iron bodies for 125 lbs. WWP, all bronze trim and flanged ends.<br />

3. Interior check valves 2" and smaller shall be all bronze swing check valves with screwed<br />

ends, for 125 lbs. WWP.<br />

4. Interior check valves 2-1/2" and larger shall be iron or semi-steel bronze trim, swing check<br />

valves with flanged ends for 125 lbs. WWP.<br />

5. Drain and test valves shall be 125 lb. V.O.G., bronze threaded globe valves with renewable<br />

composition disc.<br />

2.03 SPRINKLERS<br />

A. Sprinklers shall be provided throughout the entire project except (when approved by the local<br />

authorities) in rooms containing electrical generators, electrical transformers, or electrical<br />

switchboards. The sprinklers shall be as specified below except when the governing authorities or<br />

FM require quick response sprinklers. In that case the sprinklers shall be as specified below, except<br />

135ºF rated.<br />

1. THEATER AUDITORIUMS: Recessed or exposed pendant,, 165F, flat black heads and flat<br />

black escutcheons. Note that these can be standard (recessed) or extended coverage<br />

(pendants) heads.<br />

2. THEATER LOBBY AREA WITHOUT CEILINGS: Pendant, 165F, with color as selected by<br />

the architect.<br />

3. THEATRE LOBBY AND PUBLIC AREAS WITH CEILINGS: Recessed 165F, white in white<br />

ceilings. Centered in tiles one way.<br />

4. PROJECTION BOOTH AND MEZZANINE AREAS: with Ceilings: Recessed, 165F, white<br />

heads and white escutcheons. Without ceilings: Upright, black brass pendants.<br />

5. NON-PUBLIC AREAS: Recessed pendants, 165F, white heads and white escutcheons<br />

6. ALL ELECTRIC ROOMS: When required by the local authorities, heads are to be located in<br />

the electric room and shall be 212F.<br />

7. Any special sprinklers required by UL shall be provided.<br />

8. Upright heads to be provided in rooms without ceilings.<br />

9. Piping in areas having a ceiling shall be concealed.<br />

10. Unless noted otherwise, sprinklers shall be centered in the tile in one direction, located no<br />

closer than 6" to the edge of tile in the other direction.<br />

11. No extended coverage sprinklers shall be used, except in the auditoriums and main lobby,<br />

and only upon permission of the authorities having jurisdiction.<br />

12. Sprinkler heads in the vestibule shall be the extended barrel, freeze-proof type, recessed.<br />

13. Trash alcoves and all other ceilings or soffits 8 ft and lower shall have concealed heads with<br />

cover plates to match the surrounding ceiling color.<br />

B. Hangers: Shall be installed as required and shall be listed by the Underwriters' Laboratories for use in<br />

a sprinkler system. Hangers shall be spaced in accordance with the requirements of the NFPA.<br />

C. Sprinkler Cabinet:<br />

1. One cabinet with a minimum of twelve (12) sprinklers and a head wrench shall be installed in<br />

the concession work room.<br />

2. Included in the cabinet shall be a minimum of two (2) sprinklers for each special temperature<br />

or configuration.<br />

3. The cabinet shall be so located that it will not be subject to an ambient temperature<br />

exceeding 100ºF.<br />

2.04 FIRE DEPARTMENT CONNECTIONS<br />

A. Furnish and install fire department connections with check valve and approved automatic drip where<br />

indicated on the plans or as required by the authorities as follows:<br />

1. Wall siamese inlet shall be Allenco's No. 276, flush type with clapper valves, straight way<br />

body and caps with chains, ball drip piped to spill on grade thru wall and check valve.<br />

Threads shall match Local Fire Department. Exposed finish shall be polished brass.<br />

Cinemark 15300 - 4 Fire Protection<br />

South Napa Century Center XD 12 EnviroDesign, Inc., Bid Issue 7-7-11