E. Fire Alarm: EMT or Plenum Cable as allowed by the Governing Authorities (except as specifically<br />

detailed on the drawings). All cable to be stranded.<br />

F. Projection and Sound: As indicated on the drawings<br />

G. Smurf is not acceptable.<br />

2.03 DIMMERS<br />

A. Dimmers located in the projection booth serving the auditoriums will be furnished by the Owner,<br />

installed by the contractor. For installation and wiring, see drawings.<br />

B. All other dimmers, including wall box dimmers located in the auditoriums, will be furnished and<br />

installed by the contractor.<br />

2.04 DRY TYPE TRANSFORMERS<br />

A. Dry type transformers shall be of rating shown on plan and for 480 volts Delta Primary connection and<br />

120/208 volt, 3-phase, 4-wire, Wye secondary.<br />

B. Provide four 2-1/2 % full capacity taps in primary winding, two above and two below normal voltage.<br />

C. The insulation system shall be for 220 degrees C. and the transformer designed for 150 degrees C.<br />

above a 40 degree C. ambient temperature.<br />

D. Transformer shall have steel enclosure with knockouts for conduit connections.<br />

E. The transformer will be for floor or wall mounting.<br />

F. The transformer manufacturer will be the same as the approved panelboard manufacture.<br />

G. Provide 1/2" Neoprene pads below transformers.<br />

H. Exterior transformers shall have NEMA 3 enclosures.<br />

I. Maximum impedance shall be as scheduled on the drawings or 5.5% maximum.<br />

J. Transformers shall be “Energy Star” compliant (TP1) and shall meet the energy code<br />

requirements for impedance.<br />

2.05 SERVICE SWITCHBOARD<br />

A. Provide a service panelboard as scheduled on drawings.<br />

B. Service panelboard shall have grounded bus, neutral bus, removable tie between grounded bus,<br />

neutral, and removable link in neutral.<br />

C. Service panelboard shall have service entrance rating.<br />

D. Provide fused switches or breakers as scheduled.<br />

E. Label all circuits.<br />

F. Circuit Breakers<br />

1. Group mounted molded case circuit breakers are to be totally front accessible.<br />

2. The circuit breakers are to be mounted in the switchboard to permit installation, maintenance<br />

and testing without reaching over any line side bussing.<br />

3. The circuit breakers are to be removable by the disconnection of only the load side cable<br />

terminations and all line and load side connections are to be individual to each circuit<br />

breaker.<br />

4. No common mounting brackets or electrical bus connectors will be acceptable.<br />

5. Breakers shall be the over-the counter toggle operating type with the handle going to a<br />

position between "On" and "Off" to indicate automatic tripping.<br />

Cinemark 16050 - 2 Basic Electrical Materials and Methods<br />

South Napa Century Center XD 12 EnviroDesign, Inc., Bid Issue 7-7-11