PART 1 - GENERAL<br />

SECTION 07210<br />

BUILDING INSULATION<br />

1.01 SCOPE<br />

A. Provide Building Insulation work as indicated by the Contract Documents and as described herein.<br />

B. Work, items and requirements specified elsewhere that apply and/or relate to this Section include:<br />

1. Light Gage Metal Framing - Section 05400<br />

2. Gypsum Wallboard - Section 09250<br />

3. Mechanical - Division 15<br />

1.02 STANDARDS<br />

A. Meet requirements and recommendations of applicable portions of the Standards listed.<br />

1. American Society for Testing and Materials ASTM<br />

2. National Mineral Wool Insulation Association NMWIA<br />

3. Federal Specifications Fed. Spec.<br />

1.03 SUBMITTALS<br />

A. Refer to Section 01340 - Submittals.<br />

B. Submit two samples of each type of insulation required.<br />

C. Technical Data: Submit technical data indicating thermal conductance factors of furnished insulation.<br />

D. Recycled Content:<br />

1. Indicate recycled content; indicate percentage of pre-consumer and post-consumer recycled content per<br />

unit of product.<br />

2. Indicate material cost of product less labor included in project.<br />

3. If recycled content product is part of an assembly, indicate the percentage of recycled content product in<br />

the assembly by weight.<br />

E. Local/Regional Materials:<br />

1. Sourcing location(s): Indicate location of extraction, harvesting, and recovery; indicate distance between<br />

extraction, harvesting, and recovery and the project site.<br />

2. Manufacturing location(s): Indicate location of manufacturing facility; indicate distance between<br />

manufacturing facility and the project site.<br />

3. Product Value: Indicate dollar value of product containing local/regional materials; include materials cost<br />

only.<br />

4. Product Component(s) Value: Where product components are sourced or manufactured in separate<br />

locations, provide location information for each component. Indicate the percentage by weight of each<br />

component per unit of product.<br />

1.04 DELIVERY AND STORAGE<br />

A. Schedule deliveries to avoid delays and to prevent greater accumulations than can be suitably stored at the site.<br />

B. Deliver materials to the site in manufacturer's original, unopened, labeled containers.<br />

C. Store to prevent damage from moisture and construction work.<br />

D. Protect rigid insulation from direct sunlight with a light-colored opaque polyethylene film and ventilated to<br />

prevent excessive temperature.<br />

PART 2 - PRODUCTS<br />

2.01 MATERIALS<br />

A. Insulation in Auditoriums:<br />

1. Owens Corning: #701 unfaced semi-rigid insulation in 1"or 2", thicknesses as shown on Drawings, refer<br />

to Finish Schedule. Install at both side walls and projection wall of each auditorium at locations shown on<br />

the drawings. This acoustical insulation product will comply with ASTM C553, Mineral Fiber Blanket<br />

Thermal Insulation, Type III. Nominal Density per ASTM C 167 of 1.5 pcf.<br />

2. Owens Corning: #703 ASJ faced semi-rigid insulation in 2" thickness. Install at all exterior walls of each<br />

auditorium. This acoustical insulation product will comply with ASTM C 612 Mineral Fiber Block and<br />

Board Thermal Insulation, Types IA, IB. Nominal Density per ASTM C 303 of 3.0 pcf.<br />