E. Comply with NEMA PB 1.<br />

F. Comply with NFPA 70.<br />

1.06 PROJECT CONDITIONS<br />

A. Environmental Limitations: Rate equipment for continuous operation under the following<br />

conditions, unless otherwise indicated:<br />

1. Ambient Temperature: Not exceeding 104 deg F (40 deg C).<br />

2. Altitude: Not exceeding 6600 feet (2000 m).<br />

B. Interruption of Existing Electric Service: Do not interrupt electric service to facilities<br />

occupied by Owner or others unless permitted under the following conditions and then<br />

only after arranging to provide temporary electric service according to requirements<br />

indicated:<br />

1. Notify Construction Manager no fewer than two weeks in advance of proposed<br />

interruption of electrical service.<br />

2. Do not proceed with interruption of electrical service without Construction<br />

Manager's written permission.<br />

1.07 COORDINATION<br />

A. Coordinate layout and installation of panelboards and components with other construction<br />

that penetrates walls or is supported by them, including electrical and other types of<br />

equipment, raceways, piping, and encumbrances to workspace clearance requirements.<br />

B. Coordinate size and location of concrete bases for free standing panels. Cast anchor-bolt<br />

inserts into bases. Concrete, reinforcement, and formwork requirements are specified in<br />

Division 3.<br />

PART 2 - PRODUCTS<br />

2.01 MANUFACTURERS<br />

A. Manufacturers: Subject to compliance with requirements, provide products by one of the<br />

following:<br />

1. Panelboards, Overcurrent Protective Devices, Controllers, Contactors, and<br />

Accessories:<br />

a. Eaton Corporation; Cutler-Hammer Products.<br />

b. General Electric Co.; Electrical Distribution & Protection Div.<br />

c. Square D.<br />

11020 PANELBOARDS<br />

06/21/10: jmy: REV. 07/11 16442 -3 LPAS PROJECT NO.