<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />

<strong>Universal</strong> <strong>Interfaces</strong><br />

<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />

<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />

1 switch operation, moving<br />

Start of operation Alternately “MOVE UP” or “MOVE DOWN”<br />

End of operation STOP / lamella adjustment*<br />

* Note: If the actuator is in a limit position (see “Upper limit position”<br />

or “Lower limit position”), the direction of movement is<br />

preset.<br />

In 1 push button/switch operation mode, the last direction<br />

of movement is determined via the last update of the object<br />

“Telegr. shutter UP/DOWN”.<br />

2 push button, standard<br />

Short operation<br />

Long operation<br />

“STOP / lamella UP” or “STOP / lamella DOWN”<br />

(can be parameterised)<br />

“MOVE UP” or “MOVE DOWN” (can be parameterised)<br />

2 switch operation, moving (shutter)<br />

Start of operation “MOVE UP” or “MOVE DOWN” (can be parameterised)<br />

End of operation “STOP / lamella UP” or “STOP / lamella DOWN”<br />

2 push button, moving (shutter)<br />

On operation<br />

The following commands are sent in sequence:<br />

… -> “MOVE UP” -> “STOP / lamella UP” -> … or<br />

“MOVE DOWN” -> “STOP / lamella DOWN” -> …<br />

2 push button, stepping<br />

On operation<br />

“STOP / lamella UP” or “STOP / lamella DOWN”<br />

Parameter: “Connected contact type”<br />

This parameter defines whether the contact at the input is a normally open<br />

contact or a normally closed contact.<br />

Parameter: “Reaction on operation”<br />

This parameter is visible if there is no distinction between a short and long<br />

operation. It can be set whether the input triggers commands for upward<br />

movement (“UP”) or downward movement (“DOWN”).<br />

Parameter: “Reaction on short operation” or<br />

“Reaction on long operation”<br />

This parameter is visible in all operating modes in which there is a distinction<br />

between a short and long operation. It can be set whether the input triggers<br />

commands for upward movement (“UP”) or downward movement (“DOWN”).<br />

Parameter: “Long operation after”<br />

This parameter is visible in all operating modes in which there is a distinction<br />

between a short and long operation. The period which defines a long operation<br />

is set here.<br />

18