 1 lot<br />

including bolts, washer, etc hot dipped galvanized<br />

complete with all the required accessories<br />

A7 Installation Materials consisting of conductors, 1 lot<br />

insulators, connectors, pole line hardwares and other<br />

accessories<br />

A8 Grounding Materials consisting of insulated and bare 1 lot<br />

copper cables, lightning rod, copper rods, fittings.<br />

complete with the required materials for aerial and<br />

grounding mat and to substation equipment and<br />

structures.<br />

A9 AC and DC Auxiliary Panels Indoor type, complete with 1 lot<br />

the required equipment, devices and required<br />

accessories<br />

Page 12 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A10 Distribution Board 125 VDC complete with enclosure, 1 lot<br />

main, Automatic transfer switch, tie breaker, branch<br />

breakers, and accessories for installation.<br />

A11 Distribution Board 3 Phase 230 VAC with enclosure , 1 lot<br />

main breaker, tie breaker, automatic transfer switch,<br />

branch circuit and accessories<br />

A12 Cable Trays (various type) hot dipped galvanized,<br />

1 lot<br />

complete with supports, fittings, and other accessories.<br />

Cost of cable tray to be included at cable trenches<br />

A13<br />

Substation Control System<br />

Main Control Switchboard, with all instrument, meters,<br />

indicators, control switches, annunciators, push buttons,<br />

LED indicating lamps, terminal blocks, wiring and<br />

miscellaneous auxiliary and accessory devices<br />

1 lot<br />

Bay Control Unit with provision for integration to existing<br />

Micro Processor Base Control System complete with<br />

necessary accessories<br />

1 lot<br />

A14<br />

Substation Protection System<br />

a. Breaker Failure Protection System Complete with 1 set<br />

the required protective relays and accessories for<br />

four (4) 230 kV Power Circuit Breakers in one<br />

panel.<br />

b. 230 kV Bus Protection System, - complete with the 1 lot<br />

required Peripheral Unit protective relays and<br />

accessories for the integration of two (2) 230 kV<br />

Power Circuit Breakers<br />

A15<br />

Line Protection System<br />

a. Distance Protection System (Main 1 and Main 2 sets<br />

2) Main 1 complete with the required protective<br />

relays and accessories in one panel and Main 2<br />

complete with the required protective relays and<br />

accessories in one panel.<br />

b. Differential Protection System (Main 1 and Main 2 sets<br />

2) Main 1 complete with the required protective<br />

relays and accessories in one panel and Main 2<br />

complete with the required protective relays and<br />

accessories in one panel.<br />

A16 Current Transformers 230 kV, Multi-ratio, three core, 12 sets<br />

outdoor type oil filled, free standing complete with<br />

support structure and required accessories in<br />

accordance with NGCP specs.<br />

A17 Power Control , Instrumentation and Protection<br />

1 lot<br />

Cables, complete with insulated terminal lugs, glands,<br />

etc.<br />

Page 13 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

A18 Fiber Optic Communication System<br />

a. Fiber Optic Terminal Equipment complete with 1 lot<br />

Optical Distribution Frame (ODF), access<br />

multiplexers, circuit protections, indicators,<br />

annunciators, appurtenances, pigtails, patch<br />

cords, complete with the required accessories.<br />

b. Fiber Optic Approach Cable, 36 fibers, 1550nm, 1 lot<br />

signal mode (from station gantry to the Optical<br />

Distribution Frame at the FOT Equipment Room.<br />

c. Protection Signaling Equipment complete with all 1 lot<br />

the necessary interface cables, software and<br />

manuals. Programmable teleprotection unit for<br />

transmitting / receiving minimum of four (4)<br />

independent command signals capable of<br />

communicating over analog and digital<br />

communication channel i.e., MUX (4WE&M,<br />

RS232, V.32, X.21, etc), PLC, copper wire and<br />

fiber optic.<br />

A19<br />

Microwave Radio Communication System<br />

a. Complete integration and interconnection of<br />

1 lot<br />

existing FOT and MW telecommunication system<br />

with associated equipment including interface<br />

cables, MUX equipment / channel cards, etc.<br />

b. Protection Signaling Equipment complete with all 1 lot<br />

the necessary interface cables, software and<br />

manuals. Programmable teleprotection unit for<br />

transmitting / receiving minimum of four (4)<br />

independent command signals capable of<br />

communicating over analog and digital<br />

communication channel i.e., MUX (4WE&M,<br />

RS232, V.32, X.21, etc), PLC, copper wire and<br />

fiber optic.<br />

A20 NETWORK DISTURBANCE MONITORING<br />

1 Lot<br />

EQUIPMENT Supply of DAU complete with cables and<br />

accessories, Reconfiguration of the existing NDME to<br />

conform with the new setup/configuration of the<br />

substation under this project<br />

A21 Spares, Spare parts and tools:<br />

a. 230 kV Power Circuit Breakers<br />

1 lot<br />

b. 230 kV Ganged Disconnect Switches<br />

1 lot<br />

c. 230 kV Coupling Capacitor Voltage Transformers<br />

1 lot<br />

d. 230 kV Surge Arresters<br />

1 lot<br />

e. 230 kV Current Transformers<br />

1 lot<br />

f. Substation and Line Protection System (incl at Clark SS) 1 lot<br />

g. 460,230 VAC & 125 VDC Auxiliary Switchboard<br />

1 lot<br />

SUB-TOTAL FOR ITEMS 8A ELECTRICAL WORKS<br />

B CIVIL and ARCHITECTURAL WORKS<br />

Complete Design, Furnish, install, construct, place, apply<br />

and/or lay, including furnishing of plant, labor, equipment<br />

and materials<br />

Page 14 of 15


DESIGN AND BUILD SERVICES FOR THE CLARK 230 KV POWER TRANSMISSION LINE PROJECT -<br />

PHASE 3B<br />

ITEM DESCRIPTION<br />

QTY UNIT UNIT COST AMOUNT<br />

B1<br />

Equipment Foundation consisting of concrete (211<br />

kg/sq. cm, NGCP specs), Non-shirk Grout, Reinforcing<br />

steel Bars (Grade 275, NGCP specs), Excavation and<br />

backfill, Leveling Concrete (141 kg/sq. cm) and other<br />

incidentals required to complete the works.<br />

a. Power Circuit Breakers<br />

6 lot<br />

b. Ganged Disconnect Switches<br />

12 lot<br />

c. Capacitor Voltage Transformers<br />

3 lot<br />

d. Surge Arresters<br />

3 lot<br />

e. Current Transformers<br />

12 lot<br />

B2 230 kV Gantry Structure Foundation Consisting of<br />

1 lot<br />

concrete (211kg/sq cm), Non-shrink Grout, Reinforcing<br />

Steel Bars (Grade 275), Excavation and backfill, Leveling<br />

Concrete (141) kg/sq cm) and other incidentals required<br />

to complete the works.<br />

B3 Roadways, Concrete Curve & Gutter Construction of 1 lot<br />

access road from the existing roadway to the switchyard<br />

area, consisting of concrete pavement (246 kg/ sq cm),<br />

curb and gutter (211 kg/ sq cm) including dowels,<br />

Reinforcing Steel bars (Grade 275, Aggregate sub-base<br />

and other incidentals required to complete the work.<br />

B4 Drainage System, Consisting of different sizes of RCDP, 1 lot<br />

drainage appurtenances consisting of concrete (211kg/<br />

sq cm), Reinforcing steel bars Grade 275, Excavation<br />

and backfill, miscellaneous Steel (ASTM A36), CHB<br />

including demolition/restoration works for the affected<br />

portion of the existing drainage appurtenances and other<br />

incidentals required to complete the works.<br />

B5 Cable Trenches Consisting of concrete (211 kg/sq cm) 50 l.m.<br />

Reinforcing Steel Bars Grade 275, Excavation, leveling<br />

concrete (141 kg/sq cm), checkered steel plate cover,<br />

stiffener, embedded metals, steel angle, pits, discharge<br />

pipes including demolition/restoration and works for the<br />

affected portion of the existing cable trench to connect<br />

the new trench and other incidentals required to<br />

complete the works.<br />

B7 Switchyard Gravel Surfacing, Gravel surfacing on the 1 lot<br />

bays where the equipment will be installed with lines and<br />

extent as directed by the owner.<br />

SUB-TOTAL FOR ITEM 8B CIVIL WORKS<br />

9.0 Reconfiguration/ Parameterization/ Data Base<br />

1 lot<br />

Configuration of existing MBSC System complete with<br />

Bay Control units, Cables, accessories, peripheral, etc.<br />

to conform with the new set-up of NGCP Mexico<br />

Substation<br />

TOTAL MEXICO SUBSTATION 230KV<br />

TOTAL PROJECT DIRECT COST<br />

Page 15 of 15

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!