ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
Object: “Telegr. value (…)” (various types)<br />
This communication object sends a value on the bus when the contact<br />
is opened or closed. The value and data types can be freely selected<br />
in the parameters.<br />
When there is a distinction between a short and long operation, 2 objects are<br />
visible per input. One object only transmits a value after a short operation<br />
while the other object only sends after a long operation.<br />
Note:<br />
By default, the “Write” flag is deleted for the value objects<br />
(except for the 1 bit objects). The object value cannot thus be<br />
modified via the <strong>EIB</strong>. If this function is required, the “Write” flag<br />
must be set in ETS. On bus voltage recovery, the object value<br />
is overwritten with the parameterised value.<br />
22