SECTION 15500<br />

HEATING, VENTILATING AND AIR CONDITIONING<br />

PART 1 - GENERAL<br />

1.01 RELATED DOCUMENTS<br />

A. The general provisions of the Contract, including General and Supplementary Conditions, apply to the<br />

work specified in this Section.<br />

1.02 RELATED WORK SPECIFIED ELSEWHERE<br />

A. All other Sections of Division 15.<br />

B. All other Divisions of the Contract Documents. Refer to each Division's specifications and drawings<br />

for all requirements.<br />

C. Section 16900<br />

1.03 SCOPE<br />

A. Provide a complete heating, ventilating and air conditioning systems including all air distribution, as<br />

indicated on the drawings and in these specifications.<br />

B. Meet or exceed the minimum requirements of local heating, ventilating and air conditioning codes.<br />

C. Provide shop drawings and submittal data for approval. Refer to Section 15000. No work is to be<br />

installed without approved shop drawings.<br />

D. HVAC Contractor must be certified by the Environmental Protection Agency (EPA) to handle<br />

refrigerant and maintain records of their certification throughout the duration of the project and during<br />

the subsequent one year warrantee period.<br />

E. The HVAC Contractor shall closely coordinate the locations of all roof top equipment with the steel<br />

erector/fabricator and the structural drawings. The contractor shall verify all roof (and slab)<br />

penetration sizes and modify the sizes and or the locations of the penetrations such that the ducts<br />

and the associated duct fittings fit within the structural members. The contractor shall locate the<br />

openings dimensionally from the closest structural member. These requirements apply to both the<br />

Owner furnished equipment and the equipment furnished by the HVAC contractor.<br />

.<br />

F. The HVAC Contractor shall make the preparation for and corrections necessary for the testing,<br />

adjusting and balancing of the HVAC systems.<br />

G. Parts and labor warranty for the Owner furnished equipment is to be furnished by the Owner for a<br />

period of one year. All other products and the labor associated warranty is the responsibility of the<br />

contractor. The service calls for the HVAC shall be made on a 24-hour, seven days a week basis.<br />

H. The contractor shall perform the start-up of the all furnished HVAC equipment.<br />

I. At the completion of the project, the test and balance contractor shall furnish and install<br />

(replace) all of the RTU factory variable sheaves with new fixed sheaves.<br />

1.04 PERMITS - INSPECTIONS<br />

A. Secure and pay for all permits and inspections by regulating authorities.<br />

B. Perform work in accordance with all governing regulations.<br />

1.05 CONTRACT DRAWINGS<br />

A. Heating, ventilating and air conditioning work shown on drawings.<br />

B. Supplementary drawings or details will be furnished if necessary.<br />

C. Refer also to Architectural interior details, floor plans and elevations, structural and other<br />

Cinemark 15500 - 1 Heating, Ventilating and Air Conditioning<br />

South Napa Century Center XD 12 EnviroDesign, Inc., Bid Issue 7-7-11