PBS 140 Child Care Center Design Guide - The Whole Building ...

PBS 140 Child Care Center Design Guide - The Whole Building ... PBS 140 Child Care Center Design Guide - The Whole Building ...

16.11.2012 Views

CHAPTER 10: TECHNICAL CRITERIA Whenever possible, provide HVAC separate from the other building systems. Apart from other advantages, this will facilitate better filtration of the dust and molds to which many children are particularly sensitive. Air diffusers should minimize drafts on children. Design ventilation systems to allow zero exposure of non-smokers to environmental tobacco smoke (ETS) even if smoking is limited to outdoor areas, as described in LEED Version 2.0. Design ventilation systems to achieve an air-change effectiveness of minimum 0.9 per ASHRAE 129- 1997 and as described in LEED Version 2.0. Locate air return over diaper and toilet areas. 10.9.3 Safety Issues: The following restrictions apply in child care centers: � Heating units that utilize flame must be vented properly to the outside and shall be supplied with sufficient combustion air. � Heating units hotter than 43 °C shall be made inaccessible to children by the use of barriers such as guards or locks. � Ensure that any gas-fired equipment takes 100% outside air for combustion to minimize negative pressure potential and the resulting backdrafting of combustion products into the indoor environment. 10.10 Lighting Well-considered lighting for each activity area is a key element in creating the “home-like” environment which is a goal of the program. The quality of light should remind children of a residential environment. Broad ambient lighting is most appropriate for large motor activity spaces; task lighting is required for manipulative activities; lower light levels are needed for quiet and sleeping areas. The amount and orientation of natural light needs to be considered in the design and variation in light levels. Up to a maximum of 500 lx will be acceptable in rooms with poor natural lighting capability. Classrooms without skylights or exterior windows should have ducted light tubes to provide natural light. Light shelves which transmit light deeper into the interior are to be considered for all south-facing elevations. See the table for the minimum light levels for various functions. In addition, the following should be provided: � 500 lx on children’s work surface for reading and close work. � 250 lx ambient light for class and play areas (additional task lighting up to 500 lx provided where appropriate). � Capability of being dimmed in a range of 500 lx to 50 lx for sleeping and napping areas. 10-10 � 100 lx in stairs and corridors. � Light fixtures in classrooms and nap rooms are to be dimmable. Light levels in all rooms, including sleeping rooms, must be maintained at a sufficient level to provide visual observation of the space from adjoining spaces. Lighting should be utilized to emphasize areas, designate boundaries, create a particular feeling, or cause a desired response. When using fluorescent lighting, utilize electronic ballast light fixtures. Their high frequency cycles avoid perceptible flickering and allow dimming. Fluorescent lamps are to have a color temperature of 3500 degrees Kelvin minimum with the highest possible color rendering index (CRI). Minimum CRI is to be 80 or greater. This is of paramount importance to the center’s environmental quality. If there is adequate ceiling height, the better quality of reflected, ambient lighting from pendants or recesses is strongly preferred to troffer-style fluorescent fixtures. If troffer flourescents must be used, use lamps which are to be baffled to provide predominantly indirect lighting. With reflected light, children (who are at a far lower vantage point than adults) will not look directly into the light source, a condition which causes glare and eye fatigue. Task lights, such as those provided by residential type pendant fixtures, should be used for reading, painting, and close work. Design for variety in lighting, through such devices as dimming controls, separate switching, adjustable directional fixtures, and pendant fixtures that are positioned over work areas. Consider using specialized lighting to display art work, pools of light to create excitement and variety, and high levels of light to encourage physical activity. Provide food preparation areas with fixtures having shielded or shatterproof bulbs. Exterior light can be controlled with adjustable blinds, shades, or other types of window coverings. Window treatments on interior windows must allow for clear visibility. Ensure that there is adequate exterior lighting to allow safe exterior circulation and site security. All lamps must have shatterproof lenses or covers. PBS-140 - July 2003

Table 10.2: Lighting Requirements Space Natural Light Lighting (in lux) (lx)) Vestibule View 200 - 250 Reception View 250 - 350 Main Circulation 100 - 350 Director’s Office View 500 Sick Bay 300 - 500 (Dimmable) Staff Lounge View 500 (Dimmable) Parent/Teacher Conference 500 (Dimmable) Adult Toilet 150 - 250 Central Storage 250 - 350 Laundry 300 - 400 Kitchen 300 - 500 Janitor’s Closet 300 - 400 Telephone Closet 400 - 500 Multiple-Purpose Space Play Area 300 - 500 Meeting Area 300 - 500 (Dimmable) Play Yard Storage 300 - 500 Infant Activity Area Natural light 250 - 500 (Quiet areas dimmable) Toddler Activity Area Natural light 300 - 500 (Quiet areas dimmable) Pre-Schooler Activity Area Natural light 300 - 500 (Quiet areas dimmable) PBS-140 - July 2003 CHAPTER 10: TECHNICAL CRITERIA School-Age Activity Area Natural light 300 - 750 (Quiet areas dimmable) Food Preparation 300 - 750 Eating Natural light 300 - 500 Cubby Storage Area/Locker 300 - 500 Children’s Art Sink Natural light 500 - 750 (Dimmable) Sleeping/Crib/Napping 50 - 500 (Dimmable) Diapering Station 300 - 500 Children’s Toilet 300 - 500 Children’s Handwashing Sink 300 - 500 Children’s Private Toilet 300 - 500 Minimize exterior light pollution, as described in LEED Version 2.0, by designing lighting as follows: � Exterior lighting not to exceed Illuminating Engineering Society of North America (IESNA) footcandle level requirements, as stated in the Recommended Practice Manual: Lighting for Exterior Environments. � Interior and exterior lighting such that zero direct-beam illumination leaves the building site. � Design lighting controls to provide a high level of occupant control over interior lighting levels, including controls at child height where appropriate. � Use compact fluorescent lamps (CFLs) instead of incandescent lamps as a general rule. CFLs should meet, at a minimum, the efficiency standards of the EPA Energy Star program. Exit signs should use LED technology and should also be EPA Energy Star labeled. 10-11

CHAPTER 10: TECHNICAL CRITERIA<br />

Whenever possible, provide HVAC separate from the other building<br />

systems. Apart from other advantages, this will facilitate better filtration of<br />

the dust and molds to which many children are particularly sensitive. Air<br />

diffusers should minimize drafts on children.<br />

<strong>Design</strong> ventilation systems to allow zero exposure of non-smokers to environmental<br />

tobacco smoke (ETS) even if smoking is limited to outdoor areas,<br />

as described in LEED Version 2.0. <strong>Design</strong> ventilation systems to<br />

achieve an air-change effectiveness of minimum 0.9 per ASHRAE 129-<br />

1997 and as described in LEED Version 2.0. Locate air return over diaper<br />

and toilet areas.<br />

10.9.3 Safety Issues:<br />

<strong>The</strong> following restrictions apply in child care centers:<br />

� Heating units that utilize flame must be vented properly to the outside<br />

and shall be supplied with sufficient combustion air.<br />

� Heating units hotter than 43 °C shall be made inaccessible to children<br />

by the use of barriers such as guards or locks.<br />

� Ensure that any gas-fired equipment takes 100% outside air for combustion<br />

to minimize negative pressure potential and the resulting backdrafting<br />

of combustion products into the indoor environment.<br />

10.10 Lighting<br />

Well-considered lighting for each activity area is a key element in creating<br />

the “home-like” environment which is a goal of the program. <strong>The</strong> quality of<br />

light should remind children of a residential environment. Broad ambient<br />

lighting is most appropriate for large motor activity spaces; task lighting is<br />

required for manipulative activities; lower light levels are needed for quiet<br />

and sleeping areas. <strong>The</strong> amount and orientation of natural light needs to<br />

be considered in the design and variation in light levels. Up to a maximum<br />

of 500 lx will be acceptable in rooms with poor natural lighting capability.<br />

Classrooms without skylights or exterior windows should have ducted light<br />

tubes to provide natural light. Light shelves which transmit light deeper<br />

into the interior are to be considered for all south-facing elevations. See<br />

the table for the minimum light levels for various functions. In addition, the<br />

following should be provided:<br />

� 500 lx on children’s work surface for reading and close work.<br />

� 250 lx ambient light for class and play areas (additional task lighting<br />

up to 500 lx provided where appropriate).<br />

� Capability of being dimmed in a range of 500 lx to 50 lx for sleeping<br />

and napping areas.<br />

10-10<br />

� 100 lx in stairs and corridors.<br />

� Light fixtures in classrooms and nap rooms are to be dimmable.<br />

Light levels in all rooms, including sleeping rooms, must be maintained at<br />

a sufficient level to provide visual observation of the space from adjoining<br />

spaces. Lighting should be utilized to emphasize areas, designate<br />

boundaries, create a particular feeling, or cause a desired response.<br />

When using fluorescent lighting, utilize electronic ballast light fixtures. <strong>The</strong>ir<br />

high frequency cycles avoid perceptible flickering and allow dimming.<br />

Fluorescent lamps are to have a color temperature of 3500 degrees Kelvin<br />

minimum with the highest possible color rendering index (CRI). Minimum<br />

CRI is to be 80 or greater. This is of paramount importance to the center’s<br />

environmental quality. If there is adequate ceiling height, the better quality<br />

of reflected, ambient lighting from pendants or recesses is strongly preferred<br />

to troffer-style fluorescent fixtures. If troffer flourescents must be used,<br />

use lamps which are to be baffled to provide predominantly indirect lighting.<br />

With reflected light, children (who are at a far lower vantage point than<br />

adults) will not look directly into the light source, a condition which causes<br />

glare and eye fatigue. Task lights, such as those provided by residential<br />

type pendant fixtures, should be used for reading, painting, and close work.<br />

<strong>Design</strong> for variety in lighting, through such devices as dimming controls,<br />

separate switching, adjustable directional fixtures, and pendant fixtures<br />

that are positioned over work areas. Consider using specialized lighting to<br />

display art work, pools of light to create excitement and variety, and high<br />

levels of light to encourage physical activity. Provide food preparation areas<br />

with fixtures having shielded or shatterproof bulbs.<br />

Exterior light can be controlled with adjustable blinds, shades, or other<br />

types of window coverings. Window treatments on interior windows must<br />

allow for clear visibility.<br />

Ensure that there is adequate exterior lighting to allow safe exterior<br />

circulation and site security. All lamps must have shatterproof lenses or<br />

covers.<br />

<strong>PBS</strong>-<strong>140</strong> - July 2003

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!