SECTION 16111 - CONDUITS AND FITTINGS<br />

PART 1. - GENERAL<br />

1.1 SUMMARY<br />

A. Section Includes: Provide raceways wherever required by the Drawings and<br />

Specifications.<br />

PART 2. - PRODUCTS<br />

2.1 MANUFACTURERS<br />

A. Steel Conduit and Fittings: Galvanized steel by recognized manufacturers of raceway<br />

systems of type and sizes required.<br />

B. Non-Metallic Conduit: High impact PVC (Polyvinyl Chloride) Schedule 40 rated for 90-<br />

degree C wire, Underwriters’ Laboratories (UL) listed in accordance with Article 347 of<br />

the National Electric Code (NEC) for underground and exposed use. PVC conduit shall<br />

be Schedule 80 for under roadway or vehicle crossing area.<br />

C. The following manufacturers are approved for conduit:<br />

1. Alfex<br />

2. Allied<br />

3. Canon<br />

4. Republic<br />

5. Sealtight<br />

6. Triangle<br />

7. VAW of America<br />

8. Youngstown<br />

D. The following manufactures are approved for conduit fittings:<br />

2.2 CONDUITS<br />

1. Appleton<br />

2. CH<br />

3. Kellems<br />

4. OZ Red Dot<br />

5. T&B<br />

A. Minimum Size: Conduit shall be sized according to the Drawings, with no conduit smaller<br />

than ½-inch trade size. If not sized on the Drawings, the NEC shall be used to determine<br />

the size based on the number and size of conductors required with THHN/THWN<br />

insulation. The Engineer shall approve all calculated conduit sizes and method of<br />

installation prior to installation.<br />

CONDUITS AND FITTINGS<br />

16111-1