D. Terminate conductors No. 10 AWG and smaller specified in Division 26 to be stranded,<br />

with crimp type lug or stud. Direct termination of stranded conductors without crimp<br />

terminator to terminal screws, lugs, or other points is not permitted even if terminal is rated<br />

for stranded conductors. Crimp terminal shall be the configuration type suitable for<br />

terminal point. T&B “Sta-Kon” or equal.<br />

3.04 FIELD QUALITY CONTROL<br />

A. Testing: Contractor will engage a qualified testing agency to perform field quality control<br />

testing. The Contractor is responsible for coordinating the schedule of the testing agency<br />

to ensure no impact on the construction schedule. The Contractor shall pre-test all<br />

conductors and cable for opens, shorts, and grounds.<br />

B. Test Reports: Prepare a written report to record the following:<br />

1. Each cable and conductor tested.<br />

2. Test results that comply with requirements.<br />

3. Test results that do not comply with requirements and corrective action taken to<br />

achieve compliance with requirements.<br />

END OF SECTION 26 05 19<br />

11020 CONDUCTORS AND CABLES<br />

06/21/10: jmy: REV. 07/11 16120 -4 LPAS PROJECT NO.