ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
Scene control via 5 separate objects<br />
Push button 1 and push button 2 control shutter 1 and lamp 1. A short operation<br />
recalls the scene. After a long operation, the current shutter position and<br />
the brightness value are stored. Both push buttons store different scene<br />
values.<br />
Linking the group addresses:<br />
Push button 1 Shutter 1<br />
<strong>Universal</strong> interface<br />
<strong>US</strong>/U x.2<br />
Telegr. value actuator group A 1/1/1<br />
Telegr. value actuator group B 1/1/2<br />
Shutter actuator *<br />
JA/S …<br />
1/1/1 Move to position 0…255<br />
1/1/2 Adjust lamella 0…255<br />
Telegr. value actuator group C 1/1/3<br />
Push button 2 Lamp 1<br />
<strong>Universal</strong> interface<br />
<strong>US</strong>/U x.2<br />
Telegr. value actuator group A 1/1/1<br />
Dimming actuator<br />
UD/S 2.300.1<br />
1/1/3 Brightness value/status<br />
Telegr. value actuator group B 1/1/2<br />
Telegr. value actuator group C 1/1/3<br />
Parameter settings for push button 1 and push button 2:<br />
* This function is only available for shutter actuators that can move into position<br />
via an 8 bit value.<br />
54