SECTION 09510<br />

ACOUSTICAL CEILINGS<br />

PART 1 - GENERAL<br />

1.01 SCOPE<br />

A. Provide Acoustical Ceiling work as indicated by the Contract Documents.<br />

B. Work, items and requirements specified elsewhere that apply and/or relate to this Section include:<br />

1. Gypsum Wallboard - Section 09250<br />

2. Building Insulation - Section 07210<br />

3. Painting - Section 09900<br />

4. Electrical - Division 16.<br />

1.02 STANDARDS AND QUALITY<br />

A. Meet requirements and recommendations of applicable portions of the Standards listed.<br />

1. Underwriters Laboratories, Inc. UL<br />

2. Acoustical and Insulation Materials Assoc. AIMA<br />

3. Suspended Ceiling Manufacturers Assoc. SCMA<br />

1.03 QUALITY ASSURANCE<br />

A. Applicator Qualifications: Applicator shall have satisfactorily installed accepted suspension system and<br />

acoustical units on at least three other projects of equal scope.<br />

B. Design Criteria:<br />

1. Deflection: Suspension system components, hangers and fastening devices shall support light fixtures,<br />

ceiling grilles, and acoustical units without deflecting more than 1/360 of the span.<br />

2. Test for deflection in accordance with methods and procedures prescribed by ASTM C636-92 with latest<br />

revisions.<br />

3. Reduce hanger spacing as required to satisfy design criteria.<br />

4. Increase hanger sizes as required to satisfy design criteria.<br />

5. Increase members and components of system, as required, to satisfy design criteria.<br />

C. Fire Safety Requirements:<br />

1. Maximum flame spread index of acoustical materials: 25.<br />

2. Flame spread index shall be listed by UL Building Materials List or determined by ASTM E84-95b.<br />

D. Allowable tolerance of finished acoustical ceiling system: Level within 1/8" of 12'.<br />

E. To insure proper interface and color match, all acoustical panel units and grid components shall be produced or<br />

supplied by a single manufacturer. Materials supplied by more than one manufacturer are not permissible.<br />

F. Suspended Ceiling Requirements for Seismic Projects:<br />

1. Installation must confirm to CISCA recommendations for areas subject to severe seismic activity.<br />

2. Minimum 2” wall moulding<br />

3. Grid must be attached to two adjacent walls opposite walls must have ¾” clearance<br />

4. Ends of main beams and cross tees must be tired together to prevent their spreading<br />

5. Perimeter support wires<br />

6. Heavy-duty grid system<br />

7. Ceiling areas over 1,000 SF must have horizontal restraint wire or rigid bracing<br />

8. Ceiling areas over 2,000 SF must have seismic separation Joints or full height partitions<br />

9. Ceilings without rigid brace must have 2” oversized trim rings for sprinklers and other pentrations<br />

10. Chnaged in ceiling plane must have positive bracing<br />

11. Cable trays and electrical conduits must be independently supported and braced<br />

12. Suspended ceiling will be subject to special inspection.<br />

1.04 SUBMITTALS<br />

A. Refer and comply with Section 01340 - Submittals.<br />

B. Submit a sample of each color of ceiling tiles and each color of suspension systems that are being proposed for<br />

the installation to the Architect for approval.<br />

1.05 DELIVERY AND STORAGE<br />

A. Schedule deliveries to avoid delays in the work.<br />

B. Deliver and store materials in their original unopened protective containers.<br />

NAPA CENTURY CENTER XD 12<br />