<strong>ABB</strong> i-bus ® <strong>EIB</strong><br />
4.5.2 Communication objects<br />
<strong>Universal</strong> <strong>Interfaces</strong><br />
<strong>US</strong>/U 2.2, GH Q631 0074 R0111<br />
<strong>US</strong>/U <strong>4.2</strong>, GH Q631 0070 R0111<br />
Object: “Telegr. switch”, 1 bit (EIS 1)<br />
This object is visible if the value “Switching and dimming” has been set in the<br />
parameter “Dimming functionality”.<br />
Depending on the parameter setting, the object value can be switched on,<br />
off or toggled after a short operation. For dimming with 1 button, this object<br />
should be linked with the status response of the dimming actuator as a nonsending<br />
group address. The input is thus informed about the current switching<br />
status of the dimming actuator.<br />
Object: “Telegr. dimming”, 4 bit (EIS 2)<br />
A long operation of the input causes a dim brighter or dim darker command<br />
to be sent on the bus via this object. A stop command is sent at the end<br />
of this operation.<br />