PolluTherm Integrator for measuring heat and chill energy

PolluTherm Integrator for measuring heat and chill energy

PolluTherm Integrator for measuring heat and chill energy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>PolluTherm</strong><br />

<strong>Integrator</strong> <strong>for</strong> <strong>measuring</strong><br />

<strong>heat</strong> <strong>and</strong> <strong>chill</strong> <strong>energy</strong><br />

Application<br />

Special Features<br />

The integrator <strong>PolluTherm</strong> is applicable <strong>for</strong> <strong>energy</strong><br />

consumption measurement in <strong>heat</strong>ing or cooling<br />

circuits. Optionally <strong>PolluTherm</strong> is available <strong>for</strong> the<br />

usage in combined <strong>heat</strong>ing <strong>and</strong> cooling systems,<br />

where an automatic switch-over point provides<br />

storing of <strong>heat</strong>ing <strong>and</strong> cooling <strong>energy</strong> in separate<br />

registers. This switch-over point can be changed in<br />

accordance with the <strong>heat</strong>ing <strong>and</strong> cooling system<br />

requirements even after the meter has already been<br />

installed (e.g. concrete core activation).<br />

Regarding data communication <strong>and</strong> remote reading<br />

the novel casing conception offers two slots <strong>for</strong><br />

anytime upgrade with various modules, e.g. M-Bus or<br />

remote reading pulses.<br />

After expiry of the verification period it is sufficient to<br />

exchange the internal calibrated integrator module –<br />

the outer casing including all connecting terminals<br />

can remain in the <strong>measuring</strong> point. There<strong>for</strong>e it is no<br />

longer necessary to disconnect extension cables <strong>for</strong><br />

temperature sensors, lines <strong>for</strong> data communication or<br />

mains connections when a meter exchange is<br />

necessary.<br />

✔ Compatible with almost any flow sensor type due to 9 different input pulse<br />

values (0.25 litre to 10,000 litres)<br />

✔ For simplification of stock-keeping the input pulse values can also be<br />

programmed on site (order variant without surcharge)<br />

✔ St<strong>and</strong>ard possibility to connect temperature sensors Pt 100 or Pt 500 in fourwire<br />

technology <strong>for</strong> quick <strong>and</strong> economic extension of temperature sensor<br />

cables<br />

✔ Removable calibrated integrator module <strong>for</strong> efficient verification exchange<br />

✔ High-resolution <strong>measuring</strong> cycles (2 seconds <strong>for</strong> temperatures, 4 seconds <strong>for</strong><br />

power <strong>and</strong> flowrate)<br />

✔ Back up of <strong>measuring</strong> <strong>and</strong> counting functions of mains-operated instruments<br />

<strong>for</strong> up to 3 months in case of external power failure<br />

✔ Password-protected parameter setting right at the meter itself without any<br />

further peripheral equipment<br />

UK & Irel<strong>and</strong> Enquiries<br />

Sensus Metering Systems<br />

11 The Quadrangle, Abbey Park,<br />

Romsey, Hampshire SO51 9DL UK<br />

T: +44 (0) 1794 526100<br />

F: +44 (0) 1794 526101<br />

Email: info.gb@sensus.com<br />

www.sensus.com<br />

International Enquiries<br />

Sensus Metering Systems GmbH Ludwigshafen<br />

Industriestraße 16,<br />

67063 Ludwigshafen Germany<br />

T: +49 (0) 621-6904-0<br />

F: +49 (0) 621-6904-1409<br />

Email: info.int@sensus.com<br />

www.sensus.com<br />

LH 6110 INT • Page 1/12


Casing conception<br />

Consumption registers<br />

Internal view, type Pt 500,<br />

battery-operated<br />

In addition to the calibrated main register there are two further registers<br />

available:<br />

Register „<strong>chill</strong>" – automatic switch-over between <strong>heat</strong> <strong>and</strong><br />

<strong>chill</strong> metering<br />

This option allows a measurement of the <strong>heat</strong>ing as well as of the cooling<br />

<strong>energy</strong> in combined <strong>heat</strong>ing <strong>and</strong> cooling systems, where the cooling <strong>energy</strong> is<br />

stored in the register "<strong>chill</strong>".<br />

A so-called „automatic switch-over point", which depends on the supply<br />

temperature as well as on the difference between supply <strong>and</strong> return<br />

temperature, specifies when <strong>heat</strong>ing or cooling <strong>energy</strong> is to be measured. Both<br />

values are suitably preset in the factory <strong>and</strong>, in case of need, can be changed<br />

on site according to the system requirements (e.g. in case of concrete core<br />

activation). The integrator allows a direct control of the active settings:<br />

Removable calibrated integrator unit<br />

Example: Switch-over of <strong>heat</strong> to <strong>chill</strong> metering at a<br />

supply flow temperature ≤ 25 °C <strong>and</strong> a concurrent<br />

negative temperature difference of ≥ - 0,15 K<br />

Tariff register 1<br />

Spacious terminal box<br />

This st<strong>and</strong>ard tariff register stores the <strong>heat</strong>ing <strong>and</strong> cooling <strong>energy</strong> respectively,<br />

as well as exceeding or falling below programmable limit values (> or ≤) <strong>for</strong><br />

below system parameters:<br />

• Heat <strong>and</strong> <strong>chill</strong> power resp.<br />

• Flowrate of <strong>heat</strong>ing <strong>and</strong> cooling fluid resp.<br />

• Temperature in the warmer line<br />

• Temperature in the colder line<br />

• Temperature difference<br />

The required settings or changes are possible via optical interface at any time.<br />

• High-quality bevel terminal block<br />

• St<strong>and</strong>ard possibility to connect temperature<br />

sensors in four-wire technology<br />

• Two slots <strong>for</strong> various upgrading modules<br />

• St<strong>and</strong>ard Mini-Bus interface<br />

• Novel cable strain relief with removable preshaped<br />

parts<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 2/12


LC Display<br />

<strong>PolluTherm</strong> is equipped with a com<strong>for</strong>table LC<br />

display with eight-digit main reading line <strong>and</strong> sixfigure<br />

subordinate reading line. Moreover 12<br />

additional symbols support the read-out.<br />

L 1: User menu<br />

• Accumulated consumptions<br />

• Segment test<br />

• Instantaneous values (power, flowrate, temperatures)<br />

• Customer’s reference number<br />

L 2: Target day menu<br />

Consumption values at a programmable annual target day<br />

Segment test<br />

One of many useful features of this conception is<br />

the simultaneous display of stored consumption<br />

values together with the associated date – an<br />

important contribution to avoid misreadings:<br />

L 3: Archive menu<br />

Rolling monthly storage of the following values <strong>for</strong> the last 16 months:<br />

• Consumptions<br />

• Volumina of the <strong>heat</strong>ing resp.<strong>chill</strong>ing liquid<br />

• Maxima <strong>for</strong> power <strong>and</strong> flowrate<br />

• Potential failure hours<br />

L 4: Service menu<br />

• Maximum values since operational start-up<br />

• Date <strong>and</strong> time<br />

Example: monthly value <strong>for</strong> <strong>heat</strong>ing <strong>energy</strong><br />

Wherever it is appropriate, the display shows<br />

additional letters in the six-figure subordinate line in<br />

order to increase the read-out com<strong>for</strong>t:<br />

• Next target day<br />

• Operation days<br />

• M-Bus addresses<br />

L 5: Control menu<br />

• Set tariff parameters<br />

• Switch-over point between <strong>heat</strong> <strong>and</strong> <strong>chill</strong> metering<br />

• Correction factor in case of using water-antifreeze-mixtures<br />

L 6: Parameter menu<br />

Example: M-Bus secondary address<br />

The available display items are clearly structured in 6<br />

menus <strong>and</strong> include in substance:<br />

This is the menu where, among other possibilities, following items can be set<br />

right at the meter itself (protected by password):<br />

• M-Bus addresses<br />

• Customer’s reference number<br />

• Date <strong>and</strong> time<br />

• Next target date<br />

• Reset of maximum values<br />

For details of the complete scope of display possibilities please refer to the<br />

installation <strong>and</strong> operation instructions MH 6110 INT.<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 3/12


Upgrade plugin modules<br />

For electronic reading <strong>and</strong> connection to building<br />

automation systems a variety of anytime upgrade<br />

plugin modules are available <strong>for</strong> the <strong>PolluTherm</strong>:<br />

M-Bus according to EN 1434-3<br />

Order number: 68504020<br />

This plugin module allows reading the meter via its<br />

primary or secondary address with an M-Bus level<br />

converter (300 <strong>and</strong> 2400 Baud, automatic<br />

recognition). The secondary address is preset in the<br />

factory to the eight-digit meter serial number. If<br />

required both M-Bus addresses can be changed at<br />

the meter itself. Because of the short updating time<br />

<strong>for</strong> temperatures of 2 secons only as well as <strong>for</strong><br />

power <strong>and</strong> flowrate values of 4 seconds only, the<br />

mains-operated <strong>PolluTherm</strong> is excellently suitable <strong>for</strong><br />

the connection to district <strong>heat</strong>ing regulators.<br />

Suitable read-out software:<br />

DOKOM CS (leaflet LS 1300)<br />

Suitable read-out hardware:<br />

See leaflet LS 1100<br />

Remote reading pulses <strong>energy</strong><br />

For battery-operated <strong>PolluTherm</strong><br />

Order number: 68503922<br />

Remote reading pulses <strong>energy</strong> <strong>and</strong> volume<br />

For mains-operated <strong>PolluTherm</strong><br />

Order number: 68503920<br />

Those two plugin modules provide potential-free <strong>and</strong><br />

bounce-free remote reading pulses, which can be<br />

added up by a remote totalizer.<br />

The pulse values depend on the size of the connected flow sensor:<br />

Input pulse value<br />

in l<br />

0.25 or 1 2.5 or 10 25 or 100<br />

250, 1.000 or<br />

10,000<br />

Display of the<br />

integrator with decimal<br />

digits <strong>for</strong> MWh, GJ <strong>and</strong><br />

00000.000 000000.00 0000000.0 00000000<br />

m 3<br />

Pulse value in case of<br />

remote <strong>energy</strong> reading<br />

in MWh<br />

0.001 0.01 0.1 1<br />

Pulse value in case of<br />

remote volume reading 0.001 0.01 0.1 1<br />

in m 3<br />

M-Bus with two inputs <strong>for</strong> external consumption meters<br />

Order number: 68504686<br />

This plugin module allows the additional connection of up to two external<br />

consumption meters (cold water, warm water, electricity, gas, „others") with<br />

passive remote reading pulse output (reed switch, open collector). The<br />

consumptions of those meters can then be read out via the M-Bus or Mini-Bus<br />

interface of the <strong>PolluTherm</strong>.<br />

Required pulse duration:<br />

Pulse input frequency:<br />

Terminal voltage:<br />

> 125 ms<br />

≤ 3 Hz<br />

3 V<br />

Closing time:<br />

Bounce time:<br />

Max. voltage:<br />

Max. power:<br />

125 ms<br />

none<br />

28 V DC or AC<br />

0.1 A<br />

USB interface<br />

Order number: 68504688<br />

This plugin unit allows the connection of the meter to a USB interface of a PC<br />

or a notebook.<br />

USB-Port: 1.1 or 2.0<br />

Connection plug:<br />

Cable length:<br />

type A<br />

ca. 1.5 m<br />

Baud rate: ≤ 19,200<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 4/12


Further options<br />

Mini-Bus interface<br />

This st<strong>and</strong>ard interface offers the following<br />

possibilities of application:<br />

Connection of an inductive read-out point (MiniPad,<br />

order number: 182079) with an up to 50 m long cable.<br />

A typical application is the quick <strong>and</strong> accurate remote<br />

reading of single meters in <strong>measuring</strong> sites with<br />

difficult access.<br />

Suitable read-out systems:<br />

• MiniReader, leaflet LS 3200<br />

• DOKOM Mobil, leaflet LS 3400<br />

Integration of <strong>PolluTherm</strong> into the radio system<br />

Sensus((S))cout. For details of this system please<br />

refer to leaflet LS 3300.<br />

Integrated data logger<br />

By this factory-set option the following values are<br />

stored in a selectable time interval (3 to 1440<br />

minutes):<br />

• Consumption (incl. tariff consumption <strong>and</strong>, if<br />

applicable, consumptions of the two external<br />

meters)<br />

• Volume of the <strong>heat</strong>ing <strong>and</strong> cooling liquid resp.<br />

• Flowrate of the <strong>heat</strong>ing <strong>and</strong> cooling liquid<br />

• Heat <strong>and</strong> <strong>chill</strong> power resp.<br />

• Temperature in the warmer line<br />

• Temperature in the colder line<br />

• Temperature difference<br />

• Potential failure hours<br />

The capacity is 1260 data records, i.e. <strong>for</strong> example<br />

covering ca. 52 days in case of hourly logger<br />

intervals.<br />

The logger values are read out with the service<br />

software MiniCom, version 3.6.0.28 or higher.<br />

Technical data<br />

Temperature <strong>measuring</strong> range<br />

Temperature difference<br />

Cut-off threshold<br />

Measuring accuracy<br />

Updating times <strong>and</strong> integration cycles<br />

resp.<br />

Temperatures<br />

Flowrate<br />

Power<br />

Energy<br />

Volume<br />

Buffering of <strong>measuring</strong> <strong>and</strong> counting<br />

functions in case of power failure<br />

Optical data interface<br />

Permissible environmental<br />

temperature<br />

Battery lifetime<br />

Electromagnetic environment class<br />

1 ... 180 °C<br />

(-20 … 180 °C uncalibrated)<br />

3 ... 150 K<br />

0.15 K<br />

better than<br />

+ 1.5 % <strong>for</strong> 3 K < ∆t < 20 K<br />

+ 1 % <strong>for</strong> 20 K < ∆t<br />

2 sec<br />

4 sec<br />

4 sec<br />

4 sec (16 sec *)<br />

4 sec (16 sec *)<br />

* <strong>for</strong> battery-operated instruments<br />

≤ 3 months<br />

Physical acc. to EN 61107<br />

Data telegram acc. to EN 1434-3<br />

5 ... 55 °C<br />

6 years + 1 year storing reserve<br />

optional: 10 years<br />

A acc. to EN 1434-4 (2003)<br />

resp. E1 acc. MID<br />

Storing temperature - 10 °C ... + 60 °C<br />

Dimensions (wall mounting)<br />

Wall mounting<br />

Suitable types of temperature sensors<br />

Input pulse values <strong>for</strong> flow sensors<br />

Type of the pulsers<br />

Input pulse frequency<br />

ca. 125 x 159 x 52 mm<br />

(WxHxD)<br />

C-rail<br />

Pt 500 <strong>and</strong> Pt 100 resp.<br />

Two- or four-wire connection<br />

1 / 10 / 100 / 1,000 / 10,000 /<br />

0.25 / 2.5 / 25 or 250 litres<br />

Reed switch, open collector<br />

≤ 3 Hz<br />

Protection class IP 54<br />

Dimensional drawings<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 5/12


Order details <strong>for</strong> st<strong>and</strong>ard integrator sub-unit<br />

• Physical unit of the <strong>heat</strong> quantity in MWh, adjusted <strong>for</strong> flow sensors in the colder line<br />

Description<br />

Order no.<br />

<strong>for</strong> complete instrument<br />

(incl. outer casing)<br />

Order no.<br />

<strong>for</strong> internal integrator module (<strong>for</strong><br />

verification exchange)<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 500<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 100<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 122 KM B<br />

310E 132 KM B<br />

310E 142 KM B<br />

310E 102 KM B<br />

310E 222 KM B<br />

310E 232 KM B<br />

310E 242 KM B<br />

310E 202 KM B<br />

310E M22 KM B<br />

310E M32 KM B<br />

310E M42 KM B<br />

310E M02 KM B<br />

310E N22 KM B<br />

310E N32 KM B<br />

310E N42 KM B<br />

310E N02 KM B<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 500<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 100<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 120 KM B<br />

310E 130 KM B<br />

310E 140 KM B<br />

310E 100 KM B<br />

310E 221 KM B<br />

310E 231 KM B<br />

310E 241 KM B<br />

310E 201 KM B<br />

310E M20 KM B<br />

310E M30 KM B<br />

310E M40 KM B<br />

310E M00 KM B<br />

310E N21 KM B<br />

310E N31 KM B<br />

310E N41 KM B<br />

310E N01 KM B<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 6/12


Order details <strong>for</strong> integrator sub-unit<br />

• Physical unit of the <strong>heat</strong> quantity in MWh, adjusted <strong>for</strong> flow sensors in the colder line<br />

• In addition: Automatic switch-over between <strong>heat</strong> <strong>and</strong> <strong>chill</strong> metering<br />

Description<br />

Order no.<br />

<strong>for</strong> complete instrument (incl. outer<br />

casing)<br />

Order no.<br />

<strong>for</strong> internal integrator module (<strong>for</strong><br />

verification exchange)<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 500<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 100<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 122 KO B<br />

310E 132 KO B<br />

310E 142 KO B<br />

310E 102 KO B<br />

310E 222 KO B<br />

310E 232 KO B<br />

310E 242 KO B<br />

310E 202 KO B<br />

310E M22 KO B<br />

310E M32 KO B<br />

310E M42 KO B<br />

310E M02 KO B<br />

310E N22 KO B<br />

310E N32 KO B<br />

310E N42 KO B<br />

310E N02 KO B<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 500<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 100<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 120 KO B<br />

310E 130 KO B<br />

310E 140 KO B<br />

310E 100 KO B<br />

310E 221 KO B<br />

310E 231 KO B<br />

310E 241 KO B<br />

310E 201 KO B<br />

310E M20 KO B<br />

310E M30 KO B<br />

310E M40 KO B<br />

310E M00 KO B<br />

310E N21 KO B<br />

310E N31 KO B<br />

310E N41 KO B<br />

310E N01 KO B<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 7/12


Order details <strong>for</strong> integrator sub-unit<br />

• Physical unit of the <strong>heat</strong> quantity in MWh, adjusted <strong>for</strong> flow sensors in the colder line<br />

• In addition: Integrated data logger<br />

Description<br />

Order no.<br />

<strong>for</strong> complete instrument (incl. outer<br />

casing)<br />

Order no.<br />

<strong>for</strong> internal integrator module (<strong>for</strong><br />

verification exchange)<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 500<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 100<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 422 KM B<br />

310E 432 KM B<br />

310E 442 KM B<br />

310E 402 KM B<br />

310E 522 KM B<br />

310E 532 KM B<br />

310E 542 KM B<br />

310E 502 KM B<br />

310E O22 KM B<br />

310E O32 KM B<br />

310E O42 KM B<br />

310E O02 KM B<br />

310E P22 KM B<br />

310E P32 KM B<br />

310E P42 KM B<br />

310E P02 KM B<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 500<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 100<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 420 KM B<br />

310E 430 KM B<br />

310E 440 KM B<br />

310E 400 KM B<br />

310E 521 KM B<br />

310E 531 KM B<br />

310E 541 KM B<br />

310E 501 KM B<br />

310E O20 KM B<br />

310E O30 KM B<br />

310E O40 KM B<br />

310E O00 KM B<br />

310E P21 KM B<br />

310E P31 KM B<br />

310E P41 KM B<br />

310E P01 KM B<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 8/12


Order details <strong>for</strong> integrator sub-unit<br />

• Physical unit of the <strong>heat</strong> quantity in MWh, adjusted <strong>for</strong> flow sensors in the colder line<br />

• In addition: Automatic switch-over between <strong>heat</strong> <strong>and</strong> <strong>chill</strong> metering<br />

• In addition: Integrated data logger<br />

Description<br />

Order no.<br />

<strong>for</strong> complete instrument (incl. outer<br />

casing)<br />

Order no.<br />

<strong>for</strong> internal integrator module (<strong>for</strong><br />

verification exchange)<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 500<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> N Pt 100<br />

Mains-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 422 KO B<br />

310E 432 KO B<br />

310E 442 KO B<br />

310E 402 KO B<br />

310E 522 KO B<br />

310E 532 KO B<br />

310E 542 KO B<br />

310E 502 KO B<br />

310E O22 KO B<br />

310E O32 KO B<br />

310E O42 KO B<br />

310E O02 KO B<br />

310E P22 KO B<br />

310E P32 KO B<br />

310E P42 KO B<br />

310E P02 KO B<br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 500<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 500<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

<strong>Integrator</strong> <strong>PolluTherm</strong> B Pt 100<br />

Battery-operated version <strong>for</strong> temperature sensors Pt 100<br />

Input pulse value: 10 litres<br />

Input pulse value: 100 litres<br />

Input pulse value: 1000 litres<br />

Input pulse value: programmable on site<br />

Further pulse values on dem<strong>and</strong><br />

310E 420 KO B<br />

310E 430 KO B<br />

310E 440 KO B<br />

310E 400 KO B<br />

310E 521 KO B<br />

310E 531 KO B<br />

310E 541 KO B<br />

310E 501 KO B<br />

310E O20 KO B<br />

310E O30 KO B<br />

310E O40 KO B<br />

310E O00 KO B<br />

310E P21 KO B<br />

310E P31 KO B<br />

310E P41 KO B<br />

310E P01 KO B<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 9/12


Order details <strong>for</strong> accessories<br />

Description<br />

Order no.<br />

Power supply unit 230 V AC<br />

<strong>for</strong> modification from battery to mains operation<br />

68504679<br />

Junction box <strong>for</strong> four-wire extension of temperature sensor cables 88599001<br />

Adapter plate to fasten <strong>PolluTherm</strong> on wall adapters<br />

or boreholes of earlier integrator types<br />

(type B/N 101, B/N 501, B/N 100, B/N 500)<br />

68503892<br />

Upgrading plugin units<br />

Remote reading of <strong>energy</strong> <strong>and</strong> volume pulses *<br />

<strong>for</strong> mains-operated <strong>PolluTherm</strong> only<br />

68503920<br />

Remote reading of <strong>energy</strong> pulses<br />

<strong>for</strong> battery-operated <strong>PolluTherm</strong> only<br />

68503922<br />

M-Bus interface acc. to EN 1434-3 * 68504020<br />

M-Bus interface acc. to EN 1434-3 with two inputs <strong>for</strong> external consumption meters with<br />

remote reading output (e.g. water or gas meters)<br />

68504686<br />

Accessories <strong>for</strong> data communication<br />

USB interface <strong>for</strong> connection to PC or notebook 68504688<br />

Optical data coupler with nine-pole RS 232 connection 04410230<br />

Optical data coupler with USB connection<br />

On dem<strong>and</strong><br />

Inductive readout point MiniPad 182079<br />

Inductive data coupler MDK with nine-pole<br />

RS 232 connection<br />

88004082<br />

* Those plugin units are compatible to the <strong>for</strong>mer version of <strong>PolluTherm</strong> <strong>and</strong> can, as far as already available, reused in the present<br />

<strong>PolluTherm</strong>.<br />

Regarding the plugin unit <strong>for</strong> remote reading of <strong>energy</strong> pulses (order no. 68503922) we recommend to use a new plugin unit after expiry<br />

of the verification period because of the soldered-on battery.<br />

For further accessories please refer to our present price liste <strong>for</strong> <strong>heat</strong> / <strong>chill</strong> meters <strong>and</strong> system technology.<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 10/12


Order details <strong>for</strong> complete <strong>measuring</strong> points<br />

A complete <strong>measuring</strong> point includes following components:<br />

• <strong>Integrator</strong> <strong>PolluTherm</strong> (battery- or mains-operated)<br />

• One pair of temperature sensors Pt 500 or Pt 100<br />

• One pair of wells (stainless steel V4A)<br />

• Flow sensor with volume pulse output<br />

For the order numbers <strong>for</strong> the complete kits (including the a.m. components) please refer to the present price list <strong>for</strong> <strong>heat</strong> / <strong>chill</strong><br />

meters.<br />

Suitable flow sensors<br />

Nominal flowrate from 1.5 to 10 m_/h (QN or Qp 1.5 to 10), nominal size DN 20 to 40:<br />

Multi-jet dry-dial meter type AN 130, leaflet: LH 7100<br />

Type Qp (QN) Overall length (mm) / PN<br />

nominal size/width<br />

With screwed ends <strong>for</strong> horizontal mounting position<br />

1.5 190 / R 3/4"<br />

2.5 190 / R 3/4"<br />

3.5 260 / R 1" 16<br />

6 260 / R 1"<br />

10 300 / R 1 1/2"<br />

Flanged <strong>for</strong> horizontal mounting position<br />

1.5 190 / DN 20<br />

2.5 190 / DN 20<br />

3.5 260 / DN 25 16<br />

6 260 / DN 25<br />

10 300 / DN 40<br />

1.5 190 / DN 20<br />

2.5 190 / DN 20<br />

3.5 260 / DN 25 25<br />

6 260 / DN 25<br />

10 300 / DN 40<br />

For vertical mounting position in down pipe<br />

1.5 105 / R 3/4"<br />

2.5 105 / R 3/4"<br />

3.5 150 / R 1" 16<br />

6 150 / R 1"<br />

10 200 / R 1 1/2"<br />

For vertical mounting position in riser pipe<br />

1.5 105 / R 3/4"<br />

2.5 105 / R 3/4"<br />

3.5 150 / R 1" 16<br />

6 150 / R 1"<br />

10 200 / R 1 1/2"<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 11/12


Order details <strong>for</strong> complete <strong>measuring</strong> points<br />

Nominal flow from 15 to 600 m 3 /h (QN or Qp 15 to 600), nominal size DN 50 to 300:<br />

Woltman type WS, QN 15 to 150, <strong>for</strong> horizontal mounting position, PN 16 / 40, leaflet LB 4200<br />

Woltman type WP, QN 250 to 600, <strong>for</strong> horizontal mounting position, PN 16, leaflet LB 4100<br />

Woltman type WP, QN 15 to 600, <strong>for</strong> riser <strong>and</strong> down pipes, PN 16, leaflet LB 4100<br />

Woltman type WP, QN 250 to 600, <strong>for</strong> horizontal mounting position, PN 25 / 40, leaflet LB 5200<br />

Woltman type WP, QN 15 to 600, <strong>for</strong> riser <strong>and</strong> down pipes, PN 25 / 40, leaflet LB 5200<br />

Type Qp (QN) DN PN Overall length (mm)<br />

Flanged <strong>for</strong> horizontal mounting position<br />

15 50 270<br />

25 65 300<br />

40 80 16 300<br />

60 100 360<br />

150 150 500<br />

15 50 270<br />

25 65 300<br />

40 80 40 300<br />

60 100 360<br />

150 150 500<br />

Flanged <strong>for</strong> vertical mounting position in down or riser pipe<br />

15 50 200<br />

25 65 200<br />

40 80 225<br />

16<br />

60 100 250<br />

100 125 250<br />

150 150 300<br />

15 50 200<br />

40 80 225<br />

40<br />

60 100 250<br />

150 150 300<br />

Flanged <strong>for</strong> horizontal <strong>and</strong> vertical mounting position (down or riser pipe)<br />

250 200 350<br />

400 250 16 450<br />

600 300 500<br />

250 200 40 350<br />

400 250 450<br />

25<br />

600 300 500<br />

LH 6110 INT / 001-0407 • Subject to change without notice<br />

Certified according to ISO 9001<br />

Quality Management System ÖQS Reg.no. 3496/0<br />

<strong>PolluTherm</strong><br />

LH 6110 INT • Page 12/12