SECTION 16113 - PULL AND JUNCTION BOXES<br />

PART 1. - GENERAL<br />

1.1 SUMMARY<br />

A. Section Includes: Provide pull boxes as required to facilitate the pulling of wires or when<br />

more than four quarter bends occur in any conduit run. No attempt has been made to<br />

show all necessary boxes on Drawings.<br />

PART 2. - PRODUCTS<br />

2.1 MATERIALS<br />

A. Type:<br />

1. Pull and junction boxes shall be sized and installed to meet requirements of<br />

Article 370 of the latest edition National Electric Code (NEC).<br />

2. Provide galvanized code-gauge sheet steel junction and pull boxes.<br />

PART 3. - EXECUTION<br />

3.1 INSTALLATION<br />

A. General Requirements: Locate pull and junction boxes shall be located so as to be<br />

accessible after building is finished. Pull and junction boxes shall not be placed in any<br />

finished spaces without prior approval of Architect/Engineer. No boxes shall be installed<br />

above plaster ceilings without prior approval of Architect/Engineer.<br />

1. Pull boxes installed above lay-in ceiling tiles shall be within twenty-four inches of<br />

ceiling for accessibility and shall not conflict with removal of ceiling tiles.<br />

2. Pull boxes shall be within twenty-four inches where installed above access<br />

panels.<br />

3.2 CONDUCTORS IN PULL BOXES<br />

A. General Requirements: Conductors shall be of sufficient length within pull boxes to neatly<br />

install and organize conductors without excess.<br />

3.3 IDENTIFICATION<br />

A. Pull Boxes: Pull boxes shall be identified as to type of system in box as follows:<br />

1. Stencil coverplate with 1/2-inch black letters in non-finished areas.<br />

2. Identify with a tag inside of box in finished areas.<br />

3. Paint boxes red and stencil “FIRE ALARM” for all boxes used for fire alarm and<br />

detection systems.<br />

B. Conductors: Identify in a permanent neat and legible manner all conductors or cables<br />

within box by means of tags, pressure sensitive tape or cable ties.<br />

END OF SECTION 16113<br />

PULL AND JUNCTION BOXES<br />

16113-1