2.07 ACCESSORY COMPONENTS AND FEATURES<br />

A. Furnish accessory set including tools and miscellaneous items required for overcurrent<br />

protective device test, inspection, maintenance, and operation.<br />

PART 3 - EXECUTION<br />

3.01 INSTALLATION<br />

A. Install panelboards and accessories according to NEMA PB 1.1.<br />

B. Mount top of trim 74 inches (1880 mm) above finished floor, unless otherwise indicated.<br />

C. Mount plumb and rigid without distortion of box. Mount recessed panelboards with fronts<br />

uniformly flush with wall finish.<br />

D. Install overcurrent protective devices and controllers.<br />

E. Install filler plates in unused spaces.<br />

F. Stub four 1-inch (27-GRC) empty conduits from panelboard into accessible ceiling space<br />

or space designated to be ceiling space in the future. Stub four 1-inch (27-GRC) empty<br />

conduits into raised floor space or below slab not on grade.<br />

G. Arrange conductors in gutters into groups and bundle and wrap with wire ties.<br />

3.02 IDENTIFICATION<br />

A. Identify field-installed conductors, interconnecting wiring, and components; provide<br />

warning signs as specified in Section "Electrical Identification."<br />

B. Panelboard Nameplates: Label each panelboard with laminated-plastic nameplate<br />

mounted with corrosion-resistant screws.<br />

3.03 CONNECTIONS<br />

A. Ground equipment according to Section "Grounding and Bonding."<br />

B. Connect wiring according to Section "Conductors and Cables."<br />

3.04 FIELD QUALITY CONTROL<br />

A. Prepare for acceptance tests as follows:<br />

1. Test insulation resistance for each panelboard bus, component, connecting<br />

supply, feeder, and control circuit.<br />

2. Test continuity of each circuit.<br />

B. Testing Agency: The Contractor will engage a qualified testing and inspecting agency to<br />

perform field tests and inspections and prepare test reports. The Contractor is responsible<br />

11020 PANELBOARDS<br />

06/21/10: jmy: REV. 07/11 16442 -6 LPAS PROJECT NO.