not acceptable.<br />

5. Bearings shall be corrosion resistant, molded synthetic sleeve type turning in an extruded<br />

hole in the damper frame. Axles shall be ½” (13) plated steel, hexagonal shaped and<br />

positively locked into the damper blade (round axles are not acceptable).<br />

6. Linkage shall be concealed out of airstream, within the damper frame to reduce pressure<br />

drop and noise and lessen the need for maintenance.<br />

7. Submittals must include leakage, maximum airflow and maximum pressure ratings based on<br />

AMCA Publication 500. Damper leakage shall not exceed 10 cfm per square foot at 4” sp.<br />

8. Damper shall be equal to Ruskin model CD36.<br />

L. Electronic / Electric Damper Actuators:<br />

1. Manufactured, brand labeled or distributed by BELIMO or equal.<br />

2. Size for torque required for damper seal at load conditions.<br />

3. Coupling: V-bolt dual nut clamp with a V-shaped, toothed cradle.<br />

4. Mounting: Actuators shall be capable of being mechanically and electrically paralleled to<br />

increase torque if required.<br />

5. Overload Protection: Electronic overload or digital rotation-sensing circuitry without the use<br />

of end switches to prevent any damage to the actuator during a stall condition.<br />

6. Fail-Safe Operation: Mechanical, spring-return mechanism<br />

7. Power Requirements (Spring Return): 24 V ac, maximum 10 VA at 24-V ac or 8 W at 24-V<br />

dc.<br />

8. Temperature Rating: -22 to +122ºF<br />

9. Housing: Minimum requirement NEMA type 2 / IP54 mounted in any orientation.<br />

10. Agency Listing: ISO 9001, cULus, and CSA C22.2 No. 24-93.<br />

11. The manufacturer shall warrant all components for a period of 5 years from the date of<br />

production, with the first two years unconditional.<br />

2.10 FANS<br />

A. Furnish and install the fans as scheduled on drawings.<br />

B. Rated and labeled by AMCA.<br />

C. Switched as shown on Electrical drawings.<br />

D. Equipped with manual reset firestats.<br />

E. Furnish fans pre-wired thermal disconnect switches and 16" high factory curb or height as<br />

scheduled. The motorized dampers shall be shipped pre-wired from the factory or field wired by<br />

the mechanical contractor.<br />

F. Direct drive fans shall be furnished with SCR variable speed controllers factory wired internal to<br />

the fan.<br />

G. Fans to be as manufactured by Cook, Acme, or Greenheck.<br />

2.11 ROOFTOP UNIT<br />

A. Units and curbs shall be furnished as specified on the drawings.<br />

B. Install heating and cooling units as scheduled and detailed. Units shall be factory assembled<br />

and tested complete and ready for operation, except for the economizer components (and/or<br />

outside air intakes) which shall be field installed by the mechanical contractor.<br />

C. Each unit shall be provided with 16" high 14 gauge galvanized steel fabricated roof-mounting<br />

frame. Curbs formed as detailed with corners riveted or welded as required for strength. Curbs<br />

shall be self-supporting and shall be sloped to match the roof slope and maintain the units level.<br />

Curbs shall be the acoustic type shown on the drawings (factory installed acoustic fill) as<br />

manufactured by ThyBar.<br />

Cinemark 15500 - 7 Heating, Ventilating and Air Conditioning<br />

South Napa Century Center XD 12 EnviroDesign, Inc., Bid Issue 7-7-11