<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />

<strong>Universal</strong> <strong>Interfaces</strong><br />

<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />

<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />

Object: “8 bit scene”, 8 bit<br />

This object is visible if the control is carried out via an “8 bit scene”. It sends<br />

a scene number and the information as to whether a scene should be recalled<br />

or the current scene should be stored. The storing of the scene is carried<br />

out in the actuator.<br />

Telegram code in bits: MxSSSSSS<br />

M: 0 – Scene is recalled<br />

1 – Scene is stored<br />

x: Not used<br />

S: Number of the scene (0…63)<br />

Object: “Store scene”, 1 bit (EIS 1)<br />

This object can be used to trigger the saving of a scene via the bus or to<br />

indicate that the scene has been stored. The function depends on the method<br />

of storing the scene.<br />

Refer to the description of the parameter “Store scene” for more detailed<br />