<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
Object: “8 bit scene”, 8 bit<br />
This object is visible if the control is carried out via an “8 bit scene”. It sends<br />
a scene number and the information as to whether a scene should be recalled<br />
or the current scene should be stored. The storing of the scene is carried<br />
out in the actuator.<br />
Telegram code in bits: MxSSSSSS<br />
M: 0 – Scene is recalled<br />
1 – Scene is stored<br />
x: Not used<br />
S: Number of the scene (0…63)<br />
Object: “Store scene”, 1 bit (EIS 1)<br />
This object can be used to trigger the saving of a scene via the bus or to<br />
indicate that the scene has been stored. The function depends on the method<br />
of storing the scene.<br />
Refer to the description of the parameter “Store scene” for more detailed<br />
information.<br />