<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />

2.3 Description of the inputs<br />

and outputs<br />

<strong>Universal</strong> <strong>Interfaces</strong><br />

<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />

<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />

Grey core: Positive scanning voltage<br />

During operation as an input, the grey core makes the positive, pulsed<br />

scanning voltage available.<br />

Coloured core: Control of the channel<br />

During operation as an input, the status of the contact is read out via the<br />

coloured cores.<br />

During operation as an output, the coloured core makes the positive output<br />

voltage available.<br />

The following table allocates the colours to the channels:<br />

brown Channel A<br />

red<br />

Channel B<br />

orange* Channel C<br />

yellow* Channel D<br />

*only for <strong>US</strong>/U <strong>4.2</strong><br />

Black core: Negative reference potential<br />

During operation as an output, the black core makes the negative reference<br />

potential available.<br />

Important:<br />

The inputs and outputs do not have electrical isolation<br />

to the <strong>EIB</strong> bus voltage (SELV). The SELV criteria only enable<br />

the connection of floating contacts with safety separation.<br />

2.4 Assembly and installation<br />

The device can in mounted in any position. Any cores that are not required<br />

must be insulated.<br />