C. Direct Fired Make-Up Air Unit (MUA or SF-1) Accurex<br />

1. Install direct fired make-up air heaters as scheduled. Units shall be ETL or UL<br />

listed.<br />

2. Units shall be factory assembled and shipped as a complete packaged assembly<br />

and shall include the following:<br />

a. Gas Burner designed to operate with an air velocity of 2,850 FPM across<br />

non-clogging stainless steel air baffles. Burner to be designed to operate<br />

at 100% thermal efficiency throughout the life of the equipment.<br />

Turndown of the burner shall be a minimum of 25:1. Entire width of<br />

burner burns at all times. Burner section shall have adjustable profile<br />

plates for field adjustment of air velocity over the burner. Provide<br />

intermittent ignition assembly.<br />

b. Forward curved, double width, double inlet blower mounted on a solid<br />

steel shaft with self aligning 100,000 hour bearings.<br />

c. Equipment casing to be 16 gauge, G90 galvanized steel around an<br />

integral support frame of structural angle. All panels shall be removable<br />

for easy access. Provide an observation port for the main and pilot<br />

flames. All controls, gas valves and modulating controls shall be<br />

mounted in a vestibule with access doors outside of the air stream.<br />

d. Gas train shall be constructed to meet State Codes, ANSI and IRI<br />

requirements. Gas train shall be selected to operate at 14” W.C. psig<br />

pressure. Regulators to be approved for non-vented service.<br />

e. Temperature controller shall be a ductstat mounted integral to the unit.<br />

f. Provide the following controls:<br />

(1) Airflow switch<br />

(2) Electronic Flame Safety Relay<br />

(3) High Temperature Limit Switch<br />

(4) Starter Interlock<br />

(5) High Gas Pressure Switch<br />

(6) Low Gas Pressure Switch<br />

(7) Adjustable Low Limit<br />

(8) Auxiliary Circuit to shut the unit down on a flame failure<br />

(9) Adjustable burner on/off economizer intake air ductstat<br />

(10) Remote panel complete with operating lights to indicate blower<br />

on and burner on, and discharge air temperature adjustment,<br />

summer-off-winter selector switch.<br />

(11) Audible alarm to signal safety shut-down<br />

(12) Shunt trip circuit breaker in source electrical panel<br />

g. Provide motorized outside air damper that complies with the damper<br />

specification in Section 15800.<br />

h. Unit shall have single point power connection with a fused disconnect.<br />

Provide filter section with cleanable aluminum filter.<br />

10/28/2011 HEATING, VENTILATING AND AIR CONDITIONING<br />