<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
2.2 Device connection<br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
During operation as an input, the scanned contact is connected between<br />
the grey core and the coloured core.<br />
During operation as an output, the load (LED or electronic relay) is connected<br />
between the black and the coloured core. The coloured core represents<br />
the positive output voltage.<br />
Connection of a floating push button/switch<br />
coloured / farbig<br />
grey / grau<br />
Connection of an electronic relay<br />
coloured / farbig<br />
black /<br />
schwarz<br />
Connection of an LED<br />
coloured / farbig<br />
2 mA<br />
black / schwarz<br />
Note:<br />
When connecting to an S0 impulse output (e.g. an energy<br />
consumption meter), it must be ensured that it is electrically<br />
isolated from the mains. The correct polarity should also be<br />
observed (“+” on the grey core).<br />