Geotechnical Investigation South River Place, Gasser Drive, Napa 29 December 2010<br />

________________________________________________________________________________________________________<br />

Foundations<br />

Based on our field and laboratory investigation, the subsurface soils have the potential for<br />

settlement due to seismically induced liquefaction and consolidation of the subsurface soils as<br />

identified above. As stated above, the liquefaction and consolidation hazards must be mitigated by<br />

over-excavation and recompaction of the old fill soils or by in-situ densification. In addition, the<br />

site’s near surface foundation soils are considered to have a low to high expansion potential and<br />

susceptible to potential differential movements due to variations in moisture content. Therefore,<br />

provided the building pads are graded as recommended above, the buildings may be satisfactorily<br />

supported on a deepened, interconnected spread footing foundation system in conjunction with<br />

interior slabs-on-grade. Recommendations for the spread footing foundation system where<br />

densification by conventional grading techniques is performed are presented below. If in-place<br />

densification is performed, the foundation criteria should be provided by the densification designer.<br />

Spread footings should extend to a minimum depth of 30 inches below lowest adjacent pad grade<br />

(i.e., trenching depth). At this depth, the recommended design bearing pressure should not<br />

exceed 2,000 p.s.f. due to dead plus sustained live loads. The above allowable pressure may be<br />

increased by 1/3 due to all loads which include wind and seismic. Isolated footings are not<br />

recommended. All footings must be interconnected with continuous footings or tie-beams. All<br />

foundations must be adequately reinforced to provide structural continuity and resist the<br />

anticipated loads as determined by the project Structural Engineer. However, continuous<br />

footings are to be reinforced with a minimum of 4 No. 5 bars, 2 at the top and 2 near the bottom<br />

of the footing. Additional reinforcement will be as required by the structural engineer and in<br />

accordance with structural building code requirements. Foundations designed in accordance<br />

with the above criteria should be expected to experience a total settlement of 1 inch and a<br />

differential of ½ inch.<br />

To accommodate lateral building loads, the passive resistance of the foundation soil can be<br />

utilized. The passive soil pressures can be assumed to act against the front face of the footing<br />

below a depth of 1 foot below the ground surface. It is recommended that a passive pressure<br />

equivalent to that of a fluid weighing 250 p.c.f. be used. For design purposes, an allowable<br />

friction coefficient of 0.30 can be assumed at the base of the spread footings.<br />

Two bag samples of the near surface soils on Retail 1 and 2 pads were collected and transported<br />

to Sunland Analytical in Rancho Cordova for testing of water soluble sulfates in accordance with<br />

California Test Method 417. The testing indicates a sulfate content ranging from 32.3 to 124.0<br />

ppm (mg/kg) for the samples collected. Based on exposure conditions as identified in Table 19-<br />

A-4 of the California Building Code, the building site is classified as “Negligible” which<br />

requires no special provisions for cement type, concrete strength, or water/cement ratio.<br />

________________________________________________________________________________________________________<br />

KC ENGINEERING COMPANY Project No. VV3200 Page 20 of 123