2.03 FIRE EXTINGUISHER CABINETS<br />

A. (FE1 CAB): Cabinet Mounted Portable Fire Extinguishers: Type (FE1) extinguisher.<br />

B. Cabinet Configuration: Semi-recessed.<br />

1. Trim: Returned to wall surface, with 2-1/2 inch projection, 1-3/4 inch wide rolled face.<br />

2. Form cabinet enclosure with right angle inside corners and seams. Form perimeter trim<br />

and door stiles. Weld, fill, and grind components smooth.<br />

3. Metal: Formed primed steel sheet; 0.036 inch thick base metal.<br />

4. Door: 0.036 inch thick, reinforced for flatness and rigidity; latch. Hinge doors for 180<br />

degree opening with continuous piano hinge. Provide nylon catch.<br />

5. Door Glazing: Full glass, clear, 1/8 inch thick heat strengthened. Set in resilient channel<br />

gasket glazing.<br />

6. Cabinet Mounting Hardware: Appropriate to cabinet. Pre-drill for anchors.<br />

7. Finish of Cabinet Exterior Trim and Door: Manufacturer’s standard finish to accept field<br />

painting under Section 09900.<br />

8. Finish of Cabinet Interior: White enamel.<br />

2.04 ACCESSORIES<br />

A. Wall Brackets: Provide metal wall brackets with strap and fasteners, of proper size for type and<br />

capacity of extinguishers, and as required for installation conditions. Extinguisher hooks are not<br />

acceptable to hang extinguishers.<br />

PART 3 EXECUTION<br />

3.01 INSTALLATION<br />

A. Install fire extinguishers, cabinets and mounting brackets in accordance with manufacturer’s<br />

written instructions, in locations indicated on the drawings and in compliance with requirements<br />

of authorities having jurisdiction.<br />

B. Cabinets: Install fire extinguisher cabinets in locations and at mounting heights indicated.<br />

1. Fasten cabinets to structure, square and plumb.<br />

2. Remove temporary protective coverings and strippable films and clean interior and exterior<br />

surfaces.<br />

C. Brackets: Fasten mounting brackets to structure, square and plumb. Hang fire extinguishers on<br />

brackets and use straps to prevent free swinging.<br />

1. Mounting Height: Typically mount bracket at 48” A.F.F. If mounted unit projects greater<br />

than 4” out from face of wall, mount bottom of unit no greater than 27” A.F.F.<br />

3.02 SCHEDULES<br />

A. Field locate extinguishers: Maximum travel distance to extinguisher from any point in the<br />

building of 75 feet.<br />

B. Check, recharge and reuse existing extinguishers that are functional. Furnish new extinguishers<br />

as required.<br />

C. Add extinguishers as required by local fire authority.<br />

END OF SECTION<br />

04-27-11 FIRE EXTINGUISHERS AND CABINETS<br />

10523 -2