<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />

<strong>Universal</strong> <strong>Interfaces</strong><br />

<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />

<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />

The following example clarifies this:<br />

100%<br />

40%<br />

0%<br />

t ON<br />

t OFF<br />

t<br />

T<br />

CYC<br />

During t ON , the valve is triggered with OPEN (“ON phase”). During t OFF ,<br />

the valve is triggered with CLOSE (“OFF phase”). Due to tON = 0.4 x T CYC ,<br />

the valve is set at approx. 40%. T CYC is the so-called PWM cycle time for<br />

continuous control.<br />

The actuator can trigger specific special positions during “Forced positioning”,<br />

“Valve purge” and “Safety position”. The following diagram provides<br />

an overview:<br />

Start<br />

Is forced<br />

positioning<br />

active?<br />

yes<br />

Trigger forced<br />

positioning<br />

no<br />

Is valve<br />

purge<br />

active?<br />

yes<br />

Valve opened to<br />

maximum for<br />

duration of valve<br />

purge<br />

no<br />

Is fault<br />

mode<br />

active?<br />

yes<br />

Trigger safety<br />

position<br />

no<br />

1 bit<br />

Type of<br />

control<br />

8 bit<br />

Output follows<br />

object “Telegr.<br />

switch”<br />

Control acc. to<br />

object “Control<br />

value (PWM)”<br />

44