SECTION 16470 - PANELBOARDS<br />

PART 1. - GENERAL<br />

1.1 SUMMARY<br />

A. Section Includes: Provide panelboards wherever required by the Drawings and<br />

Specifications.<br />

1.2 SYSTEM DESCRIPTION<br />

A. Circuit Numbers: Circuit numbers shown on Drawings shall be used for reference only.<br />

Actual connections shall be in accordance with phasing of cabinet, load balance and<br />

common neutral requirements.<br />

B. Contractor shall contact local power utility anc coordinate all service requirements and<br />

pay all associated fees and charges.<br />

1.3 SUBMITTALS<br />

A. Shop Drawings: Provide Shop Drawings in accordance with Section 16010.<br />

1.4 QUALITY ASSURANCE<br />

A. Regulatory Requirements: Construct panelboards to NEMA and Underwriters’<br />

Laboratories (UL) standards.<br />

PART 2. - PRODUCTS<br />

2.1 MANUFACTURERS<br />

A. Acceptable Manufacturers: All panelboards shall be as follows:<br />

2.2 COMPONENTS<br />

1. AMP (Cutler-Hammer Components)<br />

2. Cutler-Hammer<br />

3. EMI (Cutler-Hammer Components)<br />

4. General Electric<br />

5. Siemens-ITE<br />

6. Square D<br />

7. States Electric<br />

A. General Requirements: Panelboards shall be dead front safety type and shall be UL<br />

listed.<br />

B. Enclosures: Enclosures shall be constructed of code grade steel with concealed trim<br />

clamps and hinges. Panel front shall be lockable with all panels throughout the Project<br />

keyed alike. Provide two keys for each panel.<br />

C. Lugs: Solderless lugs only shall be provided in mains, unless otherwise noted on the<br />

Drawings and/or the Panelboard Schedule. Main lugs shall be suitable for both 60-<br />

degree- C and 75-degree-conductors. Main and neutral lugs shall be compression type.<br />

Provide sufficient number of lugs to individually terminate each conductor.<br />