01.03.2015 Views

ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster

ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster

ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />

2.2 Device connection<br />

<strong>Universal</strong> <strong>Interfaces</strong><br />

<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />

<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />

During operation as an input, the scanned contact is connected between<br />

the grey core and the coloured core.<br />

During operation as an output, the load (LED or electronic relay) is connected<br />

between the black and the coloured core. The coloured core represents<br />

the positive output voltage.<br />

Connection of a floating push button/switch<br />

coloured / farbig<br />

grey / grau<br />

Connection of an electronic relay<br />

coloured / farbig<br />

black /<br />

schwarz<br />

Connection of an LED<br />

coloured / farbig<br />

2 mA<br />

black / schwarz<br />

Note:<br />

When connecting to an S0 impulse output (e.g. an energy<br />

consumption meter), it must be ensured that it is electrically<br />

isolated from the mains. The correct polarity should also be<br />

observed (“+” on the grey core).<br />

5