SECTION 16117- SAFETY SWITCHES<br />

PART 1. - GENERAL<br />

1.1 SUMMARY<br />

A. Section Includes: Provide safety switches wherever required by the Drawings and<br />

Specifications.<br />

1.2 SUBMITTALS<br />

1. Every effort has been expended to provide an accurate list of mechanical<br />

equipment motors as shown on the drawings and the Equipment Schedule.<br />

However, the Contractor shall verify motor horsepower sizes on site before<br />

installing switches or selecting fuses.<br />

A. Shop Drawings: Provide Shop Drawings in accordance with Section 16010.<br />

PART 2. - PRODUCTS<br />

2.1 MANUFACTURERS<br />

A. Acceptable Manufacturers: All safety switches shall be of one manufacturer as follows or<br />

approved equal.<br />

2.2 MATERIALS<br />

A. Type:<br />

1. Cutler-Hammer<br />

2. General Electric<br />

3. Siemens<br />

4. Square D<br />

1. Safety switches shall be fused. Non-fusible switches may be used in lieu of<br />

fusible where allowed by the National Electrical Code (NEC).<br />

2. Safety switches shall be NEMA HD (heavy duty) type, horsepower rated, and of<br />

ampere sizes shown on Drawings or as required by the NEC. Safety switches<br />

shall have NEMA I enclosures, except in wet locations or where indicated as<br />

weatherproof, in which case a NEMA 3R enclosure shall be used. Locations on<br />

roof or outside shall be considered wet locations.<br />

3. Fusible safety switches shall contain Class R fuse provisions to reject fuses,<br />

except Class R type.<br />

4. Safety switches shall contain padlocking provisions and defeater screw<br />

mechanisms. Provide interlock contacts where so specified.<br />

5. Safety switches shall be rated 250 volts where used on 120/208 volt or 120/240<br />

volt systems.<br />

6. Switches rated 30 amperes through 100 amperes shall have lugs listed for 60-<br />

degree C or 75-degree C conductors. Switches rated over 100 amperes shall<br />

have Iugs listed for 75 degrees C.<br />

END OF SECTION 16117<br />