ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
ABB i-bus® EIB Universal Interfaces US/U 4.2 US/U ... - WindowMaster
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
1 switch operation, moving<br />
Start of operation Alternately “MOVE UP” or “MOVE DOWN”<br />
End of operation STOP / lamella adjustment*<br />
* Note: If the actuator is in a limit position (see “Upper limit position”<br />
or “Lower limit position”), the direction of movement is<br />
preset.<br />
In 1 push button/switch operation mode, the last direction<br />
of movement is determined via the last update of the object<br />
“Telegr. shutter UP/DOWN”.<br />
2 push button, standard<br />
Short operation<br />
Long operation<br />
“STOP / lamella UP” or “STOP / lamella DOWN”<br />
(can be parameterised)<br />
“MOVE UP” or “MOVE DOWN” (can be parameterised)<br />
2 switch operation, moving (shutter)<br />
Start of operation “MOVE UP” or “MOVE DOWN” (can be parameterised)<br />
End of operation “STOP / lamella UP” or “STOP / lamella DOWN”<br />
2 push button, moving (shutter)<br />
On operation<br />
The following commands are sent in sequence:<br />
… -> “MOVE UP” -> “STOP / lamella UP” -> … or<br />
“MOVE DOWN” -> “STOP / lamella DOWN” -> …<br />
2 push button, stepping<br />
On operation<br />
“STOP / lamella UP” or “STOP / lamella DOWN”<br />
Parameter: “Connected contact type”<br />
This parameter defines whether the contact at the input is a normally open<br />
contact or a normally closed contact.<br />
Parameter: “Reaction on operation”<br />
This parameter is visible if there is no distinction between a short and long<br />
operation. It can be set whether the input triggers commands for upward<br />
movement (“UP”) or downward movement (“DOWN”).<br />
Parameter: “Reaction on short operation” or<br />
“Reaction on long operation”<br />
This parameter is visible in all operating modes in which there is a distinction<br />
between a short and long operation. It can be set whether the input triggers<br />
commands for upward movement (“UP”) or downward movement (“DOWN”).<br />
Parameter: “Long operation after”<br />
This parameter is visible in all operating modes in which there is a distinction<br />
between a short and long operation. The period which defines a long operation<br />
is set here.<br />
18