6.8 Counting energy values Input 1 is connected to the S0 output of an energy consumption meter<br />

(100 pulses/kWh). The 4 byte counter value is displayed on the bus as Wh.<br />

It is sent on the bus every 30 seconds and if the value changes by 100 Wh.<br />

Input 1<br />

<strong>Universal</strong> interface<br />

<strong>US</strong>/U x.2<br />

Telegr. counter value 4 bytes 1/1/1<br />

Request counter values 1/1/2<br />

Differential counter overflow 1/1/2<br />

Parameter settings for input 1:<br />

100 pulses per kWh means 1 pulse per 10 Wh. The counter is therefore<br />

increased every impulse by the value 10 (factor = 10).<br />

The differential counter generates an overflow every 100 Wh, which in turn<br />

requests a new counter value.<br />