05.03.2015 Views

SCC CONTROL DAMPERS FOR CIRCULAR DUCT - Madel

SCC CONTROL DAMPERS FOR CIRCULAR DUCT - Madel

SCC CONTROL DAMPERS FOR CIRCULAR DUCT - Madel

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>SCC</strong> <strong>CONTROL</strong> <strong>DAMPERS</strong> <strong>FOR</strong> <strong>CIRCULAR</strong> <strong>DUCT</strong><br />

The <strong>SCC</strong> series dampers are designed to be used for altering the<br />

flow volume rate and pressure in air-conditioning, ventilation and<br />

heating systems. Airtight damper suitable for circular duct mounting.<br />

1 09/04


<strong>SCC</strong> - MA<br />

L<br />

A B<br />

Dn 40<br />

48<br />

48<br />

Dn<br />

CLASSIFICATION<br />

<strong>SCC</strong>-R /MA Circular damper with manual<br />

control lever.<br />

<strong>SCC</strong>-E /MA Circular damper with air<br />

tightness joint and manual control lever.<br />

D Dn L A B<br />

100 98 265 105 160<br />

125 123 265 105 160<br />

150 148 265 105 160<br />

160 158 265 105 160<br />

200 198 295 130 165<br />

250 248 335 145 190<br />

315 313 345 155 190<br />

<strong>SCC</strong>-R /MO Circular damper with special<br />

axle to motorise.<br />

<strong>SCC</strong>-E /MO Circular damper with air<br />

tightness joint and special axle to<br />

motorise.<br />

<strong>SCC</strong> - MO<br />

48<br />

A<br />

L<br />

B<br />

48<br />

Dn<br />

50<br />

Ø15<br />

Dn<br />

D Dn L A B<br />

100 98 265 105 160<br />

125 123 265 105 160<br />

150 148 265 105 160<br />

160 158 265 105 160<br />

200 198 295 130 165<br />

250 248 335 145 190<br />

315 313 345 155 190<br />

2 09/04


MATERIAL<br />

Casing and blade made from galvanised<br />

steel and bearings from rubber.<br />

ADDITIONAL ACCESSORIES<br />

TN08 -24 / 230 Servomotor at 24v or<br />

230v.<br />

FIXING SYSTEMS<br />

The casing of <strong>SCC</strong> damper has been<br />

designed in order to be jointed in circular<br />

ducts.<br />

FINISHES<br />

Galvanised steel.<br />

3 09/04


<strong>SCC</strong><br />

SERIES<br />

NECK VELOCITY, PRESSURE LOSS AND SOUND POWER LEVEL.<br />

NECK AREA m2.<br />

D<br />

100<br />

125<br />

160<br />

200<br />

250<br />

315<br />

Ak(m2)<br />

0,0078<br />

0,0123<br />

0,0201<br />

0,0314<br />

0,0491<br />

0,0779<br />

AK (m2)<br />

1<br />

0,1<br />

0,09<br />

0,08<br />

0,07<br />

0,06<br />

0,05<br />

0,04<br />

0,03<br />

0,025<br />

0,02<br />

1.5 2<br />

Q (m3/h)<br />

3<br />

V k (m/s)<br />

4 5 6 7 8 9 10 12 15 17<br />

700<br />

600<br />

500<br />

400<br />

2500<br />

2000<br />

1600<br />

1300<br />

1100<br />

900<br />

20<br />

0,015<br />

300<br />

250<br />

CORRECTION FACTOR <strong>FOR</strong> DPt : Kp<br />

0 15 30<br />

Kp 1 1,5 8<br />

DPt = Kp x DPt<br />

45<br />

20<br />

60<br />

140<br />

DPt (Pa)<br />

0,01<br />

0,008<br />

0,006<br />

0,005<br />

100<br />

80<br />

60<br />

40<br />

30<br />

20<br />

15<br />

50<br />

70<br />

100<br />

200<br />

150<br />

L wa1 = ( dB (A))<br />

35 40<br />

45 50<br />

100<br />

250<br />

200<br />

160<br />

125<br />

315<br />

10<br />

30<br />

5<br />

4<br />

3<br />

2<br />

1<br />

1<br />

1.5 2 3 4<br />

V k (m/s)<br />

5 6 7 8 9 10 12 15 17 20<br />

4<br />

CD-GR1-09/04