1. Conductors: Copper cable, stranded of size per the NEC unless otherwise noted<br />

on Drawings.<br />

2. Bonding Jumper Braid: Copper braided tape, constructed of 30 gauge bare<br />

copper wires and properly sized for indicated applications.<br />

3. Connectors, Terminals, and Clamps: Burdy, Keamey, T & B, Penn-Union, or<br />

approved equal.<br />

4. Ground Rods: Copper clad steel, ½” diameter, a minimum of three 10 feet in<br />

length and 10’ apart.<br />

PART 3. - EXECUTION<br />

3.1 INSTALLATION<br />

A. General Requirements: Grounding and bonding shall comply with the requirements of the<br />

NEC and shall be coordinated with the local electrical inspector. This, however, shall not<br />

be construed as relieving the Contractor from meeting any requirements of the Drawings<br />

and Specifications that may exceed code requirements.<br />

3.2 GROUNDING ELECTRODE<br />

A. General Requirements: Grounding electrode shall be the metal water piping system of<br />

the building. Water piping system electrode shall be supplemented by the following<br />

additional electrodes:<br />

1. Metal Frame of Building: Metal frame of building in those buildings with a metal<br />

frame system.<br />

3.3 MAIN BONDING JUMPER<br />

A. General Requirements: Connect secondary service neutral and grounding electrode<br />

conductor to equipment grounding bus in service equipment.<br />

3.4 FEEDER AND BRANCH CIRCUITS<br />

A. General Requirements: Provide an insulated grounding conductor, sized in accordance<br />

with the NEC, within all PVC conduits, within all flexible metallic conduits and within all<br />

EMT conduits .<br />

3.5 CONDUITS, BOXES, CABINETS AND PANELBOARDS<br />

A. General Requirements:<br />

1. Ground all metallic conduit systems. Establish ground continuity by providing<br />

standard couplings, connectors, fittings and jumpers at all grounding type wiring<br />

devices, motor and ground terminals.<br />

2. Ground wires shall be grounded to each pull box, junction box, outlet box,<br />

cabinets and other enclosures through which the ground wires pass, except for<br />

special isolated grounding systems.<br />

GROUNDING SYSTEM<br />

16450-2