4. Heating System:<br />

a. Two stage gas heating section shall have inputs and outputs as<br />

scheduled.<br />

b. Cylindrical tube and drum heat exchanger shall be constructed of<br />

aluminized steel. Power burner shall have electric direct spark ignition,<br />

100% safety shut off electronic flame sensing controls, flame inspection<br />

glass window, pre-purging and combustion air adjustment. All controls<br />

shall be listed for operation at low outdoor air temperatures. System shall<br />

be equipped with dual limit safety controls and rated and tested<br />

according to D.O.E., F.T.C and A.G.A.<br />

5. Cabinet:<br />

6. Fans:<br />

a. Shall be of zinc coated, galvanized steel with a baked-on outdoor enamel<br />

paint finish. Base section and cabinet panels where conditioned air is<br />

handled shall be fully insulated to prevent sweating and minimize sound.<br />

a. FC centrifugal conditioned air blower shall be belt driven and be capable<br />

of delivering capacities as scheduled on the drawings,. Blower shall be<br />

statically and dynamically balanced.<br />

b. Propeller type condenser fans shall discharge vertically and be direct<br />

driven. Fan motors shall be totally enclosed with ball bearings,<br />

permanently lubricated, inherently protected and equipped with rain<br />

shield. Fans shall have a safety guard.<br />

7. Air Filters<br />

a. Throwaway 2” pleated high efficiency filters.<br />

8. Temperature Controls:<br />

a. Provide a programmable thermostat with 7-day program clock. During<br />

unoccupied periods, the RTU fan and heating section shall be energized<br />

as necessary to maintain temperature, outside dampers will be closed.<br />

b. The mechanical contractor is responsible for all control wiring.<br />

9. Provide the following options:<br />

a. Economizer<br />

b. Single point power with non fused disconnect and factory wired GFI<br />

outlet.<br />

c. Condenser coil guards<br />

d. Through the bottom electrical connections<br />

e. Five year compressor warranty<br />