G. Combination Fire/Smoke dampers, galvanized steel, UL label fire equal to Ruskin FSD60 with<br />

TS150. Coordinate the exact power requirements with the electrical contractor.<br />

1. Provide combination fire and smoke dampers where shown on the drawings. Dampers shall<br />

meet all requirements of fire dampers and additionally shall include an operating shaft,<br />

which, when rotated 90° causes the damper to operate between closed and open.<br />

2. Each damper shall be furnished complete with factory sleeve and damper operator (electric<br />

to conform to control system) factory installed on exterior of sleeve and properly linked to<br />

damper operating shaft. Operators shall be UL listed and labeled as Fire Damper<br />

Operators.<br />

3. Provide access doors for fire and smoke dampers as specified for fire dampers.<br />

4. The fire dampers shall be normally closed, held open with 120V power. Upon loss of power,<br />

the dampers shall shut, upon regaining power, the damper shall open.<br />

H. Mark all air balancing devices in balanced position with permanent paint. Tie a ribbon around<br />

the exposed handle.<br />

I. All duct connections shall have balance dampers whether shown on the drawings or not.<br />

J. SMOKE DAMPERS<br />

1. All motorized smoke dampers shall be furnished under this Section and installed per the<br />

manufacturer's UL installation instructions.<br />

2. Smoke dampers shall be qualified to and listed under Underwriters' Laboratories Standard<br />

UL 555S, September 1983 or latest version for Leakage Class II (10 cfm/SF at 1 inch W.G.)<br />

performance after 30 minute exposure at 350oF. Dampers shall also conform to NFPA 90A<br />

smoke damper requirements.<br />

3. Damper frames shall be constructed of minimum #16 gauge galvanized steel channel and<br />

shall have flanges for duct mounting. All blade to blade linkage on each section shall be<br />

concealed within the damper frame. In no case shall the section linkage be exposed to the<br />

air stream. The maximum size of single section not larger than 48 inches or less in width<br />

and 72 inches or less in height. The blades of multiple section dampers shall be<br />

interconnected with appropriate jack shafts.<br />

4. Damper blades shall not exceed 6 inches in width. Larger damper sections shall be of<br />

multiple blade type construction. Blades shall be constructed of galvanized steel with<br />

minimum #16 gauge equivalent thickness. Blade pins and linkage shall be zinc-plated steel.<br />

Bearings shall be stainless steel or oil-impregnated sintered bronze. Blade seals shall be<br />

silicone rubber, compression type flexible steel or a combination of both.<br />

5. Operators shall be mounted by the damper manufacturer at the time of damper fabrication<br />

and shall be provided with the damper as a single unit. Operators shall be qualified and<br />

labeled under UL 555S, September 1983 or later version.<br />

6. Operators shall be electric, 120V, rated to 350oF. The operators shall be of sufficient<br />

demonstrated power to open the dampers from a fully closed position against a 4 inch W.G.<br />

static pressure differential and to close the dampers from a fully open flow rate of 3000 fpm.<br />

Operators shall be mounted outside of the air stream and shall be for normally closed<br />

damper operation.<br />

7. Approved manufacturers: Ruskin Model SD60 or equivalent.<br />

K. Motorized/Automatic Control Dampers:<br />

1. Furnish and install, at locations shown on plans, or in accordance with schedules. Control<br />

damper shall be manufactured by an ISO 9001 accredited manufacturer that meets the<br />

following minimum construction requirements.<br />

2. Damper frames (when size permits) shall be constructed using roll-formed structural hat<br />

channels, reinforced at the corners, formed from a single piece of minimum 16 gauge (1.6)<br />

galvanized steel.<br />

3. The roll-formed frames shall be structurally superior to13 gauge U-channel frames. The<br />

blades shall be opposed blade, single skin, 16 gage (1.6) galvanized steel with three<br />

longitudinal grooves for reinforcement. Blade edge seals shall be PVC coated polyester<br />

fabric suitable for -25°F to +180°F (-32°C to +83°C) mechanically locked into the blade<br />

edge.<br />

4. Jamb seals shall be flexible stainless steel metal, compression type to prevent leakage<br />

between end of the blade and the damper frame. Use of the blade end to overlapping frame<br />

for jamb seal is not acceptable. Adhesive or clip-on type seals for blade and jamb seals are<br />

Cinemark 15500 - 6 Heating, Ventilating and Air Conditioning<br />